HomeMy WebLinkAboutWQ0011260_CEIARR_20210802
SENT VIA ELECTRONIC MAIL ONLY: NO HARD COPY WILL BE MAILED
August 02, 2021
Rick Hensley, Mayor
Email: mayor@oldfortnc.com
Town of Old Fort
SUBJECT: Compliance Inspection Report-Annual Report Review
Town of Old Fort DCAR
Non-discharge Permit No. WQ0011260
McDowell County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Town of Old Fort DCAR
on 8/02/2021. This inspection was conducted to verify that the facility is operating in compliance with
the conditions and limitations specified in Non-discharge Permit No. WQ0011260. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact me at 828-296-4686 or via email at
mikal.willmer@ncdenr.gov.
Sincerely,
Mikal Willmer, Environmental Specialist II
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
Ec: LF
Compliance Inspection Report
Permit:WQ0011260 Effective:02/01/20 Expiration:01/31/25 Owner :Town of Old Fort
SOC:
Contact Person:
Region:
County:
Directions to Facility:
McDowell
Asheville
Asley Wooten
Effective:Expiration:Facility:Town of Old Fort DCAR
1174 E Main St
Old Fort NC 28762
Title:Phone:828-652-7121
From ARO: Take I-40 East to Exit 72 (Old Fort/Hwy. 70 E.) Continue on Hwy. 70 E. to Collins & Aikman. Turn right at Collins &
Aikman and follow paved road around behind C&A until you come to WWTP.
Secondary ORC(s):
Phone:Certification:Primary ORC:
System Classifications:
On-Site Representative(s):
Related Permits:
NC0021229 Town of Old Fort - Old Fort WWTP
Secondary Inspector(s):
Primary Inspector:
Inspection Date:Exit Time:Entry Time:
Phone:
08/02/2021 09:30AM 10:20AM
Mikal Willmer 828-296-4686
Facility Status:
Permit Inspection Type:
Reason for Inspection:Inspection Type:
Not CompliantCompliant
Routine
Distribution of Residual Solids (503)
Annual Report Review
Question Areas:
Miscellaneous Questions Record Keeping Treatment
Pathogen and Vector Attraction
(See attachment summary)
Page 1 of 4
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0011260
08/02/2021 Annual Report Review
Town of Old Fort
Routine
Inspection Summary:
Mikal Willmer, with the Asheville Regional Office, conducted a review of the Town of Old Fort's 2020 Annual Residuals Report
for Permit No. WQ0011260.
The report appeared to be in compliance with all permit requirements.
Facility meets Pathogen reduction through PFRP Pasteurization and vector attraction reduction through alkaline
stabilization. All temperature and pH logs were included.
Phosphorus was reanalyzed in January 2020 due to an abnormally high result in December of 2019. This parameter is
monitor only. The ARO advised the ORC to use the result obtained closest to distribution to determine the most limiting
nutrient parameters.
The Town of Old Fort distributed 48.64 dry tons of residuals in April of 2020 from the pile produced in 2019. The 2019 pile
was sampled for metals and nutrients in 2019. The facility collects fecal coliform samples before distribution for the year.
The field inspection and hauling sheets were also included with the annual report. 27.1 dry tons of stabilized residuals were
generated in 2020 but have not been distributed.
Non-hazardous waste characterization: The stabilized biosolids produced in 2020 were tested for TCLP, ignitibility,
corrosivity, reactivity, metals, and nutrients in December 2020. This analysis will satisfy the once per permit cycle
non-hazardous waste characterization as listed under Attachment A. All results appeared to be within regulatory limits.
Page 2 of 4
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0011260
08/02/2021 Annual Report Review
Town of Old Fort
Routine
Type Yes No NA NE
Land Application
Distribution and Marketing
Record Keeping Yes No NA NE
Is GW monitoring being conducted, if required?
Are GW samples from all MWs sampled for all required parameters?
Are there any GW quality violations?
Is GW-59A certification form completed for facility?
Is a copy of current permit on-site?
Are current metals and nutrient analysis available?
Are nutrient and metal loading calculating most limiting parameters?
a. TCLP analysis?
b. SSFA (Standard Soil Fertility Analysis)?
Are PAN balances being maintained?
Are PAN balances within permit limits?
Has land application equipment been calibrated?
Are there pH records for alkaline stabilization?
Are there pH records for the land application site?
Are nutrient/crop removal practices in place?
Do lab sheets support data reported on Residual Analysis Summary?
Are hauling records available?
Are hauling records maintained and up-to-date?
# Has permittee been free of public complaints in last 12 months?
Has application occurred during Seasonal Restriction window?
See summary for details.Comment:
Pathogen and Vector Attraction Yes No NA NE
a. Fecal coliform SM 9221 E (Class A or B)
Class A, all test must be <1000 MPN/dry gram
Geometric mean of 7 samples per monitoring period for class B<2.0*10E6 CFU/dry gram
Fecal coliform SM 9222 D (Class B only)
Geometric mean of 7 samples per monitoring period for class B<2.0*10E6 CFU/dry gram
b. pH records for alkaline stabilization (Class A)
c. pH records for alkaline stabilization (Class B)
Temperature corrected
d. Salmonella (Class A, all test must be < 3MPN/4 gram day)
Page 3 of 4
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0011260
08/02/2021 Annual Report Review
Town of Old Fort
Routine
e. Time/Temp on:
Digester (MCRT)
Compost
Class A lime stabilization
f. Volatile Solids Calculations
g. Bench-top Aerobic/Anaerobic digestion results
Comment:
Treatment Yes No NA NE
Check all that apply
Aerobic Digestion
Anaerobic Digestion
Alkaline Pasteurization (Class A)
Alkaline Stabilization (Class B)
Compost
Drying Beds
Other
Comment:
Page 4 of 4