HomeMy WebLinkAboutWQ0010438_Regional Office Historical File Pre 2018cc: Mecklenburg County Health Department
Mooresville Regional Office, Water Quality
Russell S. Rozzelle, Mecklenburg County Environmental Protection
Camp Dresser & McKee
orth Carolina -
artment of Environment,
ealth and Natural Resources
Division of Environmental Management
James B. Hunt, Jr., Governor
Jonathan B. Howes, Secretary
A. Preston Howard, Jr., P.E., Director
Mr. Douglas Bean, Director
Charlotte -Mecklenburg Utility Department
5100 Brookshire Boulevard
Charlotte, North Carolina 28216
Dear Mr. Bean:
r 1. t.lY 7'i1/NLIt=t7.t!r -
`'�� a �� 6.11111AL RESOURCES
'.LE PFGIONAL OFFICE
1IEHN
EMI 1 1 200r
December 11, 1995
i7ATER QUALITY SECTIO
Subject: Permit No. WQ0010438
Charlotte -Mecklenburg Utility Department
CMUD Job No. 254-91-589
Six Mile Creek Basin
Sewer Extension
Mecklenburg County
In accordance with your application received November 9, 1995, we are forwarding herewith
Permit No. WQ0010438, dated December 11, 1995, to the Charlotte -Mecklenburg Utility Department for
the construction and operation of the subject wastewater collection extension.
This permit shall be effective from the -date of issuance until rescinded, shall hereby void Permit
No. WQ0010438 dated May 16, 1995, and shall be subject to the conditions and limitations as specified
therein.
Please be advised that the subject permit must be constructed in accordance with and comply with
the mitigation measures outlined in Section-6.0 of the Environmental Assessment/Finding of No
Significant Impact. - - -
•
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the
right to request an adjudicatory hearing upon written request within thirty (30) days following receiptof
this permit. This request must be in the forth of a written petition, conforming to Chapter 150B of the
North Carolina General Statutes, and filed with the Office of Administrative Hearings, P.O. Drawer
27447, Raleigh, NC 27611-7447. Unless such demands are made this permit shall be final and binding.
One set of approved plans and specifications is being forwarded to you. If you need additional
information concerning this matter, please contact Rick Moore at (919) 733-5083 ext. 527.
Sincerely, /
owa./ ...- ki.f 1 ct CUvi,aul - .
• A. Presto )Eioward, Jr., P.E. / ,
/ i
P.O. Box 29535, Raleigh, North Carolina 27626-0535 . Telephone 919-733-5083 FAX 919-733-9919
An Equal Opportunity Affirmative Action Employer 50% recycled/ 10% post -consumer paper
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT, HEALTH AND NATURAL RESOURCES
• RALEIGH
WASTEWATER COLLECTION PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as
amended, and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO THE
Charlotte -Mecklenburg Utility Department
Mecklenburg County
FOR THE
construction and operation of approximately 247 linear feet of 8 inch gravity sewer, 5,266 linear feet of 18
inch gravity sewer, 18,213 linear feet of 24 inch gravity, sewer, 8,941 linear feet of 30 inch gravity sewer,
11,000 linear feet of 36 inch gravity sewer, 3,930 linear feet of 78 inch gravity sewer, a 4,200 GPM
pump station with duplex pumps, high water alarms, standby generator with an automatic transfer switch
and approximately 15,072 linear feet of 30 inch force main, a 4600 GPM pump station with duplex
pumps, high water alarms, standby generator with an automatic transfer switch and approximately 423
linear feet of 30 inch force main to serve the Six Mile Creek Basin and the discharge of 0.GPD (flow to be
permitted under future permits) of collected domestic wastewater into the Charlotte -Mecklenburg Utility
Department's existing sewerage system, pursuant to the application received November 9, 1995, and in
conformity with the project plan, specifications, and other supporting data subsequently filed and
approved by the Department of Environment, Health and Natural Resources and considered a part of this
permit.
This permit shall be effective from the date of issuance until -rescinded, shall hereby void Permit
No. WQ0010438 dated May 16, 1995, and shall be subject to the following specified conditions and
-limitations: -
1. This permit shall become voidable unless the facilities are constructed in accordance with the
conditions of this permit, the approved plans and specifications, and other supporting data.
2. This permit is -effective only with respect to the nature and volume of wastes described in the
application and other supporting data.
3. The facilities must be properlymaintained and operated at all times.
4. The sewage and wastewater collected by this system shall be treated in the Charlotte -Mecklenburg
Utility Department's McAlpine Creek Wastewater Treatment Facility prior to being discharged into
the receiving stream. -
5. This permit is not transferable. in the event there is a desire for the facilities to change ownership,
or there is a name change of the Permittee, a formal permit request must be submitted to the
Division of Environmental Management accompanied by an application fee, documentation from
the parties involved, and other supporting materials as may be appropriate. The approval of this
request will be considered on its merits and may or may not be approved.
1
6. Construction of the sewers, pump station(s) and force main shall be scheduled so as
interrupt service by the existing utilities nor result in an overflow or bypass discharge o
wastewater to the surface waters of the State.
7. • Upon completion of construction and prior to operation of this permitted facility, a certification
must be received from a professional engineer certifying that the permitted facility has been
installed in accordance with this permit, the approved plans and specifications, and other
supporting materials. Mail the Certification to the Water Quality Permits and Engineering Unit,
P.O. Box 29535, Raleigh, NC 27626-0535.
8. A copy of the approved plans and specifications shall be maintained on file by the Permittee for a
minimum of five years from the date of the completion of construction.
9. Failure to abide by the conditions and limitations contained in this permit may subject the Permittee
to an enforcement action'by the Division of Environmental Management, in accordance with North
Carolina General Statute 143-215.6(a) to 143-215.6(c).
10. The issuance of this permit does not preclude the Permittee from complying with any and all
statutes, rules, regulations, or ordinances which may be imposed by other government agencies
(local, state, and federal) which have jurisdiction. -
11. In the event that the facilities fait to perform satisfactorily, including the creation of nuisance
conditions, the Permittee shall take immediate corrective action, including those as may be required
by. this Division, such as the construction of additional or replacement wastewater collection
facilities.
12. The Permittee shall provide for the pump station and force main the following items:
a. Pump on/off elevations located so that 2-8 pumping cycles may be achieved per hour in the
pump station, '•
b. An air relief valve located at all high points along the force main.
c. A screened vent for the wet well,
d. Fillets located in the wet well at the intersection of the flooring and sidewalls,
e. Three feet of cover (minimum) over the force main or the use of ferrous material where three
feet cannot be maintained,
f. Sufficient devices.which will protect the pump station from vandals, and
g. Flood protection if the pump stationf is located below the 100-year flood elevation.
13. Noncompliance Notification:
The Permittee shall report by telephone to the Mooresville Regional Office, telephone number
(704) 663-1699, as soon as possible, but in no case more than 24 hours or on the next working
day, following the occurrence or.firstknowledge of the occurrence of either of the following:
a. Any process unit failure, due to known or unknown reasons, that renders the facility incapable
of adequate wastewater transport, such as mechanical or electrical failures of pumps, line
blockage or breakage, etc.; or
b . Any failure of a pumping station or sewer line resulting in a by-pass directly to receiving ` ,
waters without treatment of all or any portion of the influent to such station or facility.
111.' Persons reporting such occurrences by telephone shall also file a written report in letter form within
111111111PIPP-15
days following first knowledge of the occurrence. This report must outline the actions taken or
proposed to be taken to ensure that the problem does not recur.
14. A minimum of 25 feet shall be maintained between the 30 inch force main and the private wells
located at Stations 77+50 and 88+90. The 30 inch force main shall be ductile iron piping or
encased by steel at least 25 feet to each side of the well.
Permit issued this the 1 lth day of December, 1995.
- - NORTH CAROLINA ENVIRONMENTAL MANAJDEMENT COMMISSION
A. Preston/ -3oward, Jr:, P.. , Director
Division o Environmental Management /
By Authority of the Environmental Management Commission
Permit Number WQ0010438
•
Permit No. WQ0010438
December 11, 1995
ENGINEER'S CERTIFICATION
1, , as a duly, registered Professional Engineer in the State of North
Carolina, having been authorized to observe (periodically, weekly, full time) the construction of the
project, for the
Project Nance Location
Permittee hereby state that, to the best of my abilities, due care and diligence was used in the observation
of the construction such that the construction was.observed to be built within substantial compliance and
intent of this permit, the approved plans and specifications, and other supporting materials.
Signature Registration No.
Date