HomeMy WebLinkAboutWQ0007909_Application (FTSE)_19930514i
MEMO TO: State Review Group
FROM:
Supervisor °! t
SUBJECT: Procedure'' (4)
WQ000790
Karen Lake Condominiums
Sewer Extension - Public
City of Fayetteville
Cumberland County
Division of Environmental
Management
Fayetteville Regional
Office
05/24/93
Date
State Review Group Review
Engineer Jill Little
Regional Office
Contact Ricky Revels
1) Name of wastewater treatment plant to receive the wastewater:
PWC of Fayetteville - Rockfish Creek Wastewater Treatment Plant
2) WWTP design capacity 6.0 MGD
3) NPDES Permit No.: NC0050105
4) Compliance Information:
Present treatment plant performance
for previous 12 months - beginning 04/01/92
5
(See attached self -monitoring data)
Expiration Date: 05/31/96
0/9z0
Quantity and type of wastewater from proposed sewers: -46.1--TG6' GPD
domestic 100% ; industrial
; other
6) Volume from previously approved projects not yet tributary to
WWTP 2,279,296 GPD
7) Regional Recommendations: Approval X
MJN/RR/rr
Enclosure
Denial
pgay
MAY 17 1993 Cd
ENV. MANAGEMENT
State of North Carolina FAYETTEVILLE REG. OFFICE
Department of Environment, Health and Natural Resources
Division of Environmental Management
512 North Salisbury Street • Raleigh, North Carolina 27604
James B. Hunt, Jr., Governor A. Preston Howard, Jr., P.E.
Jonathan B. Howes, Secretary Director
May 14, 1993
MR TIMOTHY WOOD
PWC FAYE 1T VII LE
PO DRAWER 1089
FAYE F1'hVWI .F, NORTH CAROLINA 28302
Subject: Application No. WQ0007909
Karen Lake Condominiums
Sewers -Public
Cumberland County
Dear MR WOOD:
The Division's Permits and Engineering Unit acknowledges receipt of your permit application and
supporting materials on May 14, 1993. This application has been assigned the number shown above.
Please refer to this number when making inquiries on this project.
Your project has been assigned to Jill Little for a detailed engineering review. A technical
acknowledgement will be forthcoming.
Be aware that the Division's regional office, copied below, must provide recommendations from the
Regional Supervisor or a Procedure Four Evaluation for this project, prior to final action by the
Division.
If you have any questions, please contact Jill Little at (919) 733-5083.
Sincerely,
Donald Safrit, P.E.
Supervisor, Permits and Engineering Unit
cc: Fayetteville Regional Office
Moorman, Kizer & Reitzel, Inc.
Pollution Prevention Pays
P.O. Box 29535, Raleigh, North Carolina 27626-0535 Telephone 919-733-7015
An Equal Opportunity Affirmative Action Employer
44
State of North Carolina
Department of Environment, Health, and Natural Resources
Division of Environmental Management
Non -Discharge Permit Application
(THIS FORM MAY BE PHOTOCOPIED FOR USE AS AN ORIGINAL)
. GRAVITY SEWER EXTENSION
I. GENERAL INFORMATION:
Public Works Commission of The
1. Applicant (corporation, individual, or other ): Ci ty of Fayettevi 11 e, NC
2. Print Owners or Signing Official's Name and Title (the person who is legally
responsible for the facility and its compliance): Timothy Wood, Manager
3. Mailing Address: Post Off ce Drawer 1089
City: Fayetteville
State:
NC Zip: 28302-1089
Telephone No.: ( 919 ) 483-1382
4. Project Name (subdivision, facility, or establishment name - should be consistent with
project name on plans/specs., letters of flow acceptance, Operational Agreements, etc.):
Karen Lake Condominiums
5. Application Date: Apri 1 1993 6. Fee Submitted: $ 200.00
7. County where project is located: Cumberl and
II. PERMIT INFORMATION:
1. Permit No. (will be completed by DEM): WQO D' )
2. Specify whether project is: x new; renewal*; modification.
*If renewal, complete only sections I through III and applicant signature
(on pg.5). Submit only pgs. 1, 2, 5 (original and 3 copies of each). Engineer
signature not required for renewal.
3. If this application is being submitted as a result of a renewal or modification to an
existing permit, list the existing permit number and issue date
4. Specify whether the applicant is x public or private.
FORM: GSEA 4/91 Page 1 of 6
GRAVITY SEWER EXTENSION
PAGE 2 (4/91)
III. INFORMATION ON WASTEWATER:
1. Nature of Wastewater: 100 % Domestic; % Commercial;
% Industrial; % Other waste (specify):
2. Please provide a one or two word description specifying the origin of the wastewater,
such as school, subdivision, hospital, commercial, industrial, apartments, etc.:
208 Unit, 26 Building Condominium
3. Indicate any parameter (and its concentration) that will be greater than normal domestic
levels: NONE
4. If wastewater is not domestic in nature, what level of pretreatment has been provided to
ensure protection of the receiving wastewater treatment facility?
