August 20, 2021
Crystal Walters, Association Manager
Dunescape Villas Condominium Owners Association Inc.
PO Box 4455
Emerald Isle, NC 28594-4455
SUBJECT: Compliance Inspection Report
Dunescape Villas WWTF
Non -discharge Permit No. WQ0003044
Carteret County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Dunescape Villas WWTF
on 8/18/2021. This inspection was conducted to verify that the facility is operating in compliance with
the conditions and limitations specified in Non -discharge Permit No. WQ0003044. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report entitled
"Compliance Inspection Report". There were no significant issues or findings noted during the inspection and
therefore, a response to this inspection report is not required.
If you should have any questions, please do not hesitate to contact Helen Perez with the Water
Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
helen.perez@ncdenr.gov.
ATTACHMENTS
Cc: Don O'Mara — electronic copy
Upload to Laserfiche
Sincerely,
DocuSigned by:
�Oµ �T�natrl OA,
7F141E7366F3456...
Morel la Sanchez -King, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
North Carolina Department of Environmental Quality I Division of Water Resources
Wilmington Regional Office 1 127 Cardinal Drive Extension I Wilmington, North Carolina 28405
910.796.7215
DocuSign Envelope ID: 1`13110F30-C154-46BO-9ABF-39FEFCC78271
Comoliance Insoection Resort
Permit: WQ0003044 Effective: 04/19/17 Expiration: 03/31/22 Owner: Dunescape Villas Condominium Owners
Association Inc
SOC: Effective: Expiration: Facility: Dunescape Villas WWTF
County: Carteret 2111 W Fort Macon Rd
Region: Wilmington
Atlantic Beach NC 28512
Contact Person: Crystal Walters
Title:
Phone: 252-354-6333
Directions to Facility:
Located on Bouge Banks, on the north side of Hwy 58. It is 1.9 miles west of the entrance to Atlantic Beach.
System Classifications: WW3.,
Primary ORC: Donald P Omara Certification: 7904 Phone: 252-247-9167
Secondary ORC(s):
On -Site Representative(s):
On -site representative Donald P Omara 252-247-9167
Related Permits:
Inspection Date: 08/18/2021 Entry Time 10:OOAM Exit Time: 11:40AM
Primary Inspector: Helen I Perez DocuSignetd�by:
Secondary Inspector(s):E r
Phone: 910-796-7387
39694BE_
cuSigned by:
Tyler G BensonE��o
Reason for Inspection: Routine
�t,liLSb�l Inspection Type: Compliance Evaluation
DCAE=754468_
Permit Inspection Type: High Rate Infiltration
Facility Status: Compliant ❑ Not Compliant
Question Areas:
Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent
Miscellaneous Questions
Treatment Flow Measurement -Water Treatment
Treatment Filters
Use Records
Record Keeping Treatment Activated Sludge
Treatment Disinfection
End Use -Infiltration Treatment Flow Measurement
Standby Power
(See attachment summary)
Page 1 of 6
DocuSign Envelope ID: FB11OF30-C154-46B0-9ABF-39FEFCC78271
Permit: WQ0003044 Owner - Facility: Dunescape Villas Condominium Owners Association Inc
Inspection Date: 08/18/2021 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
A routine compliance inspection of Dunescape Villas WWTF was conducted on August 18, 2021. The purpose of the
evaluation was to verify that the facility is operating in compliance with the conditions and limitations specified in Permit
WQ0003044. Don and Karrie O'Mara were present during the inspection.
This facility is a 50,000 gpd Integrated Surge Anoxic Mix SBR system with a high -rate infiltration system consisting of three
surface LPP fields. The current facility was constructed and put into operation in July 2017 to replace the old plant. There
has been no effluent violations since the summer of 2017. A review of GW-59s, since last inspection in 2019, show some
TDS limit exceedances in MW-6. This permit expires in March 31, 2022. A renewal application will need to be submitted by
October 1, 2021.
The facility is compliant with Non -Discharge Permit WQ0003044. Please review the comment sections of the inspection
report for more details.
Page 2 of 6
DocuSign Envelope ID: FB11OF30-C154-46B0-9ABF-39FEFCC78271
Permit: WQ0003044
Inspection Date: 08/18/2021
Owner - Facility: Dunescape Villas Condominium Owners Association Inc
Inspection Type: Compliance Evaluation Reason for Visit: Routine
Type
Yes No NA NE
Reuse (Quality)
❑
Single Family Spray, LR
❑
Lagoon Spray, LR
❑
Activated Sludge Spray, HR
❑
Activated Sludge Spray, LR
❑
Activated Sludge Drip, LR
❑
Recycle/Reuse
❑
Single Family Drip
❑
Infiltration System
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑
Comment: No comment.
