HomeMy WebLinkAboutWQ0002005_Compliance Evaluation Inspection_20210819DocuSign Envelope ID: AFDEB4DO-05F3-4FF9-8328-90AOEC245OFF
� �E srArE
ROY COOPER_, >I,
Governor
- o
ELIZABETH S. BISER
Secretary �O
S. DANIEL SMITH NORTH CAROLINA
Director Environmental Quality
August 30, 2021
Chris Murray, Cooperate Environmental Manager
House of Raeford Farms Inc.
PO Box 40
Rose Hill, NC 28458-0040
SUBJECT: Compliance Inspection Report
House of Raeford - Rose Hill WWTF
Non -discharge Permit No. WQ0002005
Duplin County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the House of Raeford -
Rose Hill WWTF on 8/19/2021. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in Non -discharge Permit No. WQ0002005. The
findings and comments noted during this inspection are provided in the enclosed copy of the inspection
report entitled "Compliance Inspection Report". There were no significant issues or findings noted during
the inspection and therefore, a response to this inspection report is not required.
If you should have any questions, please do not hesitate to contact Helen Perez with the Water
Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
helen.perez@ncdenr.gov.
Sincerely,
DocuSigned by:
I-TD,'-',l
On,
E7366F3456...
Morelia Sanchez -King, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: Drew Mason — electronic copy
Upload to Laserfiche
D_E Q�North Carolina Department of Environmental Quality I Division of Water Resources
Wilmington Regional Office 1 127 Cardinal Drive Extension I Wilmington, North Carolina 28405
mw�.mwemwm.m.i a.,� /`� 910.796.7215
DocuSign Envelope ID: AFDEB4DO-05F3-4FF9-8328-90AOEC2450FF
Compliance Inspection Report
Permit: WQ0002005 Effective: 03/01/19 Expiration: 10/31/23 Owner : House of Raeford Farms Inc
SOC: Effective: Expiration: Facility: House of Raeford - Rose Hill WWTF
County: Duplin 3333 US 117 N
Region: Wilmington
Rose Hill NC 28458
Contact Person: Joseph D Teachey Title: ORC Phone: 910-284-0148
Directions to Facility:
System Classifications: SI,
Primary ORC: Joseph D Teachey
Secondary ORC(s):
On -Site Representative(s):
On -site representative
Certification: 14930
Chris S Murray
Phone: 910-284-0148
910-289-6952
Related Permits:
WQ0000040 House of Raeford Farms Inc - Rose Hill Hatchery Complex Pump Station
WQ0001481 House of Raeford Farms Inc - House of Raeford - Rose Hill WWTF
Inspection Date: 08/19/2021 Entry Time 09:OOAM Exit Time: 10:OOAM
Primary Inspector: Helen I Perez Docusi9netd�by: Phone: 910-796-7387
Secondary Inspector(s):L r
1D645B4A39694BE_
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Wastewater Irrigation
Facility Status: Compliant Not Compliant
Question Areas:
Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent Miscellaneous Questions
Treatment Flow Measurement -Water Treatment Record Keeping
Use Records
End Use -Irrigation Treatment Disinfection Treatment Flow Measurement
(See attachment summary)
Page 1 of 5
DocuSign Envelope ID: AFDEB4DO-05F3-4FF9-8328-90AOEC245OFF
Permit: WQ0002005 Owner - Facility: House of Raeford Farms Inc
Inspection Date: 08/19/2021 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
A routine compliance inspection of the House of Raeford -Rose Hill WWTF was conducted on August 19, 2021. The purpose
of the evaluation was to verify that the facility is operating in compliance with the conditions and limitations specified in
Permit WQ0002005. Chris Murray and Drew Mason were present during the inspection.
This 800,000 gpd facultative lagoon wastewater treatment and irrigation system serves the House of Raeford industrial plant
and hatchery. Influent from the plant and the hatchery pump stations flow through the dissolved air flotation (DAF) unit.
