HomeMy WebLinkAboutNC0032077_authorization to construct_20090624ATA
NCDENR
North Carolina Department of Environment and Natural Resources
Division of Water Quality
Beverly Eaves Perdue Coleen H. Sullins Dee Freeman
Governor Director Secretary
June 24, 2009
Mr. Charles Smithwick, District Manager
Contentnea Metropolitan Sewerage District
P.O. Box 477
Grifton, North Carolina 28530
SUBJECT: Authorization to Construct
A to C No. 032077A01
Contentnea Metropolitan Sewerage District
Contentnea MSD WWTP
WWTP Improvements
Project No. E-SRL-T-08-0077
Pitt County
Dear Mr. Smithwick:
A letter of request for an Authorization to Construct was received June 13, 2008, by the
Division of Water Quality (Division), and final plans and specifications for the subject project
have been reviewed and found to be satisfactory. Authorization is hereby granted for the
construction of modifications to the existing 2.85 MGD Wastewater Treatment Plant, with
discharge of treated wastewater into Contentnea Creek in the Neuse River Basin.
This authorization results in no increase in design or permitted capacity and is awarded
for the construction of the following specific modifications:
Improvements to the CMSD WWTP including: a new mechanically cleaned bar
screen and a manually cleaned bar screen to handle a peak flow of 7.125 mgd; a
new grit removal system to handle a peak flow of 7.125 mgd with one (1) 250
gpm grit pump; a new Parshall Flume with influent metering; a new influent
splitter box; conversion of the effluent pump station to serve as the filter lift pump
station and to handle a peak flow of 7.125 mgd; four (4) new 2,030 gpm filter
feed pumps; four (4) new tertiary denitrification filtration system units with two
(2) 3,040 gpm backwash pumps, two (2) new 570 gpm mudwell pumps, three (3)
new 100 Hp backwash aeration blowers; a new three (3) bank UV disinfection
system designed to treat a peak flow of 7.125 mgd with one bank out of service; a
new post aeration system with a 10 Hp high speed aerator; and 2,020 LF of 36-
inch effluent outfall discharge line, in conformity with the project plans,
specifications, and other supporting data subsequently filed and approved by the
Department of Environment and Natural Resources.
1617 Mail Service Center, Raleigh, North Carolina 27699-1617
Location: 512 N. Salisbury St. Raleigh, North Carolina 27604
Phone: 919-807-63001 FAX: 919-807-6492 \ Customer Service: 1-877-623-6748
Internet: www.ncwaterquality.org
An Equal Opportunity \ Affirmative Action Employer
NorthCarolina
Naturally
Mr. Charles Smithwick
June 24, 2009
Page 2
This Authorization to Construct is issued in accordance with Part III, Paragraph A of
NPDES Permit No. NC0032077 issued January 23, 2007, and shall be subject to revocation
unless the wastewater treatment facilities are constructed in accordance with the conditions and
limitations specified in Permit No. NC0032077.
The sludge generated from these treatment facilities must be disposed of in accordance
with G.S. 143-215.1 and in a manner approved by the Division.
In the event that the facilities fail to perform satisfactorily, including the creation of
nuisance conditions, the Permittee shall take immediate corrective action, including those as may
be required by the Division, such as the construction of additional or replacement wastewater
treatment or disposal facilities.
The Washington Regional Office, telephone number (252) 946-6481, shall be notified at
least forty-eight (48) hours in advance of operation of the installed facilities so that an on site
inspection can be made. Such notification to the regional supervisor shall be made during the
normal office hours from 8:00 a.m. until 5:00 p.m. on Monday through Friday, excluding State
Holidays.
Upon completion of construction and prior to operation of this permitted facility, a
certification must be received from a professional engineer certifying that the permitted facility
has been installed in accordance with the NPDES Permit, this Authorization to Construct and the
approved plans and specifications. Mail the Certification to: Construction Grants & Loans,
DWQ/DENR, 1633 Mail Service Center, Raleigh, NC 27699-1633.
Upon classification of the facility by the Certification Commission, the Permittee shall
employ a certified wastewater treatment plant operator to be in responsible charge (ORC) of the
wastewater treatment facilities. The operator must hold a certificate of the type and grade at
least equivalent to or greater than the classification assigned to the wastewater treatment
facilities by the Certification Commission.
The Permittee must also employ a certified back-up operator of the appropriate type and
grade to comply with the conditions of T13A:8G.0202. The ORC of the facility must visit each
Class I facility at least weekly and each Class II, III and IV facility at least daily, excluding
weekends and holidays, must properly manage the facility, must document daily operation and
maintenance of the facility, and must comply with all other conditions of T15A:8G.0202.
A copy of the approved plans and specifications shall be maintained on file by the
Permittee for the life of the facility.
During the construction of the proposed additions/modifications, the permittee shall
continue to properly maintain and operate the existing wastewater treatment facilities at all times,
Mr. Charles Smithwick
June 24, 2009
Page 3
and in such a manner, as necessary to comply with the effluent limits specified in the NPDES
Permit.
You are reminded that it is mandatory for the project to be constructed in accordance
with the North Carolina Sedimentation Pollution Control Act, and when applicable, the North
Carolina Dam Safety Act. In addition, the specifications must clearly state what the contractor's
responsibilities shall be in complying with these Acts.
Prior to entering into any contract(s) for construction, the recipient must have obtained all
applicable permits from the State.
Failure to abide by the requirements contained in this Authorization to Construct may
subject the Permittee to an enforcement action by the Division in accordance with North
Carolina General Statute 143-215.6A to 143-215.6C.
The issuance of this Authorization to Construct does not preclude the Permittee from
complying with any and all statutes, rules, regulations, or ordinances which may be imposed by
other government agencies (local, state, and federal) which have jurisdiction.
One (1) set of approved plans and specifications is being forwarded to you. If you have
any questions or need additional information, please contact Seth Robertson, P.E. at telephone
number (919) 715-6206.
Sincerely,
rC-oleen H. Sullins
MM:sr
cc: Charles W. Davis, P.E. - The Wooten Company, 120 N. Boylan Ave., Raleigh, NC 27603
Pitt County Health Department
DWQ Washington Regional Office, Surface Water Protection
Technical Assistance and Certification Unit
Point Source Branch, NPDES Program
Michelle McKay, E.I.
SRL File