HomeMy WebLinkAboutNC0020656_Inspection_20130827AVA NCDENR North Carolina Department of Environment and Natural Resources Division of Water Resources Water Quality Programs Pat McMrory Thomas A. Reeder John E. Skvarla, III Governor Director Secretary August 27, 2013 Robert A. Ellis City of Laurinburg P.O. Box 249. Laurinburg NC 28353 SUBJECT: August 14, 2013 Compliance Evaluation Inspection City of Laurinburg Leith Creek WWTP Permit No: NC0020656 Scotland County Dear Mr. Ellis: Enclosed please find a copy of the Compliance Evaluation Inspection form from the inspection conducted on August 14, 2013. The Compliance Evaluation Inspection was conducted by Mark Brantley, Environmental Senior Specialist, of the Fayetteville Regional Office. The facility was found to be in Compliance with permit NC0020656. The cooperation of Mr. Ricky Odum, Grade IV Back-up ORC, was greatly appreciated. As a reminder, preservation of the Waters of the State can only be achieved through consistent NPDES Permit compliance. Comments • Facility was clean and neat in appearance at the time of the inspection. •. Maintenance records, log books, and laboratory records were well kept and in order. • Laboratory records for the month of February 2013 were compared to the monthly DMR and no data transcription errors were found. Please refer to the enclosed inspection report for additional observations and comments. If you or your staff have any questions, please call me at 910-433-3327. Sincerely, XIX Mark Brantley Environmental Senior Specialist Surface Water Protection Section Fayetteville Regional Office cc: Robert A. Ellis, ORC Central Files Fayetteville ;Files Location: 225 Green Street, Suite 714, Fayetteville, NC 28301 Phone (910) 433-3300\FAX: 910-486-0707\Customer Service: 1-877-623-6748 Internet: www.ncwaterquality.org An Equal Opportunity/Affirmative Action Employer — 50% Recycled/10% Post Consumer Paper United States Environmental Protection Agency E p q Washington, D.C. 20460 r/� Water Compliance Inspection Report Form Approved. OMB No. 2040 0057 Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection 1 I N I 2 15 I 31 NC0020656 111 121 13/08/14 117 Type Inspector Fac Type 18I C I 191 S I 201 I 1111 I II1 111111I66 Remarks 211111 111.111111111 11111111 11111111 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA —------ --------------Reserved------------------ 671 1 69 701 31 711 N 1 721 NI 731 1 174 761 1 1 1 1 1 1 1 80 Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include POTW name and NPDES permit Number) Leith Creek WWTP Hall St Extension Laurinburg NC 28352 Entry Time/Date 11:00 AM 13/08/14 Permit Effective Date 09/11/01 Exit Time/Date 01:00 PM 13/08/14 Permit Expiration Date 14/08/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) /// Robert A. Ellis/ORC/910-277-0214/ Other Facility Data Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Robert A. Ellis,PO Box 249 Laurinburg NC 28353//910-277-0214/ No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenance • Records/Reports Self -Monitoring Program Sludge Handling Disposal • Facility Site Review • Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Mark Brantley FRO WQ//910-433-3300 Ext.727/ 1141-A 4,-i-c, � .v?-/3 Signature of Management Q • Reviewer Agency/Office/Phone and Fax Numbers Date Belinda S Henson rr' v74 t FRO WQ//910-433-3300 Ext.726/ 0 '(29 - /3 EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page # 1 NPDES yr/mo/day Inspection Type 3I NC0020656 I11 12I 13/08/14 117 18I cI 1 Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) Facility was clean neat in appearance at the time of the inspection. Maintenance records, log books , and laboratory records were well kept and in order. Laboratory records for the month of February 2013 were compared to the monthly DMR and no data transcription errors were found. Page # 2 Permit: NC0020656 Owner - Facility: Leith Creek WWTP Inspection Date: 08/14/2013 Inspection Type: Compliance Evaluation Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? ■ n n n Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge ■ n n n Judge, and other that are applicable? Comment: Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new application? n n ■ n Is the facility as described in the permit? ■ n n n # Are there any special conditions for the permit? ❑ ❑ ■ n Is access to the plant site restricted to the general public? ■ n n n Is the inspector granted access to all areas for inspection? - ■ n n n Comment: Record Keeping Are records kept and maintained as required by the permit? Is all required information readily available, complete and current? Are all records maintained for 3 years (lab. reg. required 5 years)? Are analytical results consistent with data reported on DMRs? Is the chain -of -custody complete? Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? Has the facility submitted its annual compliance report to users and DWQ? (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift? Is the ORC visitation log available and current? Is the ORC certified at grade equal to or higher than the facility classification? Is the backup operator certified at one grade less or greater than the facility classification? Is a copy of the current NPDES permit available on site? Yes No NA NE ■ nnn ■ nnn ■ nnn ■ nnn ■ nnn ■ ■ ■ ■ ■ ■ ■ nnn ■ nnn ■ nnn ■ nnn ■ nnn ■ nnn ■ nnn Page # 3 Permit: NC0020656 Owner - Facility:. Leith Creek WWTP Inspection Date: 08/14/2013 Inspection Type: Compliance Evaluation Record Keeping Facility has copy of previous year's Annual Report on file for review? Comment: Flow Measurement - Effluent # Is flow meter used for reporting? Is flow meter calibrated annually? Is the flow meter operational? (If units are separated) Does the chart recorder match the flow meter? Comment: Aerobic Digester Is the capacity adequate? Is the mixing adequate? Is the site free of excessive foaming in the tank? # Is the odor acceptable? # Is tankage available for properly waste sludge? Comment: Drying Beds Is there adequate drying bed space? Is the sludge distribution on drying beds appropriate? Are the drying beds free of vegetation? # Is the site free of dry sludge remaining in beds? Is the site free of stockpiled sludge? Is the filtrate from sludge drying beds returned to the front of the plant? # Is the sludge disposed of through county landfill? # Is the sludge land applied? (Vacuum filters) Is polymer mixing adequate? Comment: Pump Station - Influent Is the pump wet well free of bypass lines or structures? Is the wet well free of excessive grease? Are all pumps present? Yes No NA NE ■ nnn Yes No NA NE ■ nnn ■ nnn ■ nnn ■ nnn Yes No NA NE ■ nnn ■ nnn ■ nnn ■ nnn annn Yes No NA NE ■ nnn annn ■ nnn ■ nnn ■ nnn n n■n n omo ■ nnn n n■n Yes No NA NE ■ nnn ■ nnn ■ nnn Page # 4 Permit: NC0020656 Owner - Facility: Leith Creek WWTP Inspection Date: 08/14/2013 Inspection Type: Compliance Evaluation Pump Station - Influent Are all pumps operable? Are float controls operable? Is SCADA telemetry available and operational? Is audible and visual alarm available and operational? Comment: Bar Screens Type of bar screen a.Manual b.Mechanical Are the bars adequatelyscreening debris? Is the screen free of excessive debris? Is disposal of screening in compliance? Is the unit in good condition? Comment: Equalization Basins Is the basin aerated? Is the basin free of bypass lines or structures to the natural environment? Is the basin free of excessive grease? Are all pumps present? Are all pumps operable? Are float controls operable? Are audible and visual alarms operable? # Is basin size/volume adequate? Comment: Yes No NA NE ■ nnn ■ nnn ■ nnn ■ nnn Yes No NA NE n ■ ■ nnn ■ nnn ■ nnn ■ nnn Yes No NA NE ■ nnn ■ nnn ■ nnn ■ nnn ■ nnn ■ nnn ■ nnn ■ nnn Secondary Clarifier Yes, No NA NE Is the clarifier free of black and odorous wastewater? ■ n n ❑ Is the site free of excessive buildup of solids in center well of circular clarifier? Ennn Are weirs level? ■ n n n Is the site free of weir blockage? ■ n n n Is the site free of evidence of short-circuiting? ■ n n n Page # 5 Permit: NC0020656 Owner - Facility: Leith Creek WWTP Inspection Date: 08/14/2013 Inspection Type: Compliance Evaluation Secondary Clarifier Yes No NA NE Is scum removal adequate? ■ n n n Is the site free of excessive floating sludge? ■ n n n Is the drive unit operational? ■ n n n Is the return rate acceptable (low turbulence)? ■ n n n Is the overflow clear of excessive solids/pin floc? ■ n n n Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) ■ ❑ n ❑ • Comment: Aeration Basins Yes No NA NE Mode of operation - Ext. Air Type of aeration system Surface Is the basin free of dead spots? ■ n n n Are surface aerators and mixers operational? ■ ❑ ❑ n Are the diffusers operational? n ❑ ■ n Is the foam the proper color for the treatment process? ■ n fl n Does the foam cover less than 25% of the basin's surface? ■ n n n Is the DO level acceptable? ■ n n n Is the DO level acceptable?