N/A
5. Volume of wastewater generated, by this project: 49,920 gallons per day
6. Explanation of how wastewater volume was determined: 208 uni ts 2 bedroom
@ 120 GPD per bedroom = 240 GPD per unit.
IV. DESIGN INFORMATION:
1. Brief project description: Extending 8" sanitary sewer from an existing 8"
line to serve a 208 unit condominium complex. Total of 279 1.f. of
8''and 17 manholes.
2. Name of wastewater treatment facility receiving wastewater: . Rockfish Treatment Plant
a. Facility permit no.: NC0050105
b. Engineer should provide statement of his evaluation of downstream sewers to
accept the wastewater: This system connects to the overal 1 Beaver
Creek Outfall which is designed to serve this area.
2of6
GRAVITY SEWER EXTENSION
PAGE 3 (4/91)
3. Summary of sewer pipe by diameter size and pipe material. Indicate here whether C
factor or N factor is used and circle C or N below:
Dia. Length Pipe C or N Min. Max. Minimum Max. Minimum
(In.) (Lin. Ft) Material Factor Slope % Slope % Velocity (fps) Vel.(fps) Cover (in)
8 2790 V.C. 0.013 0.40 3.10 2.2 6.0 36
NOTE: The minimum velocity must not be less than 2 fps.
For public sewers the minimum diameter is 8 inches.
4. Anchors shall be provided for sewers with slopes greater than 20 %. The anchor
spacing shall be as follows:
a. 36 feet separation for slopes of 21% to 35%;
b. 24 feet separation for slopes of 36% to 50%;
c. 16 feet separation for slopes of 50% and greater.
For velocities greater than 15 fps, it is strongly recommended that measures be
considered which will protect the sewers and manholes from erosion. For velocities
greater than 20 fps, erosion control measures must be specified.
For any excessive slopes or velocities that will occur in any sewer line segment, what
measures have been taken to protect the sewer pipe and manholes?
5. Maximum sewer reach length between manholes: 280 linear feet.
6. This sewer line segment occurs between manhole no. 15+86 and manhole no.18+66
7. Does the owner/operator have the ability to clean this length? X Yes No.
8. Sewer subject to existing or planned traffic bearing loads? X Yes No.
If yes, what measures -are being taken to enable the sewers to withstand the loads?
Min. 36" of cover with suitable backfill and compaction.
9. Outside drop manholes are provided where invert separations exceed: N/A feet.
10. Identify (by manhole number) those manholes that have drop connections: NONE
11.
GRAVITY SEWER EXTENSION'
PAGE 4 (4/91)
Maximum allowable infiltration/exfiltration test rate:
Note: Must not exceed 200(GPD/ pipe dia. in./ mile. 100 GPD/ pipe dia. in./ mile.
100
12. Minimum separation distances as shown on the plans or addressed in the specifications:
a) 100 ft. horizontal separation from wells or other water supplies? _ Yes _ No
b) 12 in. vertical separation from storm sewer or ferrous pipe
sanitary sewer specified? x Yes _ No
c) 10 ft. horizontal separation from water mains or 18 in. vertical
separation (water over sewer) or ferrous pipe specified? x Yes _ No
13. Are manholes subject to flooding? Yes x No
14. If yes, are manhole rim elevations 1 foot above 100-year flood level, Yes No
(100 year flood elevation should be indicated on plans)
15. Or are manholes watertight and vented 1 foot above the 100-year
flood elevation ( should be shown on plans): _Yes No
16. Identify (by manhole number) those manholes that are vented:
17. Does this project involve any stream crossings? _ yes x no. If yes, what precautions
or special features have been utilized to ensure protection of the sewer line and not
restrict stream flow? Identify the sheet of the plans and station number where stream
crossings are located:
THIS APPLICATION PACKAGE WILL NOT BE ACCEPTED BY THE
, DIVISION OF ENVIRONMENTAL MANAGEMENT UNLESS ALL OF
THE APPLICABLE ITEMS ARE INCLUDED WITH THE SUBMITTAL
Required Items
a. One original and three copies of the completed and appropriately executed application form.
b. Three sets of detailed plans and specifications signed and sealed by a North Carolina
Professional Engineer. The plans must include a general location map, a plan view of the
sewer extension, a profile of the sewer extension, and must show the proximity of the
sewer extension to other utilities and natural features. Specifications may be omitted for
delegated authorities. Each sheet of the plans and the first page of the specifications must be
signed and sealed. Three copies of the existing permit if a renewal or modification.
c. The appropriate permit processing fee, in accordance with 15A NCAC 2H .0205(c)(5).
d. If the owner/authority of the wastewater treatment facility (WWTF) that will be accepting
the wastewater flow from this project is different from the applicant of the project, then a
letter must be provided from the owner/authority of the WWTF specifying the volume of
flow that will be accepted. The letter should be a recent letter and should refer to the project
by the same name as that identified on the application and the plans/specifications.
e. An Operational Agreement (original and two copies) must be submitted if the sewer
extension will be serving single family residences, condominiums, mobile homes, or town
houses and if the subject sewer extension is owned by the individual residents, a
homeowners association, or a developer.
