HomeMy WebLinkAboutWQ0019907_Compliance Evaluation Inspection_20210922DocuSign Envelope ID: 3169CE77-AEA2-4405-90BE-D9836A859ECF
ROY COOPER .'.
Governor _
ELIZABETH S. BISER
Secretary wont
S. DANIEL SMITH NORTH CAROLINA
Director Environmental Qualify
September 22, 2021
David Mohr
Onslow Water and Sewer Authority
228 Georgetown Rd
Jacksonville, NC 28540
SUBJECT: Compliance Inspection Report
Holly Ridge WWTF
Non -discharge Permit No. WQ0019907
Onslow County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Holly Ridge WWTF on
9/16/2021. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in Non -discharge Permit No. WQ0019907. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact Geoff Kegley with the Water
Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
geoff.kegley@ncdenr.gov.
Sincerely,
EDocuSigned by:
-T711,11E73B6F3456...
oµfor
Morelia Sanchez -King, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: WQS Wilmington Regional Office - Enforcement File
NON -DISCHARGE Compliance/Enforcement Unit - Enforcement File
D ��North Carolina Department of Environmental QualityDivision of Water Resources
,./ Wilmington Regional Office 1127 Cardinal Drive Extension I Wilmington. North Carolina 26405
ems. aE^"��^ o�\ ! 910.796,7215
Compliance Inspection Report
Permit: WQ0019907 Effective: 03/08/17 Expiration: 02/28/22 Owner: Onslow Water and Sewer Authority
SOC: Effective: Expiration: Facility: Holly Ridge WWTF
County: Onslow 286 N Jenkins St Ext
Region: Wilmington
Holly Ridge NC 28445
Contact Person: Edward M Caron Title: Phone: 910-937-7523
Directions to Facility:
System Classifications: SI, WW2,
Primary ORC: Kary Alexander Herndon Certification: 1010314 Phone: 910-937-7572
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
WQ0034067 Onslow Water and Sewer Authority - Stump Sound Wastewater Infrastructure
Improvements Sewer
WQ0029945 Onslow Water and Sewer Authority - Summerhouse WWTF
NC0025895 Town Of Holly Ridge - Holly Ridge WWTP
Inspection Date: 09/16/2021 Entry Time 09:30AM Exit Time: 11:OOAM
Primary Inspector: Geoff Kegley Phone:
Secondary Inspector(s):
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Wastewater Irrigation
Facility Status: Compliant ❑ Not Compliant
Question Areas:
Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent Miscellaneous Questions
Treatment Flow Measurement -Water Treatment Treatment Barscreen
Use Records
Record Keeping Treatment Lagoons End Use -Irrigation
Treatment Disinfection Treatment Flow Measurement Standby Power
Wells
(See attachment summary)
Page 1 of 6
Permit: WQ0019907 Owner - Facility:Onslow Water and Sewer Authority
Inspection Date: 09/16/2021 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
A routine compliance inspection of the Holly Ridge WWTF was conducted on September 16, 2021. The purpose of the
evaluation was to verify that the facility is operating in compliance with the conditions and limitations specified in Permit
WQ0019907. Kary Herndon from ONWASA is the ORC and was present during the inspection. The Division appreciates Mr.
Herndon's assistance during the inspection.
The facility consists of a treatment lagoon with three aerated cells and a settling cell with a flow limit of 224,673gpd.
ONWASA has the ability to divert flow from the Jenkins Street Pump Station in Holly Ridge to the Summerhouse WWTF for
treatment when needed. Effluent is stored in a 51-day storage pond before irrigating on 10 spray fields. Field 1/1 D listed in
the Permit was never constructed.
The plant may be decommissioned in approximately 3 years when flow is tied to Camp Lejeune's WWTF.
One of the Blue Frog aerators in the treatment lagoon was down for repair. Solids were last removed from the lagoon in2011,
Sludge levels in the lagoon should be evaluated. Based on the projected timeline of the decommissioning and the results
from the sludge survey, removal of sludge from the lagoon may or may not be necessary.
The disinfection is currently achieved via tablet chlorinator after the UV system was damaged during Hurricane Florence. If
the UV system is not to be replaced, the permit should be modified to reflect the disinfection system. The permit is due for
renewal in February of 2022. This would be an opportune time for this minor modification.