Treatment Flow Measurement -Influent Yes No NA NE
Is flowmeter calibrated annually? ❑ ❑ ❑
Is flowmeter operating properly? ❑ ❑ ❑
Does flowmeter monitor continuously? ❑ ❑ ❑
Does flowmeter record flow? ❑ ❑ ❑
Does flowmeter appear to monitor accurately? ❑ ❑ ❑
Comment: The influent flowmeter is in a location where it records the filter backwash as well as the influent
flow. This flowmeter is not used for reporting.
Treatment Flow Measurement -Water Use Records
Is water use metered?
Are the daily average values properly calculated?
Comment:
Yes No NA NE
❑❑■❑
❑❑■❑
Treatment Flow Measurement -Effluent Yes No NA NE
Is flowmeter calibrated annually? 0 ❑ ❑ ❑
Is flowmeter operating properly? ❑ ❑ ❑
Does flowmeter monitor continuously? ❑ ❑ ❑
Does flowmeter record flow? ❑ ❑ ❑
Does flowmeter appear to monitor accurately? 0 ❑ ❑ ❑
Comment: There are 3 flowmeters to each infiltration field and are used for reporting flow. They were
calibrated on 4-29-2021.
Page 3 of 6
DocuSign Envelope ID: FB11OF30-C154-46B0-9ABF-39FEFCC78271
Permit: WQ0003044 Owner - Facility: Dunescape Villas Condominium Owners Association Inc
Inspection Date: 08/18/2021 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Standby Power Yes No NA NE
Is automatically activated standby power available? 0 ❑ ❑ ❑
Is generator tested weekly by interrupting primary power source? ❑ ❑ ❑
Is generator operable? ❑ ❑ ❑
Does generator have adequate fuel? ❑ ❑ ❑
Comment: The -generator is tested weekly. It powers the plant and the influent pump station across the
street. Power was switch to the gererator when the primary power source was interrupted
during the inspection.
Treatment Activated Sludge Yes No NA NE
Is the aeration mechanism operable? 0 ❑ ❑ ❑
Is the aeration basin thoroughly mixed? 0 ❑ ❑ ❑
Is the aeration equipment easily accessed? ❑ ❑ ❑
Is Dissolved Oxygen adequate? ❑ ❑ ❑
Are Settleometer results acceptable? ❑ ❑ ❑
Is activated sludge an acceptable color? 0 ❑ ❑ ❑
Comment: Wastewater flows through a dual Integrated Surge Anoxic Mix System and dual SBRs. The
SBRs are monitored by DO probes. A settleometer test is done daily for process control. After
the clear effluent is decanted from the SBRs, it flows to a post EQ basin and then to the tertiary
filters.
Treatment Filters
Yes No NA NE
Is the filter media present? ❑ ❑ 0❑
Is the filter media the correct size and type? ❑ ❑ ❑
Is the air scour operational? ❑ ❑ ❑
Is the scouring acceptable? ❑ ❑ ❑
Is the clear well free of excessive solids? ❑ ❑ ❑
Is the mud well free of excessive solids and filter media? 0 ❑ ❑ ❑
Does backwashing frequency appear adequate? 0 ❑ ❑ ❑
Comment: The two Hydrotech teriary filters backwash automatically bV the water level or programmed time
intervals.
Treatment Disinfection
Yes No NA NE
Is the system working?
0
❑ ❑ ❑
Do the fecal coliform results indicate proper disinfection?
❑ ❑ ❑
Is there adequate detention time (-30 minutes)?
❑
❑ ❑
Is the system properly maintained?
❑ ❑ ❑
If gas, does the cylinder storage appear safe?
❑
❑ ❑
Is the fan in the chlorine feed room and storage area operable?
❑
❑ ❑
Is the chlorinator accessible?
❑
❑ ❑
If tablets, are tablets present?
❑
❑ ❑
Page 4 of 6
DocuSign Envelope ID: FB11OF30-C154-46B0-9ABF-39FEFCC78271
Permit: WQ0003044 Owner - Facility: Dunescape Villas Condominium Owners Association Inc
Inspection Date: 08/18/2021 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Are the tablets the proper size and type?
