HomeMy WebLinkAboutWQ0002571_Recon follow-up_20210628DocuSign Envelope ID: 639FD19F-91AC-409D-9AFB-64DC1BE8208D
ROY COOPER
Governor
JOHN NICHOLSON
Interim Secretary
S. DANIEL SMITH
Director
Bobby F Williams
164 Harris Creek Rd
Jacksonville, NC 28540
i
�u
NORTH CAROLINA
Environmental Quality
June 29, 2021
SUBJECT: Compliance Inspection Report
Village Oaks Mobile Home Park WWTF
Non -discharge Permit No. WQ0002571
Onslow County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Village Oaks Mobile
Home Park WWTF on 6/28/2021. This inspection was conducted to verify that the facility is operating
in compliance with the conditions and limitations specified in Non -discharge Permit No. WQ0002571. The
findings and comments noted during this inspection are provided in the enclosed copy of the inspection
report entitled "Compliance Inspection Report".
If you should have any questions, please do not hesitate to contact Helen Perez with the Water
Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
helen.perez@ncdenr.gov.
ATTACHMENTS
Cc: Allen Rhue — electronic copy
Upload to Laserfiche
Sincerely,
DocuSignedby: For
E70
OA.
F1411.73B6F3456...
Morelia Sanchez -King, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
North Carolina Department of Environmental Quality I Division of Water Resources
Wilmington Regional Office 1 127 CardinaI Drive Extension I Wilmington North Carolina 26405
Compliance Inspection Report
Permit: WQ0002571 Effective: 08/23/19 Expiration: 09/30/24 Owner: Bobby F Williams
SOC: Effective: Expiration: Facility: Village Oaks Mobile Home Park WWTF
County: Onslow 2980 Burgaw Hwy
Region: Wilmington
Jacksonville NC 28540
Contact Person: Bobby F Williams Title: Phone: 910-346-9912
Directions to Facility:
Southwest of Jacksonville. On the North side of NC Highway 53 approximately 0.4 mile West of SR 1109.
System Classifications: SI,
Primary ORC: Allen Wayne Rhue Certification: 987930 Phone: 910-358-3254
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Inspection Date: 06/28/2021 Entry Time 10:OOAM
Primary Inspector: Helen I Perez DocuSignetd�by:
Secondary Inspector(s):� n"Iz�
1 D646B4A39694BE...
Reason for Inspection: Routine
Permit Inspection Type: Wastewater Irrigation
Facility Status: ❑ Compliant ❑ Not Compliant
Question Areas:
Exit Time: 11:OOAM
Phone: 910-796-7387
Inspection Type: Reconnaissance
Miscellaneous Questions 0 End Use -Irrigation
(See attachment summary)
Page 1 of 3
Permit: WQ0002571 Owner - Facility: Bobby F Williams
Inspection Date: 06/28/2021 Inspection Type : Reconnaissance Reason for Visit: Routine
Inspection Summary:
A reconnaissance inspection of the Village Oaks Mobile Home Park WWTF was conducted on June 28, 2021. The purpose
of the site visit was to verify that the facility has addressed the violations noted in the NOV issued for the inspection on
January 24, 2020. The Permittee, Bobby Williams, and the ORC, Allen Rhue, were present during the site visit.
Maintenance of the irrigation field has improved as well as the documentation of maintenance activities. Lines and sprinkler
heads have been repaired or replaced as needed to prevent ponding. Sprinkler heads at the end of some lines have been
shut off to allow more pressure so the remaining heads can spray the full radius and to prevent run-off in sloped areas. The
crop cover has been restored. The lagoon had a 2 foot, 10 inch freeboard during the site visit. There is a low area on the
northeast side of the lagoon berm. This issue will need to be continuously monitored and measures need to be taken to
prevent any overflow from occuring.
Page 2 of 3
Permit: WQ0002571 Owner - Facility: Bobby F Williams
Inspection Date: 06/28/2021 Inspection Type : Reconnaissance
Reason for Visit: Routine
Type
Yes No NA NE
Single Family Spray, LR
❑
Activated Sludge Spray, LR
❑
Activated Sludge Spray, HR
❑
Activated Sludge Drip, LR
❑
Recycle/Reuse
❑
Single Family Drip
❑
Reuse (Quality)
❑
Infiltration System
❑
Lagoon Spray, LR
End Use -Irrigation
Yes No NA NE
Are buffers adequate?
❑
❑ ❑
Is the cover crop type specified in permit?
❑
❑ ❑
Is the crop cover acceptable?
❑ ❑ ❑
Is the site condition adequate?
❑ ❑ ❑
Is the site free of runoff / ponding?
❑ ❑ ❑
Is the acreage specified in the permit being utilized?
❑ ❑ ❑
Is the application equipment present?
❑ ❑ ❑
Is the application equipment operational?
❑ ❑ ❑
Is the disposal field free of limiting slopes?
❑
❑ ❑
Is access restricted and/or signs posted during active site use?
❑ ❑ ❑
Are any supply wells within the CB?
❑
❑ ❑
Are any supply wells within 250' of the CB?
❑
❑ ❑
How close is the closest water supply well?
❑
❑ ❑
Is municipal water available in the area?
❑
❑ ❑
# Info only: Does the permit call for monitoring wells?
❑ ❑ ❑
Are GW monitoring wells located properly w/ respect to RB and CB?
❑ ❑ ❑
Are GW monitoring wells properly constructed, including screened interval?
❑
❑ ❑
Are monitoring wells damaged?
❑
❑ ❑
Comment: Maintenance of the irrigation field has improved and been documented since the last
inspection on 01/24/2020. The crop cover has been restored and sprinkler
heads and lines
repaired or replaced.
Page 3 of 3