Currently, there is not a gauge to measure freeboard in the treatment lagoon. Flow is gravity fed to the adjacent pump
station. The high water alarm in this pump station was tested and is operating properly.
The sprayfields were all inspected and were in good shape. Some spray heads were in need of repair after fields were
mowed. Spray heads were available on site and repairs were already planned.
Groundwater monitoring has been generally compliant with only 2 anomalous exceedances over the last five years.
The facility is compliant with non -discharge Permit W00019907. Please review the comment sections of the inspection
report for more details.
Page 2 of 6
Permit: WQ0019907
Inspection Date: 09/16/2021
Owner - Facility:Onslow Water and Sewer Authority
Inspection Type: Compliance Evaluation Reason for Visit: Routine
Type
Yes No NA NE
Activated Sludge Spray, LR
❑
Single Family Spray, LR
❑
Infiltration System
❑
Reuse (Quality)
❑
Activated Sludge Spray, HR
❑
Single Family Drip
❑
Recycle/Reuse
❑
Activated Sludge Drip, LR
❑
Lagoon Spray, LR
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑
Comment:
Treatment Flow Measurement -Influent
Yes No NA NE
Is flowmeter calibrated annually?
0
❑ ❑ ❑
Is flowmeter operating properly?
❑ ❑ ❑
Does flowmeter monitor continuously?
❑ ❑ ❑
Does flowmeter record flow?
❑ ❑ ❑
Does flowmeter appear to monitor accurately?
❑ ❑ ❑
Comment: Flowmeters were calibrated on 10/27/2020.
Treatment Flow Measurement -Water Use Records Yes No NA NE
Is water use metered? ❑ ❑ ❑
Are the daily average values properly calculated? ❑ ❑ 0 ❑
Comment:
Treatment Flow Measurement -Effluent
Yes No NA NE
Is flowmeter calibrated annually?
❑
❑ ❑
Is flowmeter operating properly?
❑
❑ ❑
Does flowmeter monitor continuously?
❑
❑ ❑
Does flowmeter record flow?
❑
❑ ❑
Does flowmeter appear to monitor accurately?
❑
❑ ❑
Comment:
Standby Power Yes No NA NE
Is automatically activated standby power available? 0 ❑ ❑ ❑
Page 3 of 6
Permit: WQ0019907 Owner - Facility:Onslow Water and Sewer Authority
Inspection Date: 09/16/2021 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Is generator tested weekly by interrupting primary power source? 0 ❑ ❑ ❑
Is generator operable? 0 ❑ ❑ ❑
Does generator have adequate fuel? 0 ❑ ❑ ❑
Comment: Generator is load tested weekly.
Treatment Barscreen Yes No NA NE
Is it free of excessive debris? 0 ❑ ❑ ❑
Is disposal of screenings in compliance? 0 ❑ ❑ ❑
Are the bars spaced properly? ❑ ❑ ❑
Is the unit in good condition? 0 ❑ ❑ ❑
Comment: The manual bar screen and grit chamber is cleaned daily.
Treatment Disinfection
Yes No NA NE
Is the system working?
0
❑ ❑ ❑
Do the fecal coliform results indicate proper disinfection?
❑
❑ ❑
Is there adequate detention time (>=30 minutes)?
❑
❑ ❑
Is the system properly maintained?
❑ ❑ ❑
If gas, does the cylinder storage appear safe?
❑
❑ ❑
Is the fan in the chlorine feed room and storage area operable?
❑
❑ ❑
Is the chlorinator accessible?
❑ ❑ ❑
If tablets, are tablets present?
❑
❑ ❑
Are the tablets the proper size and type?
❑
❑ ❑
Is contact chamber free of sludge, solids, and growth?
❑
❑ ❑
If UV, are extra UV bulbs available?
❑
❑ ❑
If UV, is the UV intensity adequate?
❑
❑ ❑
# Is it a dual feed system?
❑
❑ ❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
❑
❑ ❑
If yes, then is there a Risk Management Plan on site?
❑
❑ ❑
If yes, then what is the EPA twelve digit ID Number? (1000-
If yes, then when was the RMP last updated?
