HomeMy WebLinkAboutWQ0002056_Inspection_20210518Compliance Inspection Report
Permit: WQ0002056 Effective: 05/04/20
SOC: Effective:
County: Onslow
Region: Wilmington
Contact