Loading...
HomeMy WebLinkAboutNC0033111_Fairfield Harbor Inspection_20210809ROY COOPER Governor ELIZABETH S. RISER Secretory S. DANIEL SMITH Director *.:wn NORTH CAROLINA Environmental Quality August 09, 2021 Martin Lashua Carolina Water Service Inc of North Carolina PO Box 240908 Charlotte, NC 28224-0908 SUBJECT: Compliance Inspection Report Fairfield Harbour S/D WWTP NPDES WW Permit No. NC0033111 Craven County Dear Mr. Lashua: The North Carolina Division of Water Resources conducted an inspection of the Fairfield Harbour S/D WWTP on 7/26/2021. This inspection was conducted to verify that the facility is operating in compliance with the conditions and limitations specified in NPDES WW Permit No. NC0033111. The findings and comments noted during this inspection are provided in the enclosed copy of the inspection report entitled "Compliance Inspection Report". There were no significant issues or findings noted during the inspection and therefore, a response to this inspection report is not required. If you should have any questions, please do not hesitate to contact Paul Mays with the Water Quality Regional Operations Section in the Washington Regional Office at 252-948-3940 or via email at paul.mays@ncdenr.gov. ATTACHMENTS Cc: Laserfiche Sincerely, Pau(, Mails Paul Mays, Environmental Specialist I Water Quality Regional Operations Section Washington Regional Office Division of Water Resources, NCDEQ Lel ';;�' Re Req... United States Environmental Protection Agency E PA Washington, D.C. 20460 Water Compliance Inspection Report Form Approved. OMB No. 2040-0057 Approval expires 8-31-98 Section A: National Data System Coding (Le., PCS) Transaction Code NPDES yr/mo/day Inspection 1 IN I 2 Is 3 I N00033111 111 121 21/07/26 117 Type 181r-I IIIImii1 Inspector Fac Type 191 S I 201 21IIIIII IIIIIIIIIII IIIIIII 1 IiIIII 66 I�6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved 671761711I 72 I N I 731 I 174 i 75 I I I I I I 1 I I I80 Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include POTW name and NPDES oermit Number) Fairfield Harbour S/D WWTP 200 Broad Creek Rd New Bern NC 28560 Entry Time/Date 10:OOAM 21/07/26 Permit Effective Date 18/07/01 Exit Time/Date 11:30AM 21/07/26 Permit Expiration Date 23/06/30 Name(s) of Onsite Representative(s)/Ttles(s)/Phone and Fax Number(s) Matthew Golden/ORC/252-659-0517/ Other Facility Data Name, Address of Responsible Offcial/Titie/Phone and Fax Number Contacted Martin Lashua,PO Box 240908 Charlotte NC 282240908//704-319-0517/7045258174 No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenar Records/Reports Sludge Handling Dispo; Facility Site Review Effluent/Receiving Wate Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Victoria Herdt DWR/WARO WQ/252-948-3911/ Paul M Mays DWR/WARO WQ/252-948-3940/ Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# 1 NPDES yr/mo/day Inspection Type 3I NC0033111 I11 12I 21/07/26 17 18 I C (Cont.) 1 Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) On 07/26/2021 Paul Mays and Victoria Herdt with the Department of Environmental Quality: Division of Water Resources from the Washington Regional Office conducted a compliance evaluation of Fairfield Harbor WWTP. The facility operates under NPDES permit #NC0033111. The facility was found to be compliant with permit #NC0033111. The facility was inspected due to a complaint filed against the facility by residents nearby the facility. There was complaint was that there of an overwhelming odor issue and noise issue with the blowers. Upon inspection of the facility, there was no odor issue to be found and the blowers were no louder than ones found at the average facility. The facility has an emergency fuel agreement with Mallard. All required records were present for review, and all were maintained well over 5 years. The April 2021 DMR was spot checked vs corresponding lab data. Only a minor issue was found on the third week of the month where Total N was reported as 22.63mg/I vs the 22.56m1/I that was reported on the lab data. After a small review with ORC Mathew Golden, this was found due to a small rounding error. No other issues were found on the April 2021 DMR. The sludge blanket for clarifier 1 was 5ft and 4.5ft in clarifier 2 and this was measured via sludge judge. It is important to note both clarifiers have a sidewall depth of 14ft. Another issue noted with the clarifiers where the skimmer arms in one of the units did not touch the water and was in need repair. The skimmer arm for the clarifier was fixed the next week and a video of the fix was sent on 08/04/2021 via email. During the inspection the Eluent flowmeter was found to be last calibrated over 3 years ago on 01/01/2018. It was discussed with the ORC that the effluent flowmeter had to be calibrated annually. ORC Golden Mathew followed up 2 days later and showed that he had the effluent flowmeter calibrated on 07/28/2021. Page# 2 Permit: NC0033111 Inspection Date: 07/26/2021 Owner -Facility: Fairfield Harbour S/D VVVVTP Inspection Type: Compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ 0 • 0 application? Is the facility as described in the permit? ■ ❑ ❑ ❑ # Are there any special conditions for the permit? • ❑ ❑ ❑ Is access to the plant site restricted to the general public? ■ ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑ Comment: Permit expries 06/30/2021 Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? •❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable • 0 0 0 Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? ■ ❑ ❑ ❑ Is all required information readily available, complete and current? •❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? ■ ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? ■ ❑ ❑ ❑ Is the chain -of -custody complete? ■ ❑ ❑ ❑ Dates, times and location of sampling ■ Name of individual performing the sampling ■ Results of analysis and calibration ■ Dates of analysis ■ Name of person performing analyses ■ Transported COCs ■ Are DMRs complete: do they include all permit parameters? •❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ■ ❑ ❑ ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified 0 0 • ❑ operator on each shift? Is the ORC visitation log available and current? ■ ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? ■ ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility •❑ ❑ ❑ classification? Page# 3 Permit: NC0033111 Owner - Facility: Fairfield Harbour S/D WWTP Inspection Date: 07/26/2021 Inspection Type: Compliance Evaluation Record Keeping Is a copy of the current NPDES permit available on site? Facility has copy of previous year's Annual Report on file for review? Yes No NA NE 11000 ❑ ❑ ❑ • Comment: All required records were present for review and all were maintained well over 5 years. The April 2021 DMR was spot checked vs corresponding lab data. Only a minor issue was found on the third week of the month where Total N was reported as 22.63mg/I vs the 22.56m1/I that was reported on the lab data. After a small review with ORC Mathew Golden, this was found due to a small rounding error. No other issues were found on the April 2021 DMR. Standby Power Is automatically activated standby power available? Is the generator tested by interrupting primary power source? Is the generator tested under load? Was generator tested & operational during the inspection? Do the generator(s) have adequate capacity to operate the entire wastewater site? Is there an emergency agreement with a fuel vendor for extended run on back-up power? Is the generator fuel level monitored? Comment: The facility has an emergency fuel agreement with Mallard. Yes No NA NE ▪ ❑ ❑ ❑ ▪ ❑ ❑ ❑ • ❑ ❑ ❑ ▪ ❑ ❑ ❑ ▪ ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Bar Screens Yes No NA NE Type of bar screen a.Manual ❑ b.Mechanical Are the bars adequately screening debris? •❑ ❑ ❑ Is the screen free of excessive debris? •❑ ❑ ❑ Is disposal of screening in compliance? • 0 0 0 Is the unit in good condition? •❑ ❑ ❑ Comment: The unit is a Static Barscreen and the unit looked to be in good condition. Screenings from the unit are rem pressed into dumpster and disposed of twice a week to a lined landfill. Aeration Basins Yes No NA NE Mode of operation Ext. Air Type of aeration system Diffused Is the basin free of dead spots? 111000 Page# 4 Permit: NC0033111 Inspection Date: 07/26/2021 Owner - Facility: Fairfield Harbour S/D wwTP Inspection Type: Compliance Evaluation Aeration Basins Are surface aerators and mixers operational? Are the diffusers operational? Is the foam the proper color for the treatment process? Does the foam cover less than 25% of the basin's surface? Is the DO level acceptable? Is the DO level acceptable?(1.0 to 3.0 mg/I) Comment: Secondary Clarifier Is the clarifier free of black and odorous wastewater? Is the site free of excessive buildup of solids in center well of circular clarifier? Are weirs level? Is the site free of weir blockage? Is the site free of evidence of short-circuiting? Is scum removal adequate? Is the site free of excessive floating sludge? Is the drive unit operational? Is the return rate acceptable (low turbulence)? Is the overflow clear of excessive solids/pin floc? Is the sludge blanket level acceptable? (Approximately' of the sidewall depth) Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ ❑• ❑ ❑ ❑ • Yes No NA NE MODE • ❑ ❑ ❑ MOOD • ❑ ❑ ❑ MODE ❑•❑ ❑ MUDD • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ DIIIDD Comment: The sludge blanket for clarifier 1 was 5ft and 4.5ft in clarifier 2 and this was measured via sludge judge. It is important to note both clarifiers have a sidewall depth of 14ft. Another issue noted with the clarifiers where the skimmer arms in one of the units did not touch the water and was in need repair. The skimmer arm for the clarifier was fixed the next week and a video of the fix was sent on 08/04/2021 via email. Aerobic Digester Is the capacity adequate? Is the mixing adequate? Is the site free of excessive foaming in the tank? # Is the odor acceptable? # Is tankage available for properly waste sludge? Comment: Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ MOOD MODE MOOD Page# 5 Permit: NC0033111 Owner - Facility: Fairfield Harbour S/D wWTP Inspection Date: 07/26/2021 Inspection Type: Compliance Evaluation Filtration (High Rate Tertiary) Type of operation: Is the filter media present? Is the filter surface free of clogging? Is the filter free of growth? Is the air scour operational? Is the scouring acceptable? Is the clear well free of excessive solids and filter media? Yes No NA NE • ❑ ❑ ❑ MOOD • ❑ ❑ ❑ ❑ ❑•❑ DOME Comment: FFP Cloth Filter - no issues were found and unit appears to be in good condition, Disinfection - UV Are extra UV bulbs available on site? Are UV bulbs clean? Is UV intensity adequate? Is transmittance at or above designed level? Is there a backup system on site? Is effluent clear and free of solids? Comment: Disinfection -Liquid Is there adequate reserve supply of disinfectant? (Sodium Hypochlorite) Is pump feed system operational? Is bulk storage tank containment area adequate? (free of leaks/open drains) Is the level of chlorine residual acceptable? Is the contact chamber free of growth, or sludge buildup? Is there chlorine residual prior to de -chlorination? Yes No NA NE ❑ ❑ ❑ • MOOD • ❑ ❑ ❑ • ❑ ❑ ❑ U LIDLJ 11000 Yes No NA NE � ❑ ❑ ❑ ■ ❑ ❑ ❑ MOOD O 0110 • ❑ ❑ ❑ ❑ ❑•❑ Comment: The chlorine disinfection unit is a backup system for the UV disinfection system. De -chlorination Yes No NA NE Type of system ? Liquid Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ 0 ❑ • Is storage appropriate for cylinders? 0 0 0 • # Is de -chlorination substance stored away from chlorine containers? ❑ ❑ ❑ ■ Are the tablets the proper size and type? DODO Page# 6 Permit: NC0033111 Inspection Date: 07/26/2021 Owner - Facility: Fairfield Harbour S/D WWTP Inspection Type: Compliance Evaluation De -chlorination Yes No NA NE Comment: Sodium Bisulfate is used to dechlorinate in the event the backup chlorine disinfection unit had to be used. Are tablet de -chlorinators operational? ❑ ❑ ❑ ❑ Number of tubes in use? Comment: Flow Measurement - Effluent # Is flow meter used for reporting? Is flow meter calibrated annually? Is the flow meter operational? (If units are separated) Does the chart recorder match the flow meter? Yes No NA NE • ❑ ❑ ❑ ❑ 1E❑ ❑ • ❑ ❑ ❑ ▪ ❑ ❑ ❑ Comment: During the inspection the Eluent flowmeter was found to be last calibrated over 3 years ago on 01/01/2018. It was discussed with the ORC that the effluent flowmeter had to be calibrated annually. ORC Golden Mathew followed up 2 days later and showed that he had the effluent flowmeter calibrated on 07/28/2021. Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? •❑ ❑ ❑ Are all other parameters(excluding field parameters) performed by a certified lab? ■ ❑ ❑ ❑ # Is the facility using a contract lab? •❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 ■ ❑ ❑ ❑ degrees Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ ❑ Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ • ❑ Comment: Effluent Pipe Is right of way to the outfall properly maintained? Are the receiving water free of foam other than trace amounts and other debris? If effluent (diffuser pipes are required) are they operating properly? Comment: Yes No NA NE • ❑ ❑ ❑ ❑ ❑ ❑ • ❑ ❑•❑ Page# 7