❑
❑ 0 ❑
Is contact chamber free of sludge, solids, and growth?
❑
❑ 0 ❑
If UV, are extra UV bulbs available?
0
❑ ❑ ❑
If UV, is the UV intensity adequate?
❑
❑ ❑
# Is it a dual feed system?
❑
❑ 0 ❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
❑
❑ 0 ❑
If yes, then is there a Risk Management Plan on site?
❑
❑ 0 ❑
If yes, then what is the EPA twelve digit ID Number? (1000- - )
If yes, then when was the RMP last updated?
Comment: There are 2 Trojan UV disinfection units in series.
Record Keeping
Yes No NA NE
Is a copy of current permit available?
❑ ❑ ❑
Are monitoring reports present: NDMR?
❑ ❑ ❑
NDAR?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are application rates adhered to?
❑ ❑ ❑
Is GW monitoring being conducted, if required (GW-59s submitted)?
❑ ❑ ❑
Are all samples analyzed for all required parameters?
❑ ❑ ❑
Are there any 2L GW quality violations?
❑ ❑ ❑
Is GW-59A certification form completed for facility?
❑
❑ ❑
Is effluent sampled for same parameters as GW?
❑ ❑ ❑
Do effluent concentrations exceed GW standards?
❑
❑ ❑
Are annual soil reports available?
❑
❑ ❑
# Are PAN records required?
❑
❑ ❑
# Did last soil report indicate a need for lime?
❑
❑ ❑
If so, has it been applied?
❑
❑ ❑
Are operational logs present?
❑ ❑ ❑
Are lab sheets available for review?
❑ ❑ ❑
Do lab sheets support data reported on NDMR?
❑ ❑ ❑
Do lab sheets support data reported on GW-59s?
❑
❑ ❑
Are Operational and Maintenance records present?
❑ ❑ ❑
Were Operational and Maintenance records complete?
❑ ❑ ❑
Has permittee been free of public complaints in last 12 months?
0
❑ ❑ ❑
Is a copy of the SOC readily available?
❑
❑ 0 ❑
No treatment units bypassed since last inspection?
0
❑ ❑ ❑
Page 5 of 6
DocuSign Envelope ID: FB11OF30-C154-46B0-9ABF-39FEFCC78271
Permit: WQ0003044 Owner - Facility: Dunescape Villas Condominium Owners Association Inc
Inspection Date: 08/18/2021 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Comment: Operation/maintenance records were available for review and were complete. Field parameters
are performed by staff, Certification #5660. Calibration records for pH were complete.
Environment 1, Inc, Certification #10, analyzes the effluent and monitoring well parameters.
Since the last inspection in 2019, MW #6 shows some exceedances for TDS.
End Use -Infiltration Yes No NA NE
# Is the application High Rate or Low Rate? High Rate
Are buffers maintained?
❑
0 ❑ ❑
Are any supply wells within the CB?
❑
0 ❑ ❑
Are any supply wells within 250' of the CB?
❑
0 ❑ ❑
Is municipal water available in the area?
0
❑ ❑ ❑
Are GW monitoring wells required?
0
❑ ❑ ❑
Are GW monitoring wells located properly w/ respect to RB and CB?
❑
0 ❑ ❑
Are GW monitoring wells properly constructed, including screened interval?
❑
❑ ❑
Is a usable green area maintained?
0
❑ ❑ ❑
Is the disposal site acceptable?
0
❑ ❑ ❑
Is the distribution equipment acceptable?
0
❑ ❑ ❑
Is the disposal site free of ponding?
0
❑ ❑ ❑
Is the disposal site free of breakout?
0
❑ ❑ ❑
Are the disposal sites free of solids, algae, etc.?
0
❑ ❑ ❑
Do the records show that the fields are properly maintained?
0
❑ ❑ ❑
Are the disposal sites free of vegetation?
0
❑ ❑ ❑
Do any surface water features appear to be adversely impacted by GW discharge?
❑
0 ❑ ❑
No chemicals or rototiller used to eliminate vegetation, solids, algae, etc.?
0
❑ ❑ ❑
Comment: This facility was originally permitted prior to 2T rules. Setbacks of the high -rate fields do not
comply with 2T and MW-4, MW-5 and MW-6 are located within the review boundary.
The
location of the MWs will be re-evaluated during the renewal process. The 3 high -rate fields
were well maintained.
Page 6 of 6