4 of 6
GRAVITY SEWER EXTENSION
PAGE 5 (4/91)
Name and Complete Address of Engineering Firm: Moorman, Kizer & Rei tzel , Inc.
Post Office Box 53774
City:
Fayetteville State: NC Zip: 28305
Telephone No. (919) 484-5191
Professional Engineer's Certification:
I, James M. Kizer , attest that this application for Karen Lake
Condominiums has been reviewed by me and is accurate
and complete to the best of my knowledge. I further attest that to the best of my knowledge the
proposed design has been prepared in accordance with the applicable regulations. Although certain
portions of this submittal package may have been developed by other professionals, inclusion of
these materials under my signature and seal signifies that I have reviewed this material and have
judged it to be consistent with the proposed design.
North Carolina Professional Engineer's Registration No.
4783
Print Name of Engineer James M. Kizer
Seal and Signature (specify date):
Applicant's Certification:
I, Timothy Wood
Karen Lake Condominiums
�i ✓ tiiVGIN�`�]+• `� e
�yoN•o e
,
♦ 7
FSM.‘4-�
, attestt4tk
is application for
has been reviewed by me and is accurate and complete to the best of my knowledge. I understand
that if all required parts of this application are not completed and that if all required supporting
information and attachments are not included, this application package will be returned as
incomplete.
Signature
Date 6-9�
THE COMPLETED APPLICATION PACKAGE, INCLUDING ALL SUPPORTING
INFORMATION AND MATERIALS, SHOULD BE SENT TO THE FOLLOWING ADDRESS:
NORTH CAROLINA DIVISION OF ENVIRONMENTAL MANAGEMENT
WATER QUALITY SECTION
PERMITS AND ENGINEERING UNIT
POST OFFICE BOX 29535
512 NORTH SALISBURY STREET
RALEIGH, NORTH CAROLINA 27626-0535
TELEPHONE NUMBER: 919/733-5083
5 of 6
f
GRAVITY SEWER EXTENSION'
PAGE 6 (4/91)
PERMIT APPLICATION PROCESSING FEES
(effective October 1, 1990)
CATEGORY NEW APPLICATIONS/ RENEWALS WITHOUT
MODIFICATIONS MODIFICATIONS
> 1,000,000 GPD
Industrial $400 $300
Domestic/Cooling Water $400 $300
10,001 - 1,000,000 GPD
Industrial $400
Domestic/Cooling Water $400
$250
$250
1,001 - 10,000 GPD
Industrial $400 $200
Domestic/Cooling Water $400 $200
< or = 1,000 GPD and
Single Family Dwelling $240 $120
Sludge < or = 300 Acres $400 $250
Sludge > 300 Acres $400 $250
Sewer Extensions
(nondelegated) $400 0
Sewer Extensions
(delegated)
$200 0
Closed -Loop Recycle
or Evaporative $400 $200
NOTE: The Fees for Soil Remediation Projects are the same as for Sludges.
Under the Sewer Extension Fee, "delegated to municipalities" applies
only to those governmental jurisdictions that have specific delegation
review authority, as granted by the Division of Environmental
Management.
6 of 6
State of North Carolina
Department of Environment, Health, and Natural Resources
Division of Environmental Management
512 North Salisbury Street • Raleigh. North Carolin:: 2.7(i 64) 35
James G. Martin, Governor
\Villiam W. Cobey, Jr., Secretary
May 1, 1991
Memorandum
To: Delegated Municipalities
From: Steve W. Tedder, Chief(\
Water Quality Section
Subject: Delegated \'lunic:palit cs Ch,eckiist for Revised Non-Dischal�Te Permit Applicatio-ns
The Division of Environmental Management's Water Quality Section has revised the
Gravity Sewer Non -Discharge Permit Application Form. The form now incorporates the basic
information that the Division feels is necessary in order for the delegated municipalities to perform a
review on a gravity sewer project for the Division; therefore, the Division will no longer require that
the "Delegated Municipalities Gravity Sewer Design Checklist" be completed and submitted. We do,
however, require that the delegated municipality perform the same type of review as always required
and complete the bottom portion -of this page and attach it as the last page of all gravity seater
applications that are being submitted as a delegated municipalities project. If you have any questions
on this matter, please contact Mr. Randy Jones at 919/733-5083.
