HomeMy WebLinkAboutWQ0000224_Compliance Evaluation Inspection_20210818DocuSign Envelope ID: 68A6D362-OC12-4D75-8590-62E661 EFC83F
ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
S. DANIEL SMITH
Director
Crystal Walters, Association Manager
Point Emerald Villas Association Inc.
PO Box 4455
Emerald Isle, NC 28594-4455
rcSTATE r
NORTH CAROLINA
Environmental Quality
August 25, 2021
SUBJECT: Compliance Inspection Report
Point Emerald Villas WWTF
Non -discharge Permit No. WQ0000224
Carteret County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Point Emerald Villas
WWTF on 8/18/2021. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in Non -discharge Permit No. WQ0000224. The
findings and comments noted during this inspection are provided in the enclosed copy of the inspection
report entitled "Compliance Inspection Report". There were no significant issues or findings noted during the
inspection and therefore, a response to this inspection report is not required.
If you should have any questions, please do not hesitate to contact Helen Perez with the Water
Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
helen.perez@ncdenr.gov.
Sincerely,
EDocuSigned by:
Mon cllk Sr.�r•a� K�
E3ABA14AC7DC434...
Morella Sanchez -King, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: Dan Fortin — electronic copy
Upload to Laserfiche
DE Q�� North Carolina Department of Environmental Quality I Division of Water Resources
Wilmington Regional Office 1 127 Cardinal Drive Extension I Wilmington, North Carolina 28405
910.796.7215
DocuSign Envelope ID: 68A6D362-OC12-4D75-8590-62E661 EFC83F
Compliance Inspection Report
Permit: WQ0000224 Effective: 11/01/16 Expiration: 10/31/21 Owner: Point Emerald Villas Association Inc
SOC: Effective: Expiration: Facility: Point Emerald Villas WWTF
County: Carteret Coast Guard Rd
Region: Wilmington
Emerald Isle NC 28594
Contact Person: Jaye Spring
Directions to Facility:
Title:
Phone: 252-354-6333
Located on the western end of Bogue Banks on the south side of Coast Guard Road approximately 1.8 miles west of the stoplight
on Salter Path Road
System Classifications: WW2,
Primary ORC: Robert C Howard Certification: 996013 Phone: 252-241-5460
Secondary ORC(s):
On -Site Representative(s):
On -site representative
Related Permits:
Daniel Edward Fortin
252-393-8720
Inspection Date: 08/18/2021 Entry Time 01:20PM Exit Time: 02:25PM
Primary Inspector: Helen I Perez DocuSignetd�by: Phone: 910-796-7387
Secondary Inspector(s): r DocuSigned by:
E 39694 E...
Tyler G Benson ' i b_r btA&Sbla,
06DCAE2DD754468...
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: High Rate Infiltration
Facility Status: 0 Compliant ❑ Not Compliant
Question Areas:
Treatment Flow Measurement -Effluent
Treatment Flow Measurement -Water
Use Records
Treatment Filters
Treatment Influent Pump Station
End Use -Infiltration
Standby Power
(See attachment summary)
Treatment Flow Measurement -Influent Miscellaneous Questions
Treatment Treatment Barscreen
Record Keeping Treatment Activated Sludge
Treatment Clarifiers Treatment Disinfection
Treatment Flow Measurement Treatment Return pumps
Page 1 of 7
DocuSign Envelope ID: 68A6D362-OC12-4D75-8590-62E661 EFC83F
Permit: WQ0000224 Owner - Facility: Point Emerald Villas Association Inc
Inspection Date: 08/18/2021 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
A routine compliance inspection of the Point Emerald Villas WWTF was conducted on August 18, 2021. The purpose of the
evaluation was to verify that the facility is operating in compliance with the conditions and limitations specified in Permit
WQ0000224. Operators from Fortin Contract Service were present during the inspection.
The current permit expires on October 31, 2021. A renewal application was received on August 6, 2021 and is under review.
This facility is an extended aeration plant with high -rate infiltration and low pressure pipe, subsurface disposal systems. The
average flow for this 52,950 gpd permitted facility in 2020 was approximatedly 4300 gpd. The rotary distributor system was
replaced in 2019 and appears to be in good condition.
