HomeMy WebLinkAboutWQCSD0272_Compliance Evaluation Inspection_20210622ROY COOPER.
Governor
JOHN NICHOLSON
Interim Secretary
S. DANIEL SMITH
Director
Certified Mail #
Return Receipt Requested
Milton W Farmer
Town of Wagram
PO Box 118
Wagram, NC 28396
NORTH CAROLINA
Environmental Quality
June 11, 2021
SUBJECT: Compliance Inspection Report
Town of Wagram Collection System
Collection System Permit No. WQCSD0272
Scotland County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Town of Wagram
Collection System on 4/28/2021. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in Collection System Permit No. WQCSD0272.
The findings and comments noted during this inspection are provided in the enclosed copy of the
inspection report entitled "Compliance Inspection Report".
Please respond in writing to this office within 30 days of your receipt of this letter regarding your plans
or measures to be taken to address the following issues:
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
The Wagram Collection System is a deemed system consisting of five duplex pump stations. Mapping of this
system is in GIS format. In addition to an overall sewer map, the system is broken down into detailed
sections. Ms. Lowery keeps records well organized at the town hall and Robert takes good care of the pump
stations, inspecting them daily.
D E
North Carolina Department of Environmental Quality Division of Water Resources
Fayetteville Regional Office 1225 Green Street. Suite 714 I Fayetteville, North Carolina 28301
910.433.3300
If you should have any questions, please do not hesitate to contact Danielle Simpson with the Water
Quality Regional Operations Section in the Fayetteville Regional Office at 910-433-3300 or via email at
danielle.simpson@ncdenr.gov.
Sincerely,
DocuSigned by: Q
v"Qb
5189C2D3DD5C42B...
J. Trent Allen, Regional Supervisor
Water Quality Regional Operations Section
Fayetteville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: WQS Fayetteville Regional Office (DS)
PERCS Compliance/Enforcement Unit
�QE
Denny..,. EN1,0M1MMuI 0w114
North Carolina Department of Environmental Quality Division of Water Resources
Fayetteville Regional Office 1225 Green Street. Suite 714 I Fayetteville, North Carolina 28301
910.433.3300
Compliance Inspection Report
Permit: WQCSD0272 Effective: 03/01/00 Expiration:
SOC: Effective: Expiration:
County: Scotland
Region: Fayetteville
Contact Person: Milton W Farmer
Directions to Facility:
Owner : Town of Wagram
Facility: Town of Wagram Collection System
Title: Mayor Phone: 910-369-2776
System Classifications:
Primary ORC: Certification: Phone:
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Inspection Date: 04/28/2021
Primary Inspector: Danielle Simpson
Secondary Inspector(s):
Entry Time 09:30AM
1-DocuSig1ned by:�/ .2 ✓i vti ��¢ CJ r bo t
"-8C7638281 DAB46D...
�DocuSigned by:
.n MA Q-QkeA,
Reason for Inspection: Routine•-5189C2D3DD5C42B . Inspection Type: Collection System Inspect Non Sampling
Permit Inspection Type: Deemed permitted collection system management and operation
Facility Status: Compliant Not Compliant
Question Areas:
▪ Miscellaneous Questions
II Spills/Response Plan
▪ Manholes
(See attachment summary)
▪ General
▪ Inspections
▪ Pump Stations
Exit Time: 11:OOAM
6/16/2021 Phone: 910-433-3334
6/22/2021
▪ Grease Control
▪ Lines
Page 1 of 6
Permit: WQCSD0272 Owner - Facility:Town of Wagram
Inspection Date: 04/28/2021
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
Inspection Summary:
The Wagram Collection System is a deemed system consisting of five duplex pump stations. Mapping of this system is in
GIS format. In addition to an overall sewer map, the system is broken down into detailed sections. Ms. Lowery keeps
records well organized at the town hall and Robert takes good care of the pump stations, inspecting them daily. A grease
control ordinance was available, and education is distributed with water bills several times a year. There are no HPLs in this
system. Three of the five pump stations were inspected (#1, #2, #5) and all had proper signage, secure with restricted
access, and functioning audio and visual alarms. A spill response plan was not available at the time of inspection but has
since been developed.
Page 2 of 6
Permit: WQCSD0272 Owner - Facility:Town of Wagram
Inspection Date: 04/28/2021
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
General
# Is this system a satellite system?
# If Yes, what is system name or permit number?
Is there a overall sewer system map?
Does the map include:
Pipe sizes
Pipe materials (PVC, DIP, etc)
Pipe location
# Flow direction
# Approximate pipe age
# Pump station ID, location and capacity
# Force main air release valve location & type
# Location of satellite connections
Are system maintenance records maintained?
Comment: GIS format, stored on a flashdrive and organized by section.
Grease Control
Is grease/sewer education program documented with req'd customer distribution?
# Are other types of education tools used like websites, booths, special meetings, etc?
If Yes, what are they? (This can reduce mailing to annual.)
