Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Leith Creek WWTP
Hall St Extension
Laurinburg NC 28352
Entry Time/Date
11:OOAM 21/06/22
Permit Effective Date
21/02/01
Exit Time/Date
02:OOPM 21/06/22
Permit Expiration Date
25/08/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Dixon Lee Medlin/ORC/910-755-7921/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Robert A. Ellis,PO Box 249 Laurinburg NC 283530249//910-276-9374/9102773633
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s)
Hughie White
of Inspector(s) Agency/Office/Phone and Fax Numbers Date
�poousigneaby: DWR/FRO WQ/910-433-3300 Ext.708/ 7/9/2021
Nsa.,Lii*'W r.
"-49E06C80007E432...
Signature of Managgmegl$@gjewer
Mark Brantley
Agency/Office/Phone and Fax Numbers Date
W& bl'/FRO WQ/910-433-3300 Ext.727/ 7/15/2021
���1-1 Anne, ao1.19
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
31
NPDES yr/mo/day
NC0020656 111 121 21/06/22
I17
Inspection Type
18i i
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Records and log books appeared to be well organized and maintained. A copy of the current NPDES
permit is being kept on site. The ORC visitation log appeared to be complete and current.
Calibration records appeared to be properly documented. Laboratory data was reviewed and all data
that was reviewed appeared to be correct, as reported on the DMR's. The facility appeared to be
operated and maintained properly, however, it was noted that there were some visible solids being
discharged at the time of this inspection.
Page# 2
Permit: NC0020656
Inspection Date: 06/22/2021
Owner - Facility: Leith Creek WWTP
Inspection Type: Compliance Sampling
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable II El El El
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new El El ❑
application?
Is the facility as described in the permit? • El El El
# Are there any special conditions for the permit? El El • El
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment:
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? • ❑ ❑ ❑
Is all required information readily available, complete and current? • ❑ ❑ ❑
Are all records maintained for 3 years (lab. reg. required 5 years)? • El ❑ ❑
Are analytical results consistent with data reported on DMRs? • ❑ ❑ ❑
Is the chain -of -custody complete? • ❑ ❑ ❑
Dates, times and location of sampling •
Name of individual performing the sampling •
Results of analysis and calibration •
Dates of analysis •
Name of person performing analyses •
Transported COCs ■
Are DMRs complete: do they include all permit parameters? • ❑ ❑ ❑
Has the facility submitted its annual compliance report to users and DWQ? ❑ • ❑ ❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified ❑ ❑ • ❑
operator on each shift?
Is the ORC visitation log available and current? • ❑ ❑ ❑
Is the ORC certified at grade equal to or higher than the facility classification? • ❑ ❑ ❑
Is the backup operator certified at one grade less or greater than the facility • ❑ ❑ ❑
classification?
Page# 3
Permit: NC0020656
Inspection Date: 06/22/2021
Owner - Facility: Leith Creek WWTP
Inspection Type: Compliance Sampling
Record Keeping
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Comment: The required annual report is not being completed.
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment:
Yes No NA NE
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
❑ ❑ • ❑
Bar Screens Yes No NA NE
Type of bar screen
a.Manual ■
b.Mechanical •
Are the bars adequately screening debris? ❑ ❑ ❑ •
Is the screen free of excessive debris? ❑ ❑ ❑ •
Is disposal of screening in compliance? ❑ ❑ ❑ •
Is the unit in good condition? ❑ ❑ ❑ •
Comment: At the time of this inspection, the mechanical bar screen had been removed for repairs.
Grit Removal
Type of grit removal
a.Manual
b.Mechanical
Is the grit free of excessive organic matter?
Is the grit free of excessive odor?
# Is disposal of grit in compliance?
Comment:
Pump Station - Influent
Is the pump wet well free of bypass lines or structures?
Is the wet well free of excessive grease?
Yes No NA NE
•
Yes No NA NE
Page# 4
Permit: NC0020656
Inspection Date: 06/22/2021
Owner - Facility: Leith Creek WWTP
Inspection Type: Compliance Sampling
Pump Station - Influent Yes No NA NE
Are all pumps present? • ❑ ❑ ❑
Are all pumps operable? • ❑ ❑ ❑
Are float controls operable? • ❑ ❑ ❑
Is SCADA telemetry available and operational? • ❑ ❑ ❑
Is audible and visual alarm available and operational? ❑ ❑ ❑ •
Comment:
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Surface
Is the basin free of dead spots? • ❑ ❑ ❑
Are surface aerators and mixers operational? • ❑ ❑ ❑
Are the diffusers operational? ❑ ❑ • ❑
Is the foam the proper color for the treatment process? • ❑ ❑ ❑
Does the foam cover less than 25% of the basin's surface? • ❑ ❑ ❑
Is the DO level acceptable? • ❑ ❑ ❑
Is the DO level acceptable?(1.0 to 3.0 mg/I) • ❑ ❑ ❑
Comment:
Oxidation Ditches Yes No NA NE
Are the aerators operational? • ❑ ❑ ❑
Are the aerators free of excessive solids build up? • ❑ ❑ ❑
# Is the foam the proper color for the treatment process? ■ ❑ ❑ ❑
Does the foam cover less than 25% of the basin's surface? • ❑ ❑ ❑
Is the DO level acceptable? • ❑ ❑ ❑
Are settleometer results acceptable (> 30 minutes)? ❑ ❑ ❑ •
Is the DO level acceptable?(1.0 to 3.0 mg/I) ■ ❑ ❑ ❑
Are settelometer results acceptable?(400 to 800 ml/I in 30 minutes) El El El •
Comment:
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Yes No NA NE
• ❑ ❑ ❑
Page# 5
Permit: NC0020656
Inspection Date: 06/22/2021
Owner - Facility: Leith Creek WWTP
Inspection Type: Compliance Sampling
Secondary Clarifier Yes No NA NE
Are weirs level? • ❑ ❑ ❑
Is the site free of weir blockage? • ❑ ❑ ❑
Is the site free of evidence of short-circuiting? ■ ❑ ❑ ❑
Is scum removal adequate? • ❑ ❑ ❑
Is the site free of excessive floating sludge? • ❑ ❑ ❑
Is the drive unit operational? • ❑ ❑ ❑
Is the return rate acceptable (low turbulence)? • ❑ ❑ ❑
Is the overflow clear of excessive solids/pin floc? • ❑ ❑ ❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) • ❑ ❑ ❑
Comment:
Disinfection -Liquid Yes No NA NE
Is there adequate reserve supply of disinfectant? • ❑ ❑ ❑
(Sodium Hypochlorite) Is pump feed system operational? • ❑ ❑ ❑
Is bulk storage tank containment area adequate? (free of leaks/open drains) • ❑ El El
Is the level of chlorine residual acceptable? • ❑ ❑ ❑
Is the contact chamber free of growth, or sludge buildup? • ❑ ❑ ❑
Is there chlorine residual prior to de -chlorination? • ❑ ❑ ❑
Comment:
De -chlorination Yes No NA NE
Type of system ? Gas
Is the feed ratio proportional to chlorine amount (1 to 1)? • ❑ El El
Is storage appropriate for cylinders? • ❑ El El
# Is de -chlorination substance stored away from chlorine containers? • El El El
Comment:
Are the tablets the proper size and type? El El • El
Are tablet de -chlorinators operational? El El • El
Number of tubes in use?
Comment:
Influent Sampling
# Is composite sampling flow proportional?
Yes No NA NE
Page# 6
Permit: NC0020656
Inspection Date: 06/22/2021
Owner - Facility: Leith Creek WWTP
Inspection Type: Compliance Sampling
Influent Sampling
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is sampling performed according to the permit?
Comment: The influent sampler collects samples at timed intervals.
Yes No NA NE
II El El El
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? • ❑ ❑ ❑
Is sample collected below all treatment units? • ❑ ❑ ❑
Is proper volume collected? • El ❑ ❑
Is the tubing clean? • El El El
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 • ❑ ❑ ❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type • El El El
representative)?
Comment:
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, El El El
and sampling location)?
Comment:
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 7
Permit: NC0020656
Inspection Date: 06/22/2021
Owner - Facility: Leith Creek WWTP
Inspection Type: Compliance Sampling
Equalization Basins
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
Comment: The EQ basin was empty and not in service at the time of this inspection.
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 8