A review of monitoring reports, since the last permit renewal, shows a daily fecal exceedance in June 2019 and a NOV
issued for a monthly ammonia limit exceedance in August 2018. The GW-59s show limit exceedances in TOC and TDS in
MW-4. The Wilmington Regional Office will continue to monitor this trend in MW-4. Although reported effluent nitrate is
relatively high, there is no current permit limit for nitrate, and there were no nitrate 2L violations in any of the wells. The
treatment plant is not designed for den itrification.
The facility is compliant with Non -Discharge Permit WQ0000224. Please review the comment sections of the inspection
report for more details.
Page 2 of 7
DocuSign Envelope ID: 68A6D362-OC12-4D75-8590-62E661 EFC83F
Permit: WQ0000224
Owner - Facility: Point Emerald Villas Association Inc
Inspection Date: 08/18/2021
Inspection Type: Compliance Evaluation Reason for Visit: Routine
Type
Yes No NA NE
Reuse (Quality)
❑
Single Family Spray, LR
❑
Lagoon Spray, LR
❑
Activated Sludge Spray, HR
❑
Activated Sludge Spray, LR
❑
Activated Sludge Drip, LR
❑
Recycle/Reuse
❑
Single Family Drip
❑
Infiltration System
Treatment
Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? ❑ 0 ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑
Comment: The current permit description lists an aeration tank and a settlinq tank. There are 2 aeration
tanks of different volumes on site. Also, there are dual clarifiers and dual sand filters that are
not listed in the permit description as well as a manual bar sceen at the EQ tank.
Treatment Influent Pump Station
Yes No NA NE
Is the pump station free of bypass lines or structures?
❑
❑ ❑
Is the general housekeeping acceptable?
❑
❑ ❑
Are all pumps present?
❑
❑ ❑
Are all pumps operable?
❑
❑ ❑
Are floats/controls operable?
❑
❑ ❑
Are audio and visual alarms available?
❑
❑ ❑
Are audio and visual alarms operational?
❑
❑ ❑
# Are SCADA/Telemetry alarms required?
❑
❑ ❑
Are SCADA/Telemetry available?
❑
❑ ❑
Are SCADA/Telemetry operational?
❑
❑ 0 ❑
Comment: The influent pump station was not inspected
during this site visit. The pump station has audio
and visual alarms. The maintenance person
at the Villas alert operators of any alarms.
Treatment Flow Measurement -Influent
Yes No NA NE
Is flowmeter calibrated annually?
❑
❑ 0 ❑
Is flowmeter operating properly?
❑
❑ 0 ❑
Does flowmeter monitor continuously?
❑
❑ 0 ❑
Does flowmeter record flow?
❑
❑ 0 ❑
Does flowmeter appear to monitor accurately?
❑
❑ 0 ❑
Page 3 of 7
DocuSign Envelope ID: 68A6D362-OC12-4D75-8590-62E661 EFC83F
Permit: WQ0000224 Owner - Facility: Point Emerald Villas Association Inc
Inspection Date: 08/18/2021 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Comment:
Treatment Flow Measurement -Water Use Records Yes No NA NE
Is water use metered? ❑ ❑ ❑
Are the daily average values properly calculated? ❑ ❑ 0 ❑
Comment:
Treatment Flow Measurement -Effluent
Yes No NA NE
Is flowmeter calibrated annually?
0
❑ ❑ ❑
Is flowmeter operating properly?
❑
❑ ❑
Does flowmeter monitor continuously?
❑ ❑ ❑
Does flowmeter record flow?
❑ ❑ ❑
Does flowmeter appear to monitor accurately?
❑ ❑ ❑
Comment: The flowmeter was calibrated on 4-30-21.
Standby Power Yes No NA NE
Is automatically activated standby power available? ❑ ❑ ❑
Is generator tested weekly by interrupting primary power source? ❑ ❑ ❑
Is generator operable? ❑ ❑ ❑
Does generator have adequate fuel? ❑ ❑ ❑
Comment: The generator on site has not been operable for 3-4 months. The operators currently have
access to a portable generator. A generator has been ordered and will be leased and serviced
by Power House, Inc.
