HomeMy WebLinkAboutWQ0017700_Regional Office Historical File Pre 2018A T.c _ Michael F. Easley, Governor
William G. Ross Jr„ Secretary
North Carolina pa en of Environment and Natural Resources
Alan W. Klimek, P„E., Director
Division of Water Quality
Coleen H. Sullins, Deputy Director
Division of Water Quality
Mr. Phil Levin, General Partner
Braemar Housing Limited Partnership
850 Chicago Road
Troy, Michigan 48083
Dear Mr, Levin:
February 3, 2004
Subject: Application No. WQ0017700 Mod,
Additional Information Request
The Residences at Braemar Project
Wastewater Collection System Extension`
Mecklenburg County, North Carolina
The Division of Water Quality's Mooresville Regional Office has conducted a preliminary
review of the subject permit application package. Additional information is required before we
may continue our review, Please address the following items no later than March 5, 2004.
1. Please submit final engineering certification and 2 copies of as -built plans (not design).
2. Please clarify status of 1,016 linear feet of 8-inch gravity sewer in regards to the requested
permit modification (8-inch line was permitted in December 2, 1999 permit).
Please be aware that you are responsible for meeting all requirements set forth in North
Carolina rules and regulations. Any oversights that occurred in the review of the subject
application package are still the responsibility of the applicant. In addition, any omissions made
in responding to the above items may result in future requests for additional information.
Please reference the subject application number when providing the requested information.
Two copies of all revised and/or additional documentation should be signed, sealed, dated, and
submitted to my attention at the address below. Please note that failure to provide this
additional information on or before the above requested date may result in your application
being returned as incomplete.
If you have any questions regarding this request, please contac
Thank you for your cooperation.
Cc: Hal Bailey, Engineering Concepts, Inc.
FT Application File WQ0017700 Mod
le at (704) 663-1699.
Sincerely,
a,r- `i4,72� ,/. ac
Sonja Williams
Consultant
Mooresville Regional Office
919 N. Main Street, Mooresville, NC 28115
Internet http:/lh2o.enr.state.nc.usl
Telephone (704) 663-1699 Fax (704
6
0
DENR Customer Service Center
An Equal Opportunity Action Employer
Telephone 1 800 623-7748
50% recyced/10% post -consumer paper
r' t. fewer remitting - Kesniences at tlnwrnar
Subject:: N+C Sewer Permitting Residences at Braemar
Date: Fri, 19 Dec 2003 12:13:44 -0500
From: "Marie Doklovic" <nxarie.doklovic@nctriail..net>
To:<jeiinwaod@engineeringcancepts.com>
CC: "sonja williarns" <sonja.williams(01CMai1.Net>
Dear Mr, Ellin
Per our telephone conversatitan, the Division needs a permit application to modify Permit No. WQ0017700 (original attached).
The permit application to use is our Fast -Track application - Form FTA 02/03 Rev, 1. This can he downloaded in Word or PDF
format from http.//h2 y_jttr suttee c usindl: ully,,,tiriippjitrnl. As we discussed, the application instructions will tell you everything
you noel to complete the application and where to stand it. Only indicate the modifications to the permit and do not duplicate
information that is already in the permit.. A clear explanation, of the situation will help expedite processing.
Since our .Fast -Track process is administrative, please ensure that
i)) and our minimum design. criteria documents. 1 have attached
minimum. design criteiia documents at the address above,
)u
ith our regulations (1.5A NCAC 211 219 (h
our regulations. You can review the
Lastly, attached for future refet-encc is the NC General Statute pertaining tit o on tructiot
143-215,1). Please also see htipla2o ztr tote ..t aline pain 1, opal, itnnl#fl earnit as thi
the Division. The existing permit conditions also discuss the Engineering Certification.
of sewers/treatment works (GS
Since the pump station/force main has already been constructed, I would send the comple
record draacrin.gs and sealed pump station ealculation.s along with your permit application,
pl
vhen a permit is needed. from
Certification, final
If you have any additional questions, please contact n'tc, if you have quest o ns about the fast track application spc'o if tally, yt u
can also contact Sonja Williams at our Mooresville Regional Office.
Thanks,
Marie Doklovie
K. Marie l)oklovie, PE
Environmental Engineer
Division of Witt Quality
Non -Discharge Permitting l nit
Doklovic <marie.doklovic@nc1 na;
Environmental Engineer
Division of Water Quality
Non -Discharge Permitting Unit
1 of 2
213/200411°35 AM
Re: Residences at Braemar WQ0017700 Mod
Subject: Re: Residences at Braemar WQ0017700 Mod
Date: Wed, 17 Mar 2004 12:07:41 -0500
From: "Marie Doklovic" <marie.doklovic@ncmail.net>
To: "Sonja Williams" <Sonja.Williams@ncmail.net>
Miss Sonja,
I have reviewed the calcs and per the MDC, no variance is requested. It appears that based on the last 3 years outage data, 37
minutes was the longest outage. They have 2.4 hours storage assuming full flow and 24.1 hr storage based on their
assumption that water usage would drop to 10% of normal in an outage. Please put the following as the last condition in the
permit:
The waters which may be impacted in the event of a power failure at the pump station permitted herein
are classified as C. In accordance with 15A NCAC 2H .0219 (h)(3) and the Minimum Design Criteria
for the Fast -Track Permitting of Pump Stations and Force Mains, SEction 5.04(B)(4), a letter of power
reliability for the subject area has been provided from Duke Power Company, and included in the
application package. Sufficient storage shall be provided in the pump station wet well above the high
water alarm level to hold the wastewater expected to become tributary to the pump station during the
maximum power outage time as determined from the last three years of outage data. The selection of
this power reliability option does not relieve the applicant of liability or future enforcement actions
should a discharge of wastewater occur at the pump station. Furthermore, it is strongly recommended
that telemetry be installed as well as a portable generator receptacle.
Don't forget to also include the language about, issuance of this permit does not relieve the Permittee from
enforcement actions for construction not in accordance with the original permit. And, since they submitted a
certification, you can take out the permit condition relating to submittal of that and delete the certification page.
Thanks, Marie
K. Marie Doklovic, PE
Environmental Engineer
Division of Water Quality
Non -Discharge Permitting Unit
Original Message
From: Sonja Williams
To: Marie.Doklovic r( ncmail.net
Sent: Tuesday, March 16, 2004 4:05 PM
Subject: Residences at Braemar WQ0017700 Mod
Marie,
I have sent you a fax regarding the calculations for the wet well
storage. Duke Power
has sent them a 3 year power outage summary with 37 minutes being the
longest outage. Please review the faxed documents and let me know if I
can issue the permit with wet well storage (this is the facility that is
construction without a permit). Also, how do I write it in the permit?
Thanks.
Sonja Williams - Sonja.Williams@ncmail.net
1 of 2 3/17/2004 12:20 PM