Educational information is included with water bills 2-3 times per year.
For public systems, is there a Grease Control Program via an ordinance/agreement? • ❑ ❑ ❑
If Yes, does it require grease control devices at applicable locations? • ❑ ❑ ❑
Is the Grease Control Program enforced via periodic inspections/records review? ❑ ❑ • ❑
Is action taken against violators? ❑ ❑ • ❑
Comment: Grease control devices are required at applicable locations. Thus far the town has not had any
issues that required action to be taken against violators.
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Spills and Response Action Plan
# Is system free of known points of bypass?
If No, describe type of bypass and location
# Have there been any sewer spills in the past 3 years?
If Yes, were they reported to the Division if meeting the reportable criteria?
If applicable, is there documentation of press releases and public notices issued?
Are all spills or sewer related issues/complaints documented?
# Are there repeated overflows/problems (2 or more in 12 months) at same location?
# If Yes, is there a corrective action plan?
Yes No NA NE
• ❑ ❑ ❑
❑ ❑ • ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ • ❑ ❑
Page 3 of 6
Permit: WQCSD0272 Owner - Facility:Town of Wagram
Inspection Date: 04/28/2021
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
Is a Spill Response Action Plan available?
Is a Spill Response Action Plan available for all personnel?
Does the plan include:
# 24-hour contact numbers
# Response time
# Equipment list and spare parts inventory
# Access to cleaning equipment
# Access to construction crews, contractors, and/or engineers
# Source of emergency funds
# Site sanitation and cleanup materials
# Post-overflow/spill assessment
Comment:
Inspections
Are adequate maintenance records maintained?
Are pump stations being inspected at the required frequency?
Is at least one complete functionality test conducted weekly per pump station?
Is there a system or plan in place to observe the entire system annually?
Is the annual inspection documented?
# Does the system have any high -priority lines/locations?
Are inspections of HPL documented at least every 6 months?
Are new lines being added to the HPL list when found or created?
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The are no HPLs in this system. Pump stations are inspected daily, and functionality tests are
documented on logs.
Lines/Right-of-Ways/Aerial Lines
Please list the Lines/Right of Ways/Aerial Lines Inspected:
Are right-of-ways and easements maintained for the full width for access?
If No, give details on temporary access:
Is maintenance documented?
Were all areas/lines inspected free of issues?
Comment:
Manholes
Please list the Manholes Inspected:
Are manholes accessible?
# Are manhole covers/vents above grade?
Are manholes free of visible signs of overflow?
Are manholes free of sinkholes and depressions?
Yes No NA NE
▪ ❑ ❑ ❑
•
❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page 4 of 6
Permit: WQCSD0272 Owner - Facility:Town of Wagram
Inspection Date: 04/28/2021
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
Are manhole covers present?
# Are manholes properly seated?
# Are manholes in good condition?
# Are inverts in good condition?
Is flow unrestricted in manholes?
Are manholes free of excessive amounts of grease?
Are manholes free of excessive roots?
Are manholes free of excessive sand?
Are manhole vents screened?
Are vents free of submergence?
Are manholes free of bypass structures or pipes?
Comment:
Pump Stations
Please list the Pump Stations Inspected:
#1, #5, and #2
# Number of duplex or larger pump stations in system
# Number of vacuum stations in system
# Number of simplex pump stations in system
# Number of simplex pump stations in system serving more than one building
How many pump/vacuum stations have:
# A two-way "auto polling" communication system (SCADA) installed?
# A simple one-way telemetry/communication system (auto -dialer) installed?
For pump stations inspected:
Are they secure with restricted access?
Were they free of by-pass structures/pipes?
Were wet wells free of excessive grease/debris?
# Do they all have telemetry installed?
Is the telemetry system functional?
Is a 24-hour notification sign posted ?
Does the sign include:
Owner Name?
Pump station identifier?
# Address?
Instructions for notification?
24-hour emergency contact numbers?
Are audio and visual alarms present?
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ •
Yes No NA NE
5
0
0
0
0
5
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page 5 of 6
Permit: WQCSD0272 Owner - Facility:Town of Wagram
Inspection Date: 04/28/2021
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
Are audio and visual alarms operable?
# Is there a backup generator or bypass pump connected?
If tested during inspection, did it function properly?
Is the back-up system tested at least bi-annually under normal operating conditions?
# Does it have a dedicated connection for a portable generator?
# Is the owner relying on portable units in the event of a power outage?
# If Yes, is there a distribution plan?
If Yes, what resources (Units/Staff/Vehicles/etc) are included in Plan?
# Does Permittee have the approved percentage of replacement simplex pumps?
Is recordkeeping of pump station inspection and maintenance program adequate?
Do pump station logs include at a minimum:
Inside and outside cleaning and debris removal?
Inspecting and exercising all valves?
Inspecting and lubricating pumps and other equipment?
Inspecting alarms, telemetry and auxiliary equipment?
Comment: Replacement pumps obtained through a vendor when needed.
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page 6 of 6