HomeMy WebLinkAboutNC0025348_New Bern WWTP Inspection_20210524May 24, 2021
Walter B Hartman
City of New Bern
PO Box 1129
New Bern, NC 28563-1129
SUBJECT: Compliance Inspection Report
New Bern WWTP
NPDES WW Permit No. NC0025348
Craven County
Dear Mr. Hartman:
The North Carolina Division of Water Resources conducted an inspection of the New Bern WWTP on
5/11/2021. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NC0025348. The findings and comments
noted during this inspection are provided in the enclosed copy of the inspection report entitled
"Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact Paul Mays with the Water Quality
Regional Operations Section in the Washington Regional Office at 252-948-3940 or via email at
paul.mays@ncdenr.gov.
ATTACHMENTS
Cc: Laserfiche
�. :
Sincerely,
P MaLS
Paul Mays, Environmental Specialist 1
Water Quality Regional Operations Section
Washington Regional Office
Division of Water Resources, NCDEQ
„� :a
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection
1 Iti 1 2 I5 I 3 I NC0025348 111 121 21/05/11 I17
Type
18 L
11111111111
Inspector Fac Type
19I S I 2011
21111111 111111111111111111 1111111
r6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
671I 70I I 711751
I 72 I N I 731 1 1741
I I I I I I I80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES oermit Number)
New Bern WWTP
307 Glenbumie Dr
New Bern NC 28560
Entry Time/Date
10:OOAM 21/O5/11
Permit Effective Date
13/12/01
Exit Time/Date
12:OOPM 21/05/11
Permit Expiration Date
P
18/06/30
Name(s) of Onsite Representative(s)/Ttles(s)/Phone and Fax Number(s)
Tony Randall Hawkins/ORC/252-639-7556/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Walter B Hartman,PO Box 1129 New Bern NC 285631129/City
Manager/252-636-4014/2526361848 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Sludge Handling Dispo: Facility Site Review • Effluent/Receiving Wate Laboratory
Section ID: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Paul M Mays DWR/WARO WQ/252-948-3940/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
NPDES yr/mo/day Inspection Type
3I NC0025348 111 121 21/05/11 117 181,.1
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On 05/11/2021 Paul Mays with the Division of Water Resources from the Washington Regional Office
conducted a compliance evaluation of New Bern WWTP. The facility was found to be compliant with
permit #NC0025348. Below are the findings and observations found during the inspection:
The facility was well kept. All equipment was in good shape and operational.
10/2020 DMR and corresponding lab data was spot checked, and no discrepancies were found. The
2020 annual report was submitted, and the 2019 annual report was on hand. Operation and
maintenance logs were also present and complete. All other required documents were readily
available for review and well maintained. Staff assisted with retrieving data from lab reports to
compare with what was reported on eDMR report.
Influent flowmeter was calibrated on 04/27/2021
Influent sampler is flow proportional and obtains 450m1 samples. The temperature was set to 5
degrees Celsius.
Debris goes to a lined landfill three times a week on Monday, Wednesday, and Friday.
Grit goes to a lined landfill three times a week on Monday, Wednesday, and Friday.
Both clarifiers were in good working condition and effluent leaving them looked good. However, there
were some grease particles present. Clarifier 1 had a 1.5ft sludge blanket and clarifier 2 had a 2.25ft
sludge blanket. This was determined via sludge judge.
The generators are tested weekly, and the facility has a monthly checklist for maintenance. The fuel
tank for the generators were around 70% full.
Tertiary filters 2 backwashes a day at 11am and 3pm respectfully. The high-water alarms for the
tertiary filters were operational and function through SCADA.
Effluent flowmeter was calibrated on 04/27/2021
Effluent sampler is flow proportional and samples are 450m1 per sample. The temperature was set to
5 degrees Celsius.
Sludge press was in good working condition and was operating at the time of inspection.
Page# 2
Permit: NC0025348
Owner - Facility: New Bern WWTP
Inspection Date: 05/11/2021 Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ■ ❑ ❑ ❑
application?
Is the facility as described in the permit? MIDEID
# Are there any special conditions for the permit? MOOD
Is access to the plant site restricted to the general public? ■ ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? � ❑ ❑ ❑
Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? •❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable MOOD
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? • DOE
Is all required information readily available, complete and current? • ❑ ❑ ❑
Are all records maintained for 3 years (lab. reg. required 5 years)? MEDD
Are analytical results consistent with data reported on DMRs? ■ ❑ ❑ ❑
Is the chain -of -custody complete? ❑ ❑ ❑
Dates, times and location of sampling •
Name of individual performing the sampling •
Results of analysis and calibration •
Dates of analysis •
Name of person performing analyses •
Transported COCs
Are DMRs complete: do they include all permit parameters? ■ ❑ ❑ ❑
Has the facility submitted its annual compliance report to users and DWQ? •❑ ❑ ❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified MODE
operator on each shift?
Is the ORC visitation log available and current? MOLD
Is the ORC certified at grade equal to or higher than the facility classification? ■ ❑ ❑ ❑
Is the backup operator certified at one grade less or greater than the facility ■ ❑ ❑ ❑
classification?
Page# 3
Permit: NC0025348
Owner - Facility: New Bern W WTP
Inspection Date: 05/11/2021 Inspection Type: Compliance Evaluation
Record Keeping
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
▪ ❑ ❑ ❑
Comment: 10/2020 DMR and corresponding lab data was spot checked, and no discrepancies
were found. The 2020 annual report was submitted, and the 2019 annual report was
on hand. Operation and maintenance logs were also present and complete. All other
required documents were readily available for review and well maintained. Staff
assisted with retrieving data from lab reports to compare with what was reported on
eDMR report.
