September 21, 2021
SUBJECT: Compliance Inspection Report
La Grange WWTP
Non -discharge Permit No. WQ0034386
Lenoir County
Dear Mr. Craft:
The North Carolina Division of Water Resources conducted an inspection of the La Grange WWTP on
9/13/2021. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in Non -discharge Permit No. WQ0034386. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact Paul Mays with the Water Quality
Regional Operations Section in the Washington Regional Office at 252-948-3940 or via email at
paul.mays@ncdenr.gov.
ATTACHMENTS
Cc: Laserfiche
Sincerely,
Paul kakiS
Paul Mays, Environmental Specialist I
Water Quality Regional Operations Section
Washington Regional Office
Division of Water Resources, NCDEQ
United States Environmental Protection Agency
E PA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection
1 I N 1 2 15 1 3 I NC0021644 111 121 21/09/13 117
Type
181 [pi
IIIIIIIIIII
Inspector Fac Type
131S I 201 I
21IIIIII IIIIIIIIIII IIIIIIII IIIIII
166
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA
671 I 70I I 711I 72 �i 1 731 I 174
LJ I I I
Reserved
751
1
I I I I I I I80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
La Grange WWTP
700 E King St
La Grange NC 285510368
Entry Time/Date
10:OOAM 21/09/13
Permit Effective Date
19/04/01
Exit Time/Date
11:30AM 21/09/13
Permit Expiration Date
24/03/31
Name(s) of Onsite Representative(s)Ttles(s)/Phone and Fax Number(s)
///
James Wesley Sutton/ORC/252-566-3295/
Other Facility Data
Name, Address of Responsible Official/Ttle/Phone and Fax Number
Contacted
John P Craft,PO Box 368 La Grange NC 285518219/Town
Manager/252-566-3186/2525662201 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Sludge Handling Dispos Facility Site Review Pretreatment Effluent/Receiving Wale
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Will T Hart DWRANARO GW/ - - /
Paul M Mays DWR/WARO WQ/252-948-3940/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
NPDES yr/mo/day Inspection Type
31 Nc0021644 111 121 21/09/13 117 18 r, I
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On 09/13/2021 Paul Mays and William Hart with the Division of Water Resources from the Washington
Regional office conducted a compliance evaluation of La Grange WWTP operating under NPDES
permit #NC0021644. The facility was found to be compliant with NPDES permit #NC0021644. Below is
the findings and observations made during the inspection.
The facility itself was well maintained, and the grounds were also freshly mowed and maintained.
During the record review all required documents were readily available. The January 2021 and March
2021 DMRs were spot checked and compared to corresponding lab data. No major discrepancies
were found between the DMRs and lab data. A minor discrepancy was observed in the March 2021
DMR where temperature was not in the correct columns. Staff onsite said records were maintained for
at least 5 years, operations and maintenance logs were present and complete and ORC visitation log
was present and complete. The 2020 and 2019 Annual compliance reports were also reviewed and
found to be satisfactory.
The laboratory was clean, and equipment was well kept. The facility utilizes their lab for all sample
parameters other than Ammonia, TKN, Nitrate + Nitrite, Total Nitrogen and Total Phosphorous. All
parameters that are not measured by the facility's inhouse lab are contracted out to Environmentl.
The lab operates under certificate No. 256.
The generator is tested weekly on Mondays around 10:OOam. The facility has an emergency fuel
agreement with Travelers Service Station and the fuel tank for the generator was 3/4th full during the
inspection. The unit seemed to be in good condition and was operational at the time of the
inspection.
The influent flowmeter was calibrated on 05/27/2021 by Chadwick Instrument Inc.
The effluent flowmeter was calibrated on 05/27/2021 by Chadwick Instrument Inc. The effluent
sampler was at 0 degrees Celsius. The effluent sampler is time proportional, takes a sample every 30
minutes and each sample is 100m1. No major issues were observer with the sampler.
Page# 2
Permit: NC0021644
Inspection Date: 09/13/2021
Owner - Facility: La Grange W WTP
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ • ❑
application?
Is the facility as described in the permit? ■ ❑ ❑ ❑
# Are there any special conditions for the permit? ■ ❑ ❑ ❑
Is access to the plant site restricted to the general public? ■ ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? ■ ❑ ❑ ❑
Comment: Permit expires March 31, 2021
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ■ ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable MEDD
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The facility was well maintained, and the grounds were also freshly mowed and
maintained.
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? • ❑ ❑ ❑
Is all required information readily available, complete and current? ■ ❑ ❑ ❑
Are all records maintained for 3 years (lab. reg. required 5 years)? ■ ❑ ❑ ❑
Are analytical results consistent with data reported on DMRs? ■ ❑ ❑ ❑
Is the chain -of -custody complete? ■ ❑ ❑ ❑
Dates, times and location of sampling •
Name of individual performing the sampling ■
Results of analysis and calibration ■
Dates of analysis ■
Name of person performing analyses ■
Transported COCs ■
Are DMRs complete: do they include all permit parameters? ■ ❑ ❑ ❑
Has the facility submitted its annual compliance report to users and DWQ? •❑ ❑ ❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified ❑ ❑ ■ ❑
operator on each shift?
Is the ORC visitation log available and current? ■ ❑ ❑ ❑
Is the ORC certified at grade equal to or higher than the facility classification? •❑ ❑ ❑
Is the backup operator certified at one grade less or greater than the facility •❑ ❑ ❑
classification?