Treatment Barscreen Yes No NA NE
Is it free of excessive debris? 0 ❑ ❑ ❑
Is disposal of screenings in compliance? 0 ❑ ❑ ❑
Are the bars spaced properly? ❑ ❑ ❑
Is the unit in good condition? 0 ❑ ❑ ❑
Comment: The maual barscreen is located where the influent enters the EQ tank.
Treatment Activated Sludge Yes No NA NE
Is the aeration mechanism operable? ❑ ❑ ❑
Is the aeration basin thoroughly mixed? ❑ ❑ ❑
Is the aeration equipment easily accessed? ❑ ❑ ❑
Is Dissolved Oxygen adequate? ❑ ❑ ❑
Are Settleometer results acceptable? ❑ ❑ ❑
Is activated sludge an acceptable color? 0 ❑ ❑ ❑
Comment: The EQ basin had an accumulation of grease. Barnes Environmental is scheduled to pump the
grease and solids soon. From the EQ basin, influent flow through a splitter box to 2 aeration
tanks of different sizes. Air appeared to be evenly distributed and color was acceptable in both
aeration tanks.
Page 4 of 7
DocuSign Envelope ID: 68A6D362-OC12-4D75-8590-62E661 EFC83F
Permit: WQ0000224 Owner - Facility: Point Emerald Villas Association Inc
Inspection Date: 08/18/2021 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Treatment Clarifiers Yes No NA NE
Are the weirs level? 0 ❑ ❑ ❑
Are the weirs free of solids and algae? 0 ❑ ❑ ❑
Is the scum removal system operational? ❑ ❑ ❑
Is the scum removal system accessible? ❑ ❑ ❑
Is the sludge blanket at an acceptable level? ❑ ❑ ❑
Is the effluent from the clarifier free of excessive solids? ❑ 0 ❑ ❑
Comment: The surface of one clarifier had excessive solids. Operator stated that Barnes Environmental is
scheduled to remove solids soon.
Treatment Return pumps Yes No NA NE
Are they in place? 0 ❑ ❑ ❑
Are they operational? 0 ❑ ❑ ❑
Comment: No comment.
Treatment Filters
Yes No NA NE
Is the filter media present?
❑
❑ ❑
Is the filter media the correct size and type?
❑
❑ ❑
Is the air scour operational?
❑
❑ ❑
Is the scouring acceptable?
❑
❑ ❑
Is the clear well free of excessive solids?
❑ ❑ ❑
Is the mud well free of excessive solids and filter media?
❑ ❑ ❑
Does backwashing frequency appear adequate?
❑ ❑ ❑
Comment: No comment.
Treatment Disinfection
Yes No NA NE
Is the system working?
❑ ❑ ❑
Do the fecal coliform results indicate proper disinfection?
❑ ❑ ❑
Is there adequate detention time (>=30 minutes)?
❑
❑ ❑
Is the system properly maintained?
❑ ❑ ❑
If gas, does the cylinder storage appear safe?
❑
❑ ❑
Is the fan in the chlorine feed room and storage area operable?
❑
❑ ❑
Is the chlorinator accessible?
❑ ❑ ❑
If tablets, are tablets present?
❑ ❑ ❑
Are the tablets the proper size and type?
❑ ❑ ❑
Is contact chamber free of sludge, solids, and growth?
❑ ❑ ❑
If UV, are extra UV bulbs available?
❑
❑ ❑
If UV, is the UV intensity adequate?
❑
❑ ❑
Page 5 of 7
DocuSign Envelope ID: 68A6D362-OC12-4D75-8590-62E661 EFC83F
Permit: WQ0000224 Owner - Facility: Point Emerald Villas Association Inc
Inspection Date: 08/18/2021 Inspection Type: Compliance Evaluation Reason for Visit: Routine
# Is it a dual feed system? ❑ ❑ 0 ❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)? ❑ ❑ 0 ❑
If yes, then is there a Risk Management Plan on site? ❑ ❑ ❑
If yes, then what is the EPA twelve digit ID Number? (1 000-- )
If yes, then when was the RMP last updated?
