HomeMy WebLinkAboutNCG080822_Tier III Status Notification to MRO_20210602Georgoulias, Bethany
From: Khan, Zahid
Sent: Wednesday, June 2, 2021 10:16 AM
To: Lucas, Annette; McCoy, Suzanne; Meloy, Michael; Morman, Alaina; Georgoulias,
Bethany
Subject: FW: [External] Tier III Status Notification - City of Charlotte - Central Yard - Outfall 005
Attachments: Central Yard - Outfall 005 - Tier III Letter - May 2021_signed.pdf
Just for your information. Thanks
From: DeCristofaro, Andrew [mailto:Andrew.Decristofaro@charlottenc.gov]
Sent: Wednesday, June 2, 2021 9:51 AM
To: Khan, Zahid <zahid.khan@ncdenr.gov>; Moore, James <james.moore@ncdenr.gov>
Subject: [External] Tier III Status Notification - City of Charlotte - Central Yard - Outfall 005
CAUTION: External email. Do not click links or open attachments unless you verify. Send all suspicious email as an attachment to
Report Spam.
Zahid & James,
Please see the attached signed PDF letter which serves as notification of Tier III status for City of Charlotte's Central Yard
Facility (Outfall 005).
I have also sent you a hard copy via regular mail to:
610 E. Center Avenue
Suite 301
Mooresville, NC 28115
Please contact me with any questions or concerns you have.
Thank you and have a great day!
Andrew DeCristofaro
Water Quality Program Specialist
Storm Water Services
600 East 4th Street I 14th Floor I Charlotte, NC 28202
(704) 517-8771 1 Andrew.DeCristofaro@CharloffeNC.gov I CharlotteNC.gov
STORM
E;
Charlotte -Mecklenburg
tST®RM 600 E. Fourth Street
-Kl �R Charlotte, NC 28202
�V
`I'! 1 Fax 704.353.0473
Services
June 2, 2021
NC Department of Environmental Quality
Division of Energy, Mining, and Land Resources
Attention: Mr. Zahid Khan & Mr. James Moore
610 E. Center Avenue, Suite 301
Mooresville, NC 28115
Re: Tier III status at City of Charlotte Central Yard
NPDES Industrial Stormwater General Permit NCG080000
Dear Mr. Khan:
This letter is to inform you that the City of Charlotte's Central Yard has exceeded its permit
benchmark for total suspended solids (TSS) at Outfall 005 four times during the current permit
term.
The NPDES Industrial Stormwater General Permit NCG080000 standard for TSS is 100 mg/L.
The following summarizes the exceedances that have occurred:
Central Yard — Outfall 005
Permit Term — TSS Ezceedances to date
Date
TSS m
9/29/2020
162
2/11/2021
130
3/25/2021
238
5/3/2021
510
Outfall 005 is new and serves as a bypass from a new underground detention structure installed to
help reduce polluted discharges from the site. It had not been cleaned out since construction, but
a full cleanout and inspection was completed on May 21, 2021. Please note that regular
inspection and maintenance will be done going forward. Additional response measures include
enhanced in person site -specific training for staff.
Please feel free to contact me at (704) 517-8771 if _you would like to discuss this issue further.
Sincerely,
C� >0��
Andrew DeCristofaro
Waxer Quality Program Specialist
City of Charlotte Storm Water Services
•
To report pollution or drainage problems, call: 311
http://stormwaLer.charmeck.org
UTAIUOITE,.. 15.