Page# 3
Permit: NC0021644
Owner - Facility: La Grange W WTP
Inspection Date: 09/13/2021 Inspection Type: Compliance Evaluation
Record Keeping
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: During the record review all required documents were readily available. The January
2021 and March 2021 DMRs were spot checked and compared to corresponding lab
data. No major discrepancies were found between the DMRs and lab data. A minor
discrepancy was observed in the March 2021 DMR where temperature was not in the
correct columns. Staff onsite said records were maintained for at least 5 years,
operations and maintenance logs were present and complete and ORC visitation lop
was present and complete. The 2020 and 2019 Annual compliance reports were also
reviewed and found to be satisfactory.
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? ■ ❑ ❑ ❑
Are all other parameters(excluding field parameters) performed by a certified lab? ■ ❑ ❑ ❑
# Is the facility using a contract lab? ■ ❑ ❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 ■ ❑ ❑ ❑
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? • ❑ ❑ ❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ■ ❑ ❑ ❑
Comment: The laboratory was clean, and equipment was well kept. The facility utilizes their lab for
all sample parameters other than Ammonia TKN, Nitrate + Nitrite, Total Nitrogen and
Total Phosphorous. All parameters that are not measured by the facility's inhouse lab
are contracted out to Environment). The lab operates under certificate No. 256.
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
Yes No NA NE
▪ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The generator is tested weekly on Mondays around 10:00am. The facility has an
emergency fuel agreement with Travelers Service Station and the fuel tank for the
generator was 3/4th full during the inspection. The unit seemed to be in good condition
and was operational at the time of the inspection.
Flow Measurement - Influent Yes No NA NE
Page# 4
Permit: NC0021644
Owner • Facility: La Grange W WTP
Inspection Date: 09/13/2021 Inspection Type: Compliance Evaluation
Flow Measurement - Influent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
❑ ■ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ■ ❑
Comment: The influent flowmeter was calibrated on 05/27/2021 by Chadwick Instrument Inc.
Pump Station - Influent
Is the pump wet well free of bypass lines or structures?
Is the wet well free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry available and operational?
Is audible and visual alarm available and operational?
Comment:
Yes No NA NE
• ❑ ❑ ❑
❑ ❑ ❑ •
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Bar Screens Yes No NA NE
Type of bar screen
a.Manual �
b.Mechanical ■
Are the bars adequately screening debris? • OLD
Is the screen free of excessive debris? ■ ❑ ❑ ❑
Is disposal of screening in compliance? • ❑ ❑ ❑
Is the unit in good condition? MOOD
Comment: Screenings are sent to lined landfill once a week
Grit Removal
Type of grit removal
a.Manual
b.Mechanical
Is the grit free of excessive organic matter?
Is the grit free of excessive odor?
# Is disposal of grit in compliance?
Yes No NA NE
•
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 5
Permit: NC0021644
Inspection Date: 09/13/2021
Owner - Facility: La Grange AWTP
Inspection Type: Compliance Evaluation
Grit Removal Yes No NA NE
Comment: Grit is sent to lined landfill once a week
Oxidation Ditches
Are the aerators operational?
Are the aerators free of excessive solids build up?
# Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Are settleometer results acceptable (> 30 minutes)?
Is the DO level acceptable?(1.0 to 3.0 mg/I)
Are settelometer results acceptable?(400 to 800 ml/I in 30 minutes)
Comment:
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately % of the sidewall depth)
Comment:
Filtration (High Rate Tertiary)
Type of operation:
Is the filter media present?
Is the filter surface free of clogging?
Is the filter free of growth?
Is the air scour operational?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
MOOD
❑ ❑ ❑•
Yes No NA NE
▪ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
▪ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
▪ ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
❑ ❑ 0111
O 00111
❑ ❑ ❑•
• ❑ ❑ ❑
Page# 6
Permit: NC0021644
Inspection Date: 09/13/2021
Owner - Facility: La Grange wWTP
Inspection Type: Compliance Evaluation
Filtration (High Rate Tertiary)
Is the scouring acceptable?
Is the clear well free of excessive solids and filter media?
Comment:
Disinfection -Gas
Are cylinders secured adequately?
Are cylinders protected from direct sunlight?
Is there adequate reserve supply of disinfectant?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No.
7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1000-
If yes, then when was the RMP last updated?
Comment:
Yes No NA NE
❑ ❑ ❑•
❑ ❑ ❑ •
Yes No NA NE
▪ ❑ ❑ ❑
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
MODE
■ ❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
De -chlorination Yes No NA NE
Type of system ? Gas
Is the feed ratio proportional to chlorine amount (1 to 1)? ■ ❑ ❑ ❑
Is storage appropriate for cylinders? ■ ❑ ❑ ❑
# Is de -chlorination substance stored away from chlorine containers? NOLO
Comment:
Are the tablets the proper size and type? ❑ 0 • 0
Are tablet de -chlorinators operational? 0 0 • 0
Number of tubes in use?
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
Yes No NA NE
• ❑ ❑ ❑
i•❑ ❑❑
■ ❑ ❑ ❑
Page# 7
Permit: NC0021644
Inspection Date: 09/13/2021
Owner - Facility: La Grange WWTP
Inspection Type: Compliance Evaluation
Flow Measurement - Effluent
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
• 0.0
Comment: The effluent flowmeter was calibrated on 05/27/2021 by Chadwick Instrument Inc. The
effluent sampler was at 0 degrees Celsius. The effluent sampler is time proportional,
takes a sample every 30 minutes and each sample is 100m1. No major issues were
observer with the sampler.
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Comment:
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
▪ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
❑ ❑ ❑•
❑ ❑•❑
Page# 8