HomeMy WebLinkAboutNC0025321_BCI_20210923
SENT VIA ELECTRONIC MAIL ONLY: NO HARD COPY WILL BE MAILED.
September 23, 2021
Jeffrey Preston Stines
Town of Waynesville
Email: jstines@waynesvillenc.gov
SUBJECT: Compliance Inspection Report
Waynesville WWTP
NPDES WW Permit No. NC0025321
Haywood County
Dear Permittee:
The North Carolina Division of Water Resources conducted a Bioassay Compliance Inspection of Waynesville
WWTP on August 10, 2021 and August 12, 2021. This inspection was conducted to verify that the facility is
operating in compliance with the conditions and limitations specified in NPDES WW Permit No. NC0056561. The
test resulted in a pass and this facility appeared to be in compliance with NPDES WW Permit No. NC0056561.
The findings and comments noted during this inspection are provided in the enclosed copy of the inspection
report entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact me at 828-296-4500 or via email at
mikal.willmer@ncdenr.gov.
Sincerely,
Mikal Willmer, Environmental Specialist II
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
Ec: Laserfiche
DocuSign Envelope ID: D99F16E2-709F-439A-97EC-428F8E9B08FC
EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0025321 21/08/10 B S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
D N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Waynesville WWTP
300 Walnut Trl
Waynesville NC 28786
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
08:30AM 21/08/10 17/03/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Other Facility Data
09:00AM 21/08/10 21/01/31
Name, Address of Responsible Official/Title/Phone and Fax Number
Jeffrey Preston Stines,16 S Main St Waynesville NC 28786//828-456-3706/Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Other
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Stephanie A Williams DWR/ARO WQ/828-296-4500/
Mikal Willmer DWR/Division of Water Quality/828-296-4686/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: D99F16E2-709F-439A-97EC-428F8E9B08FC
9/23/2021
9/23/2021
9/23/2021
NPDES yr/mo/day
21/08/10
Inspection Type
B3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On August 10, 2021 and August 12, 2021, Mikal Willmer and Stephanie Williams conducted a
Bioassay Compliance Inspection at Waynesville WWTP. Whole Effluent samples were split for use in
a chronic ceriodaphnia dubia pass-fail toxicity test. The toxicity test passed for both the Division's
samples (analyzed by our Bioassay Laboratory in Raleigh) and Waynesville's samples (analyzed by
Environmental Testing Solutions, Inc.). Toxicity test information follows:
Test Type 3-Brood Ceriodaphnia dubia chronic pass-fail
Test Result Pass
Test Concentrations 9%
Control Survival 91.7%
Control Mean Reproduction 25.8 neonates
Test Treatment Survival 100%
Treatment Mean Reproduction 27.3 neonates
First Sample pH 6.82 SU
First Sample Conductivity 2360 micromhos/cm
First Sample Total Residual Chlorine <0.2 mg/L
Second Sample pH 7.28 SU
Second Sample Conductivity 3.26 micromhos/cm
Second Sample Total Residual Chlorine <0.2 mg/L
Test results for the above samples indicate that the effluent would not be predicted to have water
quality impacts on the receiving water. No violations of permit requirements or applicable regulations
were observed during this inspection.
NC0025321 17 (Cont.)
Page#2
DocuSign Envelope ID: D99F16E2-709F-439A-97EC-428F8E9B08FC
Permit:NC0025321
Inspection Date:08/10/2021
Owner - Facility:
Inspection Type:
Waynesville WWTP
Bioassay Compliance
Other Yes No NA NE
See summary.Comment:
Page#3
DocuSign Envelope ID: D99F16E2-709F-439A-97EC-428F8E9B08FC