Comment: The disinfection is currentiv achieved via tablet chlorinator after the UV system was damaged
during Hurricane Florence. If the UV system is not to be replaced, the permit should be
modified to reflect the disinfection system. The permit is due for renewal in February of 2022.
This would be an opportune time for this minor modification.
Record Keeping Yes No NA NE
Is a copy of current permit available? ❑ ❑ ❑
Are monitoring reports present: NDMR? ❑ ❑ ❑
NDAR? ❑ ❑ ❑
Page 4 of 6
Permit: WQ0019907 Owner - Facility:Onslow Water and Sewer Authority
Inspection Date: 09/16/2021 Inspection Type: Compliance Evaluation
Reason for Visit: Routine
Are flow rates less than of permitted flow?
0
❑ ❑ ❑
Are flow rates less than of permitted flow?
0
❑ ❑ ❑
Are application rates adhered to?
0
❑ ❑ ❑
Is GW monitoring being conducted, if required (GW-59s submitted)?
0
❑ ❑ ❑
Are all samples analyzed for all required parameters?
0
❑ ❑ ❑
Are there any 2L GW quality violations?
❑
0 ❑ ❑
Is GW-59A certification form completed for facility?
0
❑ ❑ ❑
Is effluent sampled for same parameters as GW?
❑
❑ ❑
Do effluent concentrations exceed GW standards?
❑
❑ ❑
Are annual soil reports available?
0
❑ ❑ ❑
# Are PAN records required?
❑
❑ 0 ❑
# Did last soil report indicate a need for lime?
❑
❑ ❑
If so, has it been applied?
❑
❑ ❑
Are operational logs present?
0
❑ ❑ ❑
Are lab sheets available for review?
0
❑ ❑ ❑
Do lab sheets support data reported on NDMR?
0
❑ ❑ ❑
Do lab sheets support data reported on GW-59s?
0
❑ ❑ ❑
Are Operational and Maintenance records present?
0
❑ ❑ ❑
Were Operational and Maintenance records complete?
0
❑ ❑ ❑
Has permittee been free of public complaints in last 12 months?
0
❑ ❑ ❑
Is a copy of the SOC readily available?
❑
❑ 0 ❑
No treatment units bypassed since last inspection?
❑
❑ ❑
Comment: Records and operational and maintenance lops were organized and complete.
Annual soil
sampling has been scheduled.
End Use -Irrigation
Yes No NA NE
Are buffers adequate?
0
❑ ❑ ❑
Is the cover crop type specified in permit?
❑
0 ❑ ❑
Is the crop cover acceptable?
❑ ❑ ❑
Is the site condition adequate?
❑ ❑ ❑
Is the site free of runoff / ponding?
❑ ❑ ❑
Is the acreage specified in the permit being utilized?
❑ ❑ ❑
Is the application equipment present?
❑ ❑ ❑
Is the application equipment operational?
❑ ❑ ❑
Is the disposal field free of limiting slopes?
❑ ❑ ❑
Is access restricted and/or signs posted during active site use?
❑ ❑ ❑
Are any supply wells within the CB?
❑
❑ ❑
Page 5 of 6
Permit: WO0019907 Owner - Facility:Onslow Water and Sewer Authority
Inspection Date: 09/16/2021 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Are any supply wells within 250' of the CB? ❑ ❑ ❑
How close is the closest water supply well? ❑ ❑ ❑
Is municipal water available in the area? ❑ ❑ ❑
# Info only: Does the permit call for monitoring wells? 0 ❑ ❑ ❑
Are GW monitoring wells located properly w/ respect to RB and CB? ❑ ❑ ❑
Are GW monitoring wells properly constructed, including screened interval? ❑ ❑ ❑
Are monitoring wells damaged? ❑ 0 ❑ ❑
Comment: The spravfields were all inspected and were in qood shape. The irrigation flow meter was
calibrated on 10/27/2020. The storage pond is lined, had a freeboard marker and the berms
were well maintained. Fields are mowed approximately every two weeks in the summer. Some
spray heads were in need of repair after fields were mowed. Spray heads were available on
site and repairs were already planned. All groundwater monitoring wells were locked and
labeled.
Page 6 of 6