DELEGATED MUNtICIPALITY GRAVITY SEWER CERTIFICATION
(THIS FORM MAY BE PHOTOCOPIED FOR USE AS AN ORIGINAL)
Applicant:
AROLINA
Project Name: KAREN LAKE CONDOMINIUMS
Delegated Municipality Reviewer's Certification:
1, VICTOR GAN.TEHSANT , attest that the subject plans and
specifications have been reviewed under my supervision and that those plans and specifications are
consistent with the information that has been specified on the Non -Discharge Application and the
Division of Environmental Management's minimum design requirements for gravity sewer projects.
Delegated Municipality Reviewers NC Processional Engineer's Registration No.:
Seal and Signature (specify date):
StIO CARD /''
�,.,........• CAROL/AP
-1. ,,
. �.(ESSIONq�
s. I a SEAL 1 r.
14368 i
CD
FORM: DMGS 4/91
PAGE 1 OF 1
State of North Carolina
Department of Environment, Health and Natural
Division of Environmental Management
512 North Salisbury Street • Raleigh, North Carolina
James B. Hunt, Jr., Governor
May 18, 1993
Mr. Timothy Wood, Manager
Public Works Commission of the City of Fayetteville
PO Drawer 1089
Fayetteville, NC 28302-1089
Dear Mr. Wood:
MAY 20 1993 v) `
ENV.
FAYETTEVILLE REG. OFFICE
Resources
27604
Jonathan B. Howes, Secretary
Subject: Application No. WQ0007909
Additional Information Request
Public Works Commission of the
City of Fayetteville
Karen Lake Condominiums
Sewer Extension
Cumberland County
The Permits and Engineering Unit has completed a preliminary engineering review of the subject
application. The following items must be addressed before we can complete our review:
1) Page 3 of the application form states that the only type of pipe material to be used is
vitrified clay, whereas the plans show that ductile iron pipe will be used in some areas.
Please submit three revised copies of page 3 of the application indicating that ductile iron
pipe will be used.
2) Please check the minimum vertical separation of the water line crossing near manhole 6 +
95 (sheet 5). Please be advised that if the vertical separation of the water line from the
sewer line is less than 18 inches, ductile iron pipe must be specified. If appropriate, please
make the necessary revisions to this sheet and submit three copies.
Refer to the subject permit application number when providing the requested information. Please
submit three copies of all information to my attention at the address below. Also, please
note that failure to provide this additional information on or before June 18, 1993, will subject your
application to being returned as incomplete, in accordance with 15A NCAC 2H .0208.
Regional Offices
Asheville Fayetteville Mooresville Raleigh Washington Wilmington Winston-Salem
704/251-6208 919/486-1541 704/663-1699 919/571-4700 919/946-6481 919/395-3900 919/896-7007
Pollution Prevention Pays
P.O. Box 29535, Raleigh, North Carolina 27626-0535 Telephone 919-733-7015
An Equal Opportunity Affirmative Action Employer
If you have any questions on this matter, please call me at 919/733-5083.
Sincerely,//
Jill Little
Environmental Engineer
State Engineering Review Group
cc: Fayetteville Regional Office
Permit File WQ0007909
Moorman, Kizer & Reitzel, Inc.
June 20, 1994
TIMOTHY WOOD
PWC/FAYETI'EVILLE-KAREN LAKE C
PO DRAWER 1089
FAYETITEVILLE, NC 28302
JUN 22 1994
ENV. MANA EMiNl
FAYETTEVILLE REG. OFFICE
SUBJECT: CERTIFICATE OF COMPLETION
PERMIT NO. WQ0007909
PWC/FAYETTEVILLE-KAREN LAKE C
CUMBERLAND COUNTY
Dear Permittee:
On May 28, 1993 the Division of Environmental Management issued you
the subject permit. One of the conditions of the subject permit read as
follows:
Upon completion of construction and prior to operation of this permitted
facility, a certification must be received from a professional engineer
certifying that the permitted facility has been installed in accordance
with the requirements of this permit and the approved plans and
specifications. Mail certification to the Permits and Engineering Unit,
P.O. Box 29535, Raleigh, N.C., 27626-0535.
To date, our records show that no certification has been received for the
subject permit. If the permitted facility has been constructed and placed into
operation please submit the required certification immediately. Operation of
the treatment system prior to submission of the required certification is in
violation of your permit and is subject to enforcement action. If you have any
questions, please contact your consulting engineer for this project,
MOORMAN,KIZER & REITZEL,I at (919)484-5191. If the facility has not been
constructed, please contact the Fayetteville Regional Office at (919)486-1541,
so that they can update their records.
Thank you for your prompt attention to this matter.
SincerelyOriginal Signed By
Angela Y. Griffin for
•
cc: File
Fayetteville Regional Office
Carolyn McCaskill, Supervisor
State Engineering Review Group