Comment: The last fecal limit exceedance was a daily exceedance in June 2019.
Record Keeping
Yes No NA NE
Is a copy of current permit available?
❑ ❑ ❑
Are monitoring reports present: NDMR?
❑
❑ ❑
NDAR?
❑
❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are application rates adhered to?
❑ ❑ ❑
Is GW monitoring being conducted, if required (GW-59s submitted)?
❑ ❑ ❑
Are all samples analyzed for all required parameters?
❑ ❑ ❑
Are there any 2L GW quality violations?
❑
❑ ❑ ❑
Is GW-59A certification form completed for facility?
❑
❑ ❑
Is effluent sampled for same parameters as GW?
❑ ❑ ❑
Do effluent concentrations exceed GW standards?
❑
❑ ❑
Are annual soil reports available?
❑
❑ ❑
# Are PAN records required?
❑
❑ ❑
# Did last soil report indicate a need for lime?
❑
❑ ❑
If so, has it been applied?
❑
❑ ❑
Are operational logs present?
❑ ❑ ❑
Are lab sheets available for review?
❑
❑ ❑
Do lab sheets support data reported on NDMR?
❑
❑ ❑
Do lab sheets support data reported on GW-59s?
❑
❑ ❑
Are Operational and Maintenance records present?
❑ ❑ ❑
Were Operational and Maintenance records complete?
❑ ❑ ❑
Has permittee been free of public complaints in last 12 months?
❑
❑ ❑
Is a copy of the SOC readily available?
❑
❑ ❑
No treatment units bypassed since last inspection?
0
❑ ❑ ❑
Comment: A review of monitoring reports since the last permit renewal shows an NOV issued for a monthly
ammonia limit exceedance in August 2018 and a daily fecal limit exceedance in June 2019.
The
GW-59s show limit exceedances in TOC and TDS in MW-4.
Although reported effluent nitrate
is relatively high, there is no current permit limit for nitrate and there were no nitrate 2L
violations in any of the wells. The treatment plant is not designed
for denitrification.
Page 6 of 7
DocuSign Envelope ID: 68A6D362-OC12-4D75-8590-62E661 EFC83F
Permit: WQ0000224 Owner - Facility: Point Emerald Villas Association Inc
Inspection Date: 08/18/2021 Inspection Type: Compliance Evaluation Reason for Visit: Routine
End Use -Infiltration
Yes No NA NE
# Is the application High Rate or Low Rate?
High
Rate
Are buffers maintained?
0
❑ ❑ ❑
Are any supply wells within the CB?
❑
❑ ❑
Are any supply wells within 250' of the CB?
❑
❑ ❑
Is municipal water available in the area?
❑ ❑ ❑
Are GW monitoring wells required?
❑ ❑ ❑
Are GW monitoring wells located properly w/ respect to RB and CB?
❑
❑ ❑
Are GW monitoring wells properly constructed, including screened interval?
❑
❑ ❑
Is a usable green area maintained?
❑ ❑ ❑
Is the disposal site acceptable?
❑ ❑ ❑
Is the distribution equipment acceptable?
❑ ❑ ❑
Is the disposal site free of ponding?
❑ ❑ ❑
Is the disposal site free of breakout?
❑ ❑ ❑
Are the disposal sites free of solids, algae, etc.?
❑ ❑ ❑
Do the records show that the fields are properly maintained?
❑
❑ ❑
Are the disposal sites free of vegetation?
❑ ❑ ❑
Do any surface water features appear to be adversely impacted by GW discharge?
❑
❑ ❑
No chemicals or rototiller used to eliminate vegetation, solids, algae, etc.?
0
❑ ❑ ❑
Comment: The rotary distributor was replaced in 2019 and appeared to be in good condition
when in
operation. The infiltration field was well maintained. The operator alternates disposal between
the low pressure pipe (LPP) subsurface system and the high -rate infiltration field.
There is
some vegetation that needs to be removed from the LPP field. The cap on MW-5
(2018 NOD)
has been replaced.
Page 7 of 7