HomeMy WebLinkAboutNCG500354_Compliance Evaluation Inspection_20210708DocuSign Envelope ID: 9BADD4E0-5AD8-41C7-88C0-F42162B50EFB
51EATEo,
4
ROY COOPER
Governor
JOHN NICHOLSON
Interim Secretary
S. DANIEL SMITH NORTH CAROLINA
Director Environmental Quality
July 08, 2021
David Callahan
Slurry Pavers Inc
107 Arendell St
Morehead City, NC 28557
SUBJECT: Compliance Inspection Report
Slurry Pavers - Morehead City
NPDES WW Permit No. NCG500354
Carteret County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Slurry Pavers -
Morehead City on 7/07/2021. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in NPDES WW Permit No. NCG500354. The
findings and comments noted during this inspection are provided in the enclosed copy of the inspection
report entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact Megan Faulkner with the Water
Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
megan.faulkner@ncdenr.gov.
Sincerely,
Do�cuySi�g�ne�dby: �q
Y vWY CUAA. � . �vvw,l
o�i14a4�Ciez-King, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: David Callahan (via email)
WQS Wilmington Regional Office-NCG500354
o.o„o..ma..wD� North Carolina Department of Environmental Quality I Division of Water Resources
Wilmington Regional Office 1127 Cardinal Drive Extension I Wilmington. North Carolina 28405
910.796.7215
DocuSign Envelope ID: 9BADD4EO-5AD8-4lC7-88CO-F42162B50EFB
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCG500354 Ill 121 21/07/07 I17 18 I C I 19 I s I 20L]
21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I n, I 71 I 74 79 I I I I I I I80
701 I 71 I LL -1 I I
LJ
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
10:OOAM 21/07/07
20/12/31
Slurry Pavers - Morehead City
107 Arendell St
Exit Time/Date
Permit Expiration Date
Morehead City NC 28557
11:15AM 21/07/07
25/11/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
David Callahan,107 Arendell St Morehead City NC 28557/Acting Facility
Manager/252-269-8872/2522223339 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar 0 Records/Reports
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) an i ftl'rts Inspector(s) Agency/Office/Phone and Fax Numbers Date
° envy 7/8/2021
John Perry DWR/Non Discharge Compliance Unit/910 796 7341/
pp
Megan D Fau n��rE38ED-Sign aby: DWR/WIRO WQ/910-796-7245/
7/8/2021
NAoni n. �Cu�Qk�e�
t�,.
SknTeRwesdnk4doagement Q A Reviewer Agency/Office/Phone and Fax Numbers Date
L`�S-6"7/9/2021
BA14AC7DC434...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
DocuSign Envelope ID: 9BADD4E0-5AD8-41C7-88C0-F42162B50EFB
NPDES yr/mo/day Inspection Type (Cont.)
NCG500354 I11 12I 21/07/07 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Megan Faulkner and John Perry from the Division of Water Resources (DWR), performed a site
inspection for permit NCG500354 on July 7, 2021. The inspectors met with onsite representative
David Callahan for the inspection. Mr. Callahan provided all documentation required and gave the
inspectors a tour of the facility and how it operates.
The facility has a boiler which blows down about once every 24 hours. An oxygen scavenger, a
polymer, and a streamline agent are still used in the boiler water. MSDS were available on site, and a
copy of the new permit from 2020 and COC were available on site.
Mr. Callahan stated that after there were 2 exceedences for residual chlorine in 2017, they switched
to using liquid chlorine in 2020 to keep these exceedences to a minimum. This has helped them stay
within their limits since making this change. Boiler blowdown water is pH adjusted with sulfuric acid
and is recirculated in a tank to allow for cooling and proper pH adjustment. They have a pH probe for
process control on the addition of sulfuric acid. Monitoring requirements are done by EnviroChem
and a copy of their lab certification was available on site. COD, pH, and temperature were analyzed,
as well as residual chlorine at least 2x/year. The water is allowed to cool in the tank while the pH is
adjusted prior to discharge in to a drain which has a tiered flow setup as well as a "pom pom" for
additional oil absorption from stormwater runoff. Estimated flow is -1000 gal/day.
Daily logs were available for discharging and they included the dates, start/stop times, initials of
discharge operator, and pH. No foam or oil sheen was present in the drain on the water surface.
Facility looks well maintained and records were complete.
Page#
DocuSign Envelope ID: 9BADD4E0-5AD8-41C7-88C0-F42162B50EFB
Permit: NCG500354 Owner -Facility: Slurry Pavers- Morehead City
Inspection Date: 07/07/2021 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ■ ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ■ ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The facility is well maintained. They keep a daily log book that includes PH and
start/stop times for pumping the boiler blowdown water.
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
■
❑
application?
Is the facility as described in the permit?
■
❑
❑
❑
# Are there any special conditions for the permit?
❑
❑
■
❑
Is access to the plant site restricted to the general public?
■
❑
❑
❑
Is the inspector granted access to all areas for inspection?
■
❑
❑
❑
Comment: The facility is located inside the State Port at Morehead City. ID's were used to perform
background checks on inspectors. The inssectors were then signed in and escorted to
the facility for inspection.
Record Keeping
Yes
No
NA NE
Are records kept and maintained as required by the permit?
■
❑
❑
❑
Is all required information readily available, complete and current?
■
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
■
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
❑
❑
■
❑
Is the chain -of -custody complete?
■
❑
❑
❑
Dates, times and location of sampling
■
Name of individual performing the sampling
■
Results of analysis and calibration
■
Dates of analysis
■
Name of person performing analyses
■
Transported COCs
■
Are DMRs complete: do they include all permit parameters?
❑
❑
■
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
■
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
❑
❑
■
❑
operator on each shift?
Is the ORC visitation log available and current?
❑
❑
■
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
■
❑
Page# 3
DocuSign Envelope ID: 9BADD4E0-5AD8-41C7-88C0-F42162B50EFB
Permit: NCG500354 Owner -Facility: Slurry Pavers- Morehead City
Inspection Date: 07/07/2021 Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Is the backup operator certified at one grade less or greater than the facility ❑ ❑ 0 ❑
classification?
Is a copy of the current NPDES permit available on site? E ❑ ❑ ❑
Facility has copy of previous year's Annual Report on file for review? 0 ❑ ❑ ❑
Comment: This facility has permit NCG500354 general permit for boiler blowdown operations.
Laboratory analysis were completed by EnviroChem which is a state certified lab.
Records were available for at least than 5 years prior to present date.
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
kreTvki[•7►/_90I:1
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
Comment: 7.5hp 2 inch diameter discharge at 170GPM. On site representative states that they
lower the levels by -1ft when discharging and estimates that amount to be-1000gal.
On site representative also states that they discharge to the storm drain which is tiered
for settlement and has a "Pom Porn" for added protection against oil/grease discharge.
Laboratory
Yes
No
NA
NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
■
❑
❑
❑
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
❑
■
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
❑
Comment: Laboratory processing done by EnviroChem State Certified Lab. pH meter is
located
on site for process control. ChemTreat checks behind them 1x/month and they
have an
extra small lab on site for analyzing boiler water to ensure that only the amount of
chemicals necessary are added.
Page# 4