(1.0 to 3.0 mg/I) ■ n n n Comment: Oxidation Ditches Yes No NA NE Are the aerators operational? Are the aerators free of excessive solids build up? # Is the foam the proper color for the treatment process? Does the foam cover less than 25% of the basin's surface? Is the DO level acceptable? Are settleometer results acceptable (> 30 minutes)? Is the DO level acceptable?(1.0 to 3.0 mg/I) Are settelometer results acceptable?(400 to 800 ml/I in 30 minutes) Comment: De -chlorination Yes No NA NE Type of system ? ■ nnn ■ nnn ■ nnn ■ nnn ■ nnn ■ nnn ■ nnn ■ nnn Liquid Page # 6 Permit: NC0020656 Owner - Facility: Leith Creek WWTP Inspection Date: 08/14/2013 Inspection Type: Compliance Evaluation De -chlorination Yes No NA NE Is the feed ratio proportional to chlorine amount (1 to 1)? ■ n n n Is storage appropriate for cylinders? n ❑ • 11 # Is de -chlorination substance stored away from chlorine containers? n n ■ ❑ Comment: Are the tablets the proper size and type? ❑ n • ❑ Are tablet de -chlorinators operational? n n • n Number of tubes in use? Comment: Standby Power Yes No NA NE Is automatically activated standby power available? Is the generator tested by interrupting primary power source? Is the generator tested under load? Was generator tested & operational during the inspection? Do the generator(s) have adequate capacity to operate the entire wastewater site? Is there an emergency agreement with a fuel vendor for extended run on back-up power? Is the generator fuel level monitored? Comment: Pumps-RAS-WAS Are pumps in place? Are pumps operational? Are there adequate spare parts and supplies on site? Comment: Laboratory Are field parameters performed by certified personnel or laboratory? Are all other parameters(excluding field parameters) performed by a certified lab? # Is the facility using a contract lab? # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? Comment: ■ nnn ■ nnil ■ nnn n nn■ ■ nnn n nn■ ■ nnn Yes No NA. NE ■ nnn ■ nnn n nn■ Yes No NA NE ■ nnn ■ nnn ■ nnn i ■ nnn ■ nnn ■ nnn Page # 7 Permit: NC0020656 Owner - Facility: Leith Creek WWTP Inspection Date: 08/14/2013 Inspection Type: Compliance Evaluation Disinfection -Liquid Is there adequate reserve supply of disinfectant? (Sodium Hypochlorite) Is pump feed system operational? Is bulk storage tank containment area adequate? (free of leaks/open drains) Is the level of chlorine residual acceptable? Is the contact chamber free of growth, or sludge buildup? Is there chlorine residual prior to de -chlorination? Comment: Influent Sampling # Is composite sampling flow proportional? Is sample collected above side streams? Is proper volume collected? Is the tubing clean? # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? Is sampling performed according to the permit? Comment: Effluent Sampling Is composite sampling flow proportional? Is sample collected below all treatment units? Is proper volume collected? Is the tubing clean? # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type representative)? Comment: Upstream / Downstream Sampling Yes No NA NE ■ nnn ■ nnn ■ nnn ■ nnn ■ nnn ■ nnn Yes No NA NE WHEW ■ nnn ■ nnn ■ nnn ■ nnn ■ nnn Yes No NA NE ■ nnn ■ nnn ■ nnn ■ nnn ■ nnn ■ nnn Yes No NA NE Is the facility sampling performed as required by the permit (frequency, sampling type, and sampling location)? ■ ❑ n n Comment: Page # 8 Regional Inspectors' Checklist for Field Parameters Facility Name: Leith Creek WWTP Lab Regional Plant Inspector: Mark Brantley NPDES #: NC002656 Regional Inspector Contact #: 910-433-3327 Field Lab Certification #: 133 Region: Fayetteville Lab Contact: Ricky Odum Date: August 14, 2013 I. Check the parameter(s) performed at this site for reporting purposes. ® Total Residual Chlorine (TRC) ® Temperature (TEMP) ® Specific Conductivity (SC) ® pH [Si Dissolved Oxygen (DO) ❑ Settleable Residue (SETT) II. General Laboratory (note an y exceptions in section XI Are instruments, meters, probes, photometric cells, etc. maintained in good condition? Are standards, reagents and consumables used within manufacturer expiration dates? [TRC gel standard is exempt.] ®Yes El No Yes ❑ No Are the following items documented (:Tik hereapplitable),; z Item ' _ TRC _ -,pw Y TEOVIP ; ? Date of sample collection* 4 q q 4 ,f Time of sample collection* •J . ,J Sample collector's initials or signature 4 4 -4 4 4 Date of sample analysis* .J .J .J .J ,I Time of sample analysis* .J J 4 4 4 Analyst initials or signature 4 .J .J ,J ,j Sample location .J .J -Ni ,J ,J ate and time of sample collection and analysis may be the same for in situ or on -site measurements. 111 k_=Tofial Residual Chlorine" `r Total Residual Chlorine meter make and model: Hach DR2800 Is a check standard analyzed each day of use? Liquid Standard A Yes ❑ No What is the assigned/observed value of the daily check standard? 300ug/I, 10ug/I Is a 5-point calibration verification performed? Note date of last verification: ❑ Yes ❑ No Alternatively, does the lab construct a linear regression, using 5 standards, to calculate results? Note date of last calibration curve constructed: ❑ Yes ❑ No True values: /1 pg/L ❑ mg/L _10_ 50 100_ _300_ _500_ Obtained values: /1 pg/L ❑ mg/L 9 _48_ _101_ _310_ _515_ What program are samples analyzed on? Are results reported in proper units? Check one: ►1 pg/L ❑ mg/L Yes ❑ No Are results reported between the facility's permit limit and the compliance limit of 50 pg/L? If value is Tess than the low standard, report as "<x", where x=low standard conc. Yes ❑ No Are samples analyzed within 15 minutes of collection? ►1 Yes ❑ No P1 pH ` pH meter make and model: YSI 60 Is the pH meter calibrated with at least 2 buffers per mfg's instructions each day of use? Note buffers used:4, 10 // Yes ❑ No Is the pH meter calibration checked with an additional buffer each day of use? Note check buffer used:7 A Yes ❑ No Does the check buffer read within ±0.1 S.U. of the known value? ►1 Yes ❑ No Are the following items documented: Meter calibration? // Yes ❑ No Check buffer reading? // Yes ❑ No Are samples analyzed within 15 minutes of collection? ►1 Yes ❑ No Are sample results reported to 0.1 pH units? Yes ❑ No Temperature . .. ..... : What instrument(s) is used to measure temperature? Check all that apply: /1 ❑ DO meter ❑ Conductivity meter ❑ Digital thermometer ❑ Glass thermometer pH meter Is the instrument/thermometer calibration checked at least annually against a NIST traceable or NIST certified thermometer? ►1 Yes ❑ No Are temperature corrections (even if zero) posted on the instrument/thermometer? 4 Yes ❑ No Are samples measured in situ or on -site? [REQUIRED - there is no holding time for temperature] I1 Yes ❑ No Are sample results reported in degrees C? i4 Yes ❑ No V f _., DsohVettl OxJ gen . _ _ _ - DO meter make and model: YSI 550A Is the air calibration of the DO meter performed each day of use? ►1 Yes ❑ No Are the following items documented: Meter calibration? 4 Yes ❑ No Are samples analyzed within 15 minutes of collection? A. Yes ❑ No Are results reported in mg/L? 0 Yes ❑ No Co;nduc4ytty _; _ __ Conductivity meter make and model: Orion 3 Star Is the meter calibrated daily according to the manufacturer's instructions? Note standard used (this isgenerally a one -point calibration): /1 Yes ❑ No Is a daily check standard analyzed? Note value: a Yes ❑ No Are the following items documented: Meter calibration? 0 Yes ❑ No Are samples analyzed within 28 days of collection? /1 Yes ❑ No Are results reported in pmhos/cm (some meters display a uivalent pS/cm units)? q� V Yes ❑ No - 1t Settleable_ Residu+e - Does the laboratory have an Imhoff Cone in good condition? Yes No Is the sample settled for 1 hour? Yes No Is the sample agitated after 45 minutes? Yes No Are the following items documented: J Volume of sample analyzed? Note volume analyzed: Yes No Date and time of sample analysis (settling start time)? Yes No Time of agitation after 45 minutes of settling? Yes No Sample analysis completion (settling end time)? Yes No Are samples analyzed within 48 hours of collection? Yes Yes Yes y❑Ft�o No No Are results reported in ml/L? al,-.'paper#rail (doniparn con ractlab anpn site data to DMR) s = p�rfvr_ , ' 0If 0' IS ai�i�fitaie i wed ia�h 0 Is;follow-up by the Laboratory CertIticattoft program recommen ded? Y T ❑ Yes: Eril ,.No Xl. Additional comments: Please submit a copy of this completed form to the Laboratory Certification program at: DWQ Lab Certification, Chemistry Lab, Courier # 52-01-01 Electronic copies may be emailed to linda.chavisAncdenr.gov. Revision 04/20/2012