Flow Measurement - Influent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: Influent flowmeter was calibrated on 04/25/2021
Influent sampler is flow proportional and obtains 450m1 samples. The temperature was
set to 5 degrees Celsius.
Pump Station - Influent
Is the pump wet well free of bypass lines or structures?
Is the wet well free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry available and operational?
Is audible and visual alarm available and operational?
Comment:
Yes No NA NE
❑•❑ ❑
▪ ❑ ❑ ❑
• ❑ ❑ ❑
O 0E10
Yes No NA NE
• ❑ ❑ ❑
■ ❑ ❑ ❑
▪ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑•❑
• ❑ ❑ ❑
❑ ❑ ❑ •
Bar Screens Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris? • ❑ ❑ ❑
Is the screen free of excessive debris? • ❑ ❑ ❑
Is disposal of screening in compliance? 11000
Page# 4
Permit: NC0025348 Owner -Facility: New Bern WWTP
Inspection Date: 05/11/2021
Inspection Type: Compliance Evaluation
Bar Screens
Is the unit in good condition?
Yes No NA NE
▪ ❑ ❑ ❑
Comment: Debris from barscreen goes to a lined landfill three times a week on Monday,
Wednesday and Friday.
Grit Removal
Type of grit removal
a.Manual
b.Mechanical
Is the grit free of excessive organic matter?
Is the grit free of excessive odor?
# Is disposal of grit in compliance?
Yes No NA NE
•
•
• ❑ ❑ ❑
▪ ❑ ❑ ❑
• ❑ ❑ ❑
Comment: Grit goes to a lined landfill three times a week on Monday, Wednesday and Friday.
Oxidation Ditches
Are the aerators operational?
Are the aerators free of excessive solids build up?
# Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Are settleometer results acceptable (> 30 minutes)?
Is the DO level acceptable?(1.0 to 3.0 mg/I)
Are settelometer results acceptable?(400 to 800 ml/I in 30 minutes)
Comment:
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
▪ ❑ ❑ ❑
O 0011
❑ ❑ ❑•
❑ ❑ • ❑
❑ ❑ ❑•
Yes No NA NE
▪ ❑ ❑ ❑
▪ ❑ ❑ ❑
▪ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
▪ ❑ ❑ ❑
▪ ❑ ❑ ❑
Page# 5
Permit: NC0025348
Inspection Date: 05/11/2021
Owner - Facility: New Bern W WTP
Inspection Type: Compliance Evaluation
Secondary Clarifier Yes No NA NE
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately''/, of the sidewall depth)
MOOD
MODE
Comment: Both clarifiers were in good working condition and effluent leaving them looked good.
However, there were some grease particles present. Clarifier 1 had a 1.5ft sludge
blanket and clarifier 2 had a 2.25ft sludge blanket. This was determined via sludge
judge.
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
Comment: The generators are tested weekly and the facility has a monthly checklist for
maintenance. The fuel tank for the generators were around 70% full.
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
L ODE
• ❑ ❑ ❑
▪ ❑ ❑ ❑
• ❑ ❑ ❑
Sand Filters (Low rate) Yes No NA NE
(If pumps are used) Is an audible and visible alarm Present and operational? ■ ❑ ❑ ❑
Is the distribution box level and watertight? •❑ ❑ ❑
Is sand filter free of ponding? •❑ ❑ ❑
Is the sand filter effluent re -circulated at a valid ratio? ❑ ❑ ❑
# Is the sand filter surface free of algae or excessive vegetation? •❑ ❑ ❑
# Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1) ❑ ❑NI ❑
Comment: Tertiary filters 2 backwashes a day at 11am and 3pm respectfully. The high-water
alarms for the tertiary filters were operational and function through SCADA.
Pumps-RAS-WAS
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
Page# 6
Permit: NC0025348
Inspection Date: 05/11/2021
Owner - Facility: New Bern wwTP
Inspection Type: Compliance Evaluation
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: Effluent sampler is flow proportional and samples are 450m1 per sample. The
temperature was set to 5 degrees Celsius.
Disinfection -Liquid
Is there adequate reserve supply of disinfectant?
(Sodium Hypochlorite) Is pump feed system operational?
Is bulk storage tank containment area adequate? (free of leaks/open drains)
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Comment:
Yes No NA NE
•❑ ❑ ❑
•❑ ❑ ❑
MO ❑ ❑
❑ ❑ ❑
Yes No NA NE
•❑ ❑ ❑
• ❑ ❑ ❑
MEDD
MOOD
• ❑ ❑ ❑
OD ❑•
De -chlorination Yes No NA NE
Type of system ? Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)? MOOD
Is storage appropriate for cylinders? MOOD
# Is de -chlorination substance stored away from chlorine containers? MOOD
Comment:
Are the tablets the proper size and type? ❑ ❑ ❑
Are tablet de -chlorinators operational? DOME]
Number of tubes in use?
Comment:
Solids Handling Equipment
Is the equipment operational?
Is the chemical feed equipment operational?
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ OD
MI ❑ ❑ ❑
MOOD
Page# 7
Permit: NC0025348
Inspection Date: 05/11/2021
Owner - Facility: New Bern VO TP
Inspection Type: Compliance Evaluation
Solids Handling Equipment Yes No NA NE
Is the site free of excessive moisture in belt filter press sludge cake? • ❑ ❑ ❑
The facility has an approved sludge management plan? ❑ ❑ ❑•
Comment: Sludge press was in good working condition and was operating at the time of
inspection.