Solids collected from the DAF are hauled to Valley Proteins a few times a day. Wastewater then flows through two 7.7 MG
facultative lagoons in series. Freeboard in lagoon #1 was 25 inches and lagoon #2 was 35 inches on day of the inspection.
Solids were removed from Lagoon #1 in 2014 before the new DAF unit was started. Staff indicated that there has been
minimal solid accumulation since using the DAF. Effluent is stored in the 35 MG irrigation pond before irrigating on the 137
acres of spray area served by a traveling bridge, center -pivot and solid -set irrigation system.
A review of files show 2L limit exceedances of TDS and Ammonia in monitoring wells located around the lagoons. The
Wilmington Regional Office continues to monitor these trends. The current permit, Attachment C, footnote 1, states that the
monitoring wells should be sampled in March, July and November. The facility is sampling in February, June and September
as in the last permit requirement. Please continue to sample on these months and a correction can be made on the next
permit cycle to reflect back to the February, June and September months.
The facility is compliant with Non -Discharge Permit WQ0002005. Please review the comment sections of the inspection
report for more details.
Page 2 of 5
DocuSign Envelope ID: AFDEB4DO-05F3-4FF9-8328-90AOEC2450FF
Permit: WQ0002005
Inspection Date: 08/19/2021
Owner - Facility: House of Raeford Farms Inc
Inspection Type: Compliance Evaluation Reason for Visit: Routine
Type
Yes No NA NE
Reuse (Quality)
❑
Infiltration System
❑
Activated Sludge Spray, LR
❑
Single Family Spray, LR
❑
Activated Sludge Drip, LR
❑
Activated Sludge Spray, HR
❑
Single Family Drip
❑
Recycle/Reuse
❑
Lagoon Spray, LR
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑
Comment: Staff uses polymer addition to optimize the DAF unit.
Treatment Flow Measurement -Influent Yes No NA NE
Is flowmeter calibrated annually? 0 ❑ ❑ ❑
Is flowmeter operating properly? ❑ ❑ ❑
Does flowmeter monitor continuously? ❑ ❑ ❑
Does flowmeter record flow? ❑ ❑ ❑
Does flowmeter appear to monitor accurately? 0 ❑ ❑ ❑
Comment: The influent flowmeter from the plant was calibrated on 4-14-2021 by AMS. Influent flow from
the hatchery is monitored by water usage at the site.
Treatment Flow Measurement -Water Use Records Yes No NA NE
Is water use metered? ❑ 1:10 ❑
Are the daily average values properly calculated? ❑ ❑ 0 ❑
Comment:
Treatment Flow Measurement -Effluent
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Does flowmeter appear to monitor accurately?
Comment: The effluent flowmeter was calibrated on 4-14-2021 by AMS and is used for reporting_
Yes No NA NE
■❑❑❑
❑❑❑■
■❑❑❑
■❑❑❑
■❑❑❑
Treatment Disinfection Yes No NA NE
Page 3 of 5
DocuSign Envelope ID: AFDEB4DO-05F3-4FF9-8328-90AOEC2450FF
Permit: WQ0002005 Owner - Facility: House of Raeford Farms Inc
Inspection Date: 08/19/2021 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Is the system working?
Do the fecal coliform results indicate proper disinfection?
Is there adequate detention time (>=30 minutes)?
Is the system properly maintained?
If gas, does the cylinder storage appear safe?
Is the fan in the chlorine feed room and storage area operable?
Is the chlorinator accessible?
If tablets, are tablets present?
Are the tablets the proper size and type?
Is contact chamber free of sludge, solids, and growth?
If UV, are extra UV bulbs available?
If UV, is the UV intensity adequate?
# Is it a dual feed system?
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1 000-- )
If yes, then when was the RMP last updated?
■❑❑❑
❑❑■❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑❑■❑
❑❑■❑
■❑❑❑
■❑❑❑
■❑❑❑
❑❑■❑
❑❑■❑
❑❑■❑
Comment: Currently pH and Total Residual Chlorine is tested 5 days a week by Envirochem, Certification
#94. The permit only requires sampling of pH and TRC per irrigation event. Afield lab
certification can be obtained through the State Lab Certification Unit so sampling and testing
could be done by the facility. Information will be provided for applying for certification.
Record Keeping
Yes No NA NE
Is a copy of current permit available?
❑
❑ ❑
Are monitoring reports present: NDMR?
❑
❑ ❑
NDAR?
❑
❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are application rates adhered to?
❑ ❑ ❑
Is GW monitoring being conducted, if required (GW-59s submitted)?
❑ ❑ ❑
Are all samples analyzed for all required parameters?
❑ ❑ ❑
Are there any 2L GW quality violations?
❑ ❑ ❑
Is GW-59A certification form completed for facility?
❑
❑ ❑
Is effluent sampled for same parameters as GW?
❑ ❑ ❑
Do effluent concentrations exceed GW standards?
❑ ❑ ❑
Are annual soil reports available?
❑ ❑ ❑
# Are PAN records required?
❑ ❑ ❑
# Did last soil report indicate a need for lime?
❑0
❑ ❑
Page 4 of 5
DocuSign Envelope ID: AFDEB4DO-05F3-4FF9-8328-90AOEC245OFF
Permit: WQ0002005 Owner - Facility: House of Raeford Farms Inc
Inspection Date: 08/19/2021 Inspection Type: Compliance Evaluation Reason for Visit: Routine
If so, has it been applied? ❑ ❑ 0 ❑
Are operational logs present? 0 ❑ ❑ ❑
Are lab sheets available for review? ❑ ❑ ❑
Do lab sheets support data reported on NDMR? ❑ ❑ ❑
Do lab sheets support data reported on GW-59s? ❑ ❑ ❑
Are Operational and Maintenance records present? 0 ❑ ❑ ❑
Were Operational and Maintenance records complete? 0 ❑ ❑ ❑
Has permittee been free of public complaints in last 12 months? ❑ ❑ ❑
Is a copy of the SOC readily available? ❑ ❑ 0 ❑
No treatment units bypassed since last inspection? 0 ❑ ❑ ❑
Comment: Annual soil analysis was completed in October 2020. In addition, the two interim and annual
soil agronomist reports were submitted to the Wilmington Regional Office as required. There
are Ammonia and TDS 2L exceedances in the wells located around the lagoons. The
Wilminaton Reaional Office continues to monitor these trends.
End Use -Irrigation
Yes No NA NE
Are buffers adequate?
0
❑ ❑ ❑
Is the cover crop type specified in permit?
❑
❑ ❑
Is the crop cover acceptable?
❑ ❑ ❑
Is the site condition adequate?
❑ ❑ ❑
Is the site free of runoff / ponding?
❑ ❑ ❑
Is the acreage specified in the permit being utilized?
❑ ❑ ❑
Is the application equipment present?
❑ ❑ ❑
Is the application equipment operational?
❑
❑ ❑
Is the disposal field free of limiting slopes?
❑ ❑ ❑
Is access restricted and/or signs posted during active site use?
❑ ❑ ❑
Are any supply wells within the CB?
❑ ❑ ❑
Are any supply wells within 250' of the CB?
❑
❑ ❑
How close is the closest water supply well?
❑
❑ ❑
Is municipal water available in the area?
❑ ❑ ❑
# Info only: Does the permit call for monitoring wells?
❑ ❑ ❑
Are GW monitoring wells located properly w/ respect to RB and CB?
❑ ❑ ❑
Are GW monitoring wells properly constructed, including screened interval?
❑
❑ ❑
Are monitoring wells damaged?
❑
❑ ❑
Comment: All fields were viewed except the soild-set irrigation system fields 5-13, 6-A, 6-B.
Fields were in
good condition but some were in need of cutting. HOR staff cut and bale between rain events
when field conditions allow. HOR uses a computerized program, Field Net, that allows them to
operate the irrigation system by computer or phone to optimize spraying events.
The 35 MG
storage pond had a freeboard of 39 inches.
Page 5 of 5