Loading...
HomeMy WebLinkAboutNC0065587_Compliance Evaluation Inspection_20210721R.OY COOPER. Governor ELIZABETH S. BISER Secretary S. DANIEL SMITH NORTH CAROLINA Director Environmental Quality July 20, 2021 Thomas Roberts Aqua North Carolina 202 Mackenan Drive Cary, NC 27511 SUBJECT: Compliance Evaluation Inspection Frye Bridge WWTP NPDES Permit No. NC0065587 Forsyth County Dear Mr. Roberts, On June 15, 2021, Gary Hudson of this office met with Samuel Pegram, Operator in Responsible Charge (ORC), to perform a Compliance Evaluation Inspection at the above referenced wastewater treatment plant. This type of inspection consists of two basic parts: an in -office file review and an on -site inspection of the treatment facility. The attached EPA inspection form details the areas that were evaluated during this inspection. The inspection of the facility was satisfactory. If you have any questions regarding the inspection or this report, please contact Gary Hudson or me at (336) 776-9800 or by email at gary.hudson@ncdenr.gov or lon.snider@ncdenr.gov. Sincerely, DocuSigned by: 145B49E225C94EA.. Lon Snider Regional Supervisor Water Quality Regional Operations Division of Water Resources Attachments: EPA Water Compliance Inspection Report cc: WSRO NORTH D E Department of Envimnmomni au.i` North Carolina Department of Environmental Quality Division of Water Resources Winston-Salem Regional Office 450 West Hanes Mill Road, Suite 300 I Winston-Salem, North Carolina 27105 336.776.9800 United States Environmental Protection Agency E PA Washington, D.C. 20460 Water Compliance Inspection Report Form Approved. OMB No. 2040-0057 Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction 1 IN I 21IIIIII Code NPDES yr/mo/day Inspection 2 IL I 3 I NC0065587 111 121 21/06/15 117 Type 1810I IIIIIIIIIII Inspector Fac Type 19I S I 2011 IIIIIIIIIII IIIIIII I IIIIII P6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved 671 I 70I I 711 172 I N I 73I 1 74 71 I I I I I I I I 180 Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include POTW name and NPDES Dermit Number) Frye Bridge WWTP NCSR 2998 Clemmons NC 27012 Entry Time/Date 09:30AM 21/06/15 Permit Effective Date 19/07/01 Exit Time/Date 10:OOAM 21/06/15 Permit Expiration Date 24/05/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) /// Samuel E. Pegram/ORC/704-489-9404/ Other Facility Data Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Tim Wadde11,202 Mackenan Cir Cary NC 27511//919-467-8712/ No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenar Records/Reports Self -Monitoring Progran Facility Site Review Effluent/Receiving Wate Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Gary Hudson DWR/Division of Water Quality/336-776-9694/ Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date FDocuSigned by: L—o, T. SA,ac>_ 7/21/2021 145B49E225C94EA... EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# 1 3I NPDES yr/mo/day NC0065587 111 121 21/06/15 117 Inspection Type 18 [j 1 Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) *The Grade 2 package wastewater treatment plant appeared to be well operated and maintained. Settleable solids, D.O., and pH are performed for process control. *The permit became effective on July 1, 2019, and will expire on May 31, 2024. *AII records were available and well maintained. *Screened materials are dried and disposed of in a dumpster. *The effluent was very clear on the day of the inspection. The effluent is discharged into Blanket Creek in the Yadkin -Pee Dee River Basin. Page# 2 Permit: NC0065587 Inspection Date: 06/15/2021 Owner - Facility: Frye Bridge WWTP Inspection Type: Compliance Evaluation Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? ❑ ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable El El El El Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: The Grade 2 package wastewater treatment plant appeared to be well operated and maintained. Settleable solids, D.O., and pH are performed for process control. Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new MODE application? Is the facility as described in the permit? • El El El # Are there any special conditions for the permit? El • El El Is access to the plant site restricted to the general public? • ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? ■ El El El Comment: The permit became effective on July 1, 2019 will expire on May 31, 2024. Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? • El El El Is all required information readily available, complete and current? • El El El Are all records maintained for 3 years (lab. reg. required 5 years)? • El El El Are analytical results consistent with data reported on DMRs? • ❑ El El Is the chain -of -custody complete? • El El El Dates, times and location of sampling ■ Name of individual performing the sampling • Results of analysis and calibration • Dates of analysis • Name of person performing analyses ■ Transported COCs • Are DMRs complete: do they include all permit parameters? • ❑ El El Has the facility submitted its annual compliance report to users and DWQ? El El • El (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified El ❑ • El operator on each shift? Is the ORC visitation log available and current? • El El El Is the ORC certified at grade equal to or higher than the facility classification? • El El El Is the backup operator certified at one grade less or greater than the facility ■ El El El classification? Page# 3 Permit: NC0065587 Inspection Date: 06/15/2021 Owner - Facility: Frye Bridge WWTP Inspection Type: Compliance Evaluation Record Keeping Yes No NA NE Is a copy of the current NPDES permit available on site? Facility has copy of previous year's Annual Report on file for review? Comment: All records were available and well maintained. Bar Screens Yes No NA NE Type of bar screen a.Manual • b.Mechanical ❑ Are the bars adequately screening debris? • ❑ ❑ ❑ Is the screen free of excessive debris? ■ ❑ ❑ ❑ Is disposal of screening in compliance? ■ ❑ ❑ ❑ Is the unit in good condition? • ❑ ❑ ❑ Comment: Screened materials are dried and disposed of in a dumpster. Aeration Basins Yes No NA NE Mode of operation Ext. Air Type of aeration system Diffused Is the basin free of dead spots? ■ ❑ ❑ ❑ Are surface aerators and mixers operational? ❑ ❑ • ❑ Are the diffusers operational? • ❑ ❑ ❑ Is the foam the proper color for the treatment process? • ❑ ❑ ❑ Does the foam cover less than 25% of the basin's surface? • ❑ ❑ ❑ Is the DO level acceptable? ❑ ❑ ❑ • Is the DO level acceptable?(1.0 to 3.0 mg/I) ❑ ❑ ❑ • Comment: Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? • ❑ ❑ ❑ Is the site free of excessive buildup of solids in center well of circular clarifier? ❑ ❑ • ❑ Are weirs level? • ❑ ❑ ❑ Is the site free of weir blockage? • ❑ ❑ ❑ Is the site free of evidence of short-circuiting? • ❑ ❑ ❑ Is scum removal adequate? • ❑ ❑ ❑ Page# 4 Permit: NC0065587 Inspection Date: 06/15/2021 Owner - Facility: Frye Bridge WWTP Inspection Type: Compliance Evaluation Secondary Clarifier Yes No NA NE Is the site free of excessive floating sludge? Is the drive unit operational? Is the return rate acceptable (low turbulence)? Is the overflow clear of excessive solids/pin floc? Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) Comment: Disinfection -Tablet Are tablet chlorinators operational? Are the tablets the proper size and type? Number of tubes in use? Is the level of chlorine residual acceptable? Is the contact chamber free of growth, or sludge buildup? Is there chlorine residual prior to de -chlorination? Comment: • ❑ ❑ ❑ • ❑ ❑ ❑ Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ De -chlorination Yes No NA NE Type of system ? Tablet Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ • El Is storage appropriate for cylinders? El El • El # Is de -chlorination substance stored away from chlorine containers? • El ❑ ❑ Comment: Are the tablets the proper size and type? • El El El Are tablet de -chlorinators operational? • ❑ El El Number of tubes in use? Comment: The effluent was very clear on the day of the inspection. The effluent is discharged into Muddy Creek in the Yadkin -Pee Dee River Basin. Page# 5