HomeMy WebLinkAboutSW3210601_SW3200102 Add Info_20201113ROY COOPER Governor MICHAEL S. REGAN Secretary BRIAN WRENN Director Nicholas R. Parker, PE 7140 Weddington Road, Suite 140 Concord, NC 28027 NORTH CAROLINA Environmental Quality November 13, 2020 Subject: Request for Additional Information Stormwater Permit No. SW3200102 Heilig Road Building Expansion Rowan County Dear Mr. Parker: The Division of Energy, Mineral and Land Resources (DEMLR), received a Stormwater Management Permit Application for the subject project on October 8, 2020. A review of that information has determined that the application is not complete. The following information is needed to continue the stormwater review: Prior Comment 16 — "Provide pdfs of all revisions, 2 hardcopies of revised plan sheets, and I hardcopy of other documents. " Please provide hard copies of the revised submittal materials that were uploaded to Laserfiche in response to the previous Request for Additional Information letter. The October 8, 2020 hard copy resubmission only included 2x copies of the revised plan set and 2x copies of the revised calculation booklet. NOTE: If any of the hard copy items from submittal 2 (the prior submittal) are being modified for submission 3 (the next submittal) then only the most recent version of the updated item needs to be submitted. 2. Prior Comment 10 — "Please provide a site -specific soils report showing the Seasonal High Water Table (SHWT) elevation (Section VI, 9 & Sand Filter MDC 1). " The provided SHWT letter states that the existing ground surface elevation in the location of the boring is approximately 811 feet and the boring was conducted to a depth of 4 feet below the existing grade (to an elevation of approximately 807 feet). Per the plans, the lowest excavated point of the sand filter is at elevation 808.5 (approximately 1.5 feet of separation). The required 2-foot vertical separation between the SHWT and lowest point of the facility has not been demonstrated. NOTE: The Supplement-EZ Form indicates that the SHWT is at or below elevation 806 feet, but this does not match the provided letter. D E Q North Carolina Department of Environmental Quality I Division of Energy, Mineral and Land Resources 512 North Salisbury Street 1 1612 Mail Service Center I Raleigh, North Carolina 27699-1612 NORTH CAROLINA - Department oEnvironmental Uual� 4� 919.707.9200 3. Prior Comment 12 — "Please provide some information on the spec'd ASTM C144 and show that it is an equivalent to ASTM C33 (Sand Filter MDC 6). " The Supplement-EZ Form still includes references to ASTM C144 (See later comment). 4. Based on the provided stage -storage table for the sand filter, the design volume of 4,288 cf would result in a temporary ponding elevation closer to 811.54 feet (811.2 feet is shown in the calculations & plans). It is a requirement that the first bypass elevation (The single 6" orifice) be at or above this temporary ponding elevation (per Sand Filter MDC 3). 5. Please correct the following issues with the provided Supplement-EZ Form: a. Sand Filter Page, "Sand Filter MCD From 02H .1056": i. VI SHWT elevation (f nsl)" — Ensure that this information matches the provided SHWT information provided and is at least 2 feet lower than the lowest point of the sand filter. ii. V2 Physical... "& "...Ponding depth in the sediment chamber... " — If these is no permanent pool in the sediment chamber, the ponding depth and physical depth of the sediment chamber are the same. Since the bottom of the sediment chamber is at elevation 811 and the maximum ponding elevation is at elevation 814, these values should be 36 inches. iii. V2 Physical... "& "...Ponding depth in the sand chamber... " — If these is no permanent pool in the sand chamber, the ponding depth and physical depth of the sand chamber are the same. Since the bottom of the sand chamber is at elevation 810 and the maximum ponding elevation is at elevation 814, these values should be 48 inches. iv. V3 Elevation of the bypass device (fmsl)" — Please include this value. This is the elevation of the lowest bypass weir or orifice. Per the plans, this value is 811.2 ft. NOTE: This elevation will probably be changed due to addressing a prior comment and is provided for illustrative purposes only. v. V3 Describe the bypass device" —Only the lowest bypass device needs to be described. If the lowest bypass device is an orifice, the diameter should be included. vi. V4 Ponding depth from the top of the sand to the bypass device (ft) " — This is the vertical distance between the top of the sand layer (810 ft) and the invert of the lowest bypass device. vii. V6 Sand specification for sand chamber" -Please show that ASTM C 144 is an equivalent to ASTM C33 or remove the reference. 6. Provide pdfs of all revisions, 2 hardcopies of revised plan sheets, and 1 hardcopy of other documents. Pdfs must be uploaded using the form at: https://edocs.deq.nc.gov/Forms/SW Project Submittal Please note that this request for additional information is in response to a preliminary review. The requested information should be received by this Office prior to December 13, 2020, or the application will be returned as incomplete. The return of a project will necessitate resubmittal of all required items, including the application fee. Please reference the State assigned project number SW3200102 on all correspondence. If you need additional time to submit the information, please submit your request for a time extension to the Division at the contact below. The request must indicate the date by which you expect to submit the required information. The Division is allowed 90 days from the receipt of a completed application to issue the permit. The construction of any impervious surfaces, other than a construction entrance under an approved Sedimentation Erosion Control Plan, is a violation of NCGS 143-215.1 and is subject to enforcement action pursuant to NCGS 143-215.6A. If you have any questions concerning this matter please feel free to contact me at Jim.Farkas@ncdenr.gov or (919) 707-3646. Sincerely, ✓_ vl Jim Farkas Environmental Engineer Stormwater Program cc: Mooresville Regional Office