May 6, 2016
Thomas J Roberts
Aqua North Carolina Inc
202 Mackenan Ct
Cary, NC 27511
SUBJECT: 5/5/2016 Compliance Evaluation Inspection
Aqua North Carolina Inc
Woodlake Country Club WWTP
Permit No: NC0061719
Moore County
PAT MCCRORY
Governor
DONALD R. VAN DER VAART
Scenario:
S. JAY ZIMMERMAN
Director
Dear Mr Roberts:
Enclosed please find a copy of the Compliance Evaluation Inspection form from the inspection
conducted on 5/5/2016. The Compliance Evaluation Inspection was conducted by Chad Turlington of
the Fayetteville Regional Office. The facility was found to be in Compliance with permit NC0061719. As
a reminder, preservation of the Waters of the State can only be achieved through consistent NPDES
Permit compliance.
Please refer to the enclosed inspection report for additional observations and comments. If you or your
staff have any questions, please call me at 910-433-3320.
cc: Ronnie E. Dickens, ORC
Central Files
Fayetteville Files
Sincerely,
Chad Turlington
Environmental Specialist
Division of Water Resources
Water Quality Regional Operations Section
State of North Carolina I Environmental Quality I Water Resources
225 Green Street -Suite 7141 Fayetteville, North Carolina 28301-5043
910- 433- 3300
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day :: • Inspection
1 N 2 5 3 NC0061719 11 12 16/05/05 17'
LJ IJ ` I
Type
1E3 C
. L
I I I t I
Inspector •FacType•
19 s 20
1 U ll
211
I I I 1 I I I 1 I I I 1 I I I 1 1 .1 I I .I I I 11..1 1 I
11.1
J 1 I I I r6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 - QA ---- Reserved------
67 I I 7o I I 71 L___I 72 I NI73 I I 74 75I
I I I 1
1
11 I 1 1 1 1l80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Woodlake Country Club WWTP
Merganser Way
Vass NC 28394
Entry Time/Date
10:30AM 16/05/05
Permit Effective Date
11/08/01
Exit Time/Date
12:30PM 16/05/05
Permit Expiration Date
16/05/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Ronnie E. Dickens/ORC/910-263-0567/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Thomas J Roberts,202 Mackenan Ct Cary NC
27511/President/919-467-8712/9194601788 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated),
Permit • Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Facility Site Review • Effluent/Receiving Waters Laboratory
-
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as. necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Chad Turlington � FRO WQ//910-433-3300 ExL720/
Signature of Management Q�Reviewer Agency/Office/Phone and Fax Numbers Date
�,
Belinda S Hen n ./ZAQ//910-433-3300 Ext.72E cv 6A0
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
NPDES
NC0061719
111 121
yr/mo/day
16/05/05
17
Inspection Type
181cj
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Plant appeared to be well maintained. Operator was able to provide all records as requested.
Records were well organized. DMR's for the months of December 2015, January and February 2016
were compared to bench sheets and no reporting errors were noted. Solids settle in chlorine contact
chamber and are removed by operator before the level reaches 12 inches. Operator should be vigilant
in observing sludge in contact chamber to insure that permit violations do not occur.
Page# 2
Permit; NC0061719
Inspection Date: 05/05/2016
Owner - Facility: Woodlake Country Club WWTP
Inspection Type: Compliance Evaluation
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment:
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis. and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility, submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility classification?
Is a copy of the current NPDES permit available on site?
Yes No NA NE
II ❑ ❑ ❑
❑ ❑ ❑
Yes No NA NE
1 ❑ , ❑ ❑
11 0 ❑ ❑
❑ MI ❑ ❑
11 ❑ ❑ ❑
11 ❑ ❑ ❑
Yes No NA NE
❑ ❑ 0
• ❑ ❑ ❑
▪ ❑ ❑ ❑
11000
11000
•
11 ❑ 0 0
❑ ❑❑ 1111
❑ ❑ • ❑
▪ ❑ ❑ ❑
II ❑ ❑ ❑
• ❑ ❑ ❑
• ❑... ❑ ❑
Page# 3
Permit: NC0061719 Owner - Facility: Woodlake Country Club wWTP
Inspection Date: 05/05/2016
Inspection Type: Compliance Evaluation
Record Keeping
Facility has copy of previous year's Annual Report on file for review?
Comment:
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment:
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Aeration Basins
Mode of operation
Type of aeration system
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/I) .
Comment:
Disinfection -Liquid
Is there adequate reserve supply of disinfectant?
Yes No NA NE
Yes No NA NE
❑ ❑ ❑
II ❑ ❑ ❑
❑ ❑ ❑ ❑
II ❑ ❑ ❑
Yes No NA NE
▪ ❑ ❑ ❑
® ❑ ❑ ❑
❑ ELM❑
Yes No NA NE
Ext. Air
Diffused
❑ ❑ ❑
❑ ❑ IN ❑
III ❑ ❑ ❑
II ❑ ❑ ❑
NI ❑ ❑ ❑
❑ ❑ ❑ II
❑ ❑ ❑ •
Yes No NA NE
® ❑ ❑ ❑
Page# 4
Permit: NC0061719 Owner - Facility: Woodlake Country Club VVWTP
Inspection Date: 05/05/2016 Inspection Type: Compliance Evaluation.
Disinfection -Liquid
(Sodium Hypochlorite) Is pump feed system operational?
Is bulk storage tank containment area adequate? (free of leaks/open drains)
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Yes. No NA NE
11 ❑ ❑ ❑
® ❑ ❑ ❑
11 ❑ ❑ ❑
• ❑ ❑ ❑
Comment: Contact chamber does collect solids. Operator monitors sludge level daily and pumps out
before the level reaches 12 inches.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at Tess than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment:
De -chlorination
Type of system ?
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment:
Yes No NA NE
▪ ❑ ❑ ❑
• ❑ ❑ ❑
▪ ❑ ❑ ❑
❑ ❑ ❑ MI
Yes No NA NE
Liquid
❑ ❑ ❑
11 ❑ ❑ ❑
11 ❑ ❑ ❑
❑ ❑ ❑ ❑
❑ ❑ ❑ ❑
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting? • ❑ ❑ ❑
Is flow meter calibrated annually? • ❑ ❑ 0
Is the flow meter operational? 1100E1
Page# 5
Permit: NC0061719 Owner - Facility: Woodlake Country Club WWfP
Inspection Date: 05/05/2016 Inspection Type: Compliance Evaluation
Flow Measurement - Effluent
(If units are separated) Does the chart recorder match the flow meter?
Comment:
Yes No NA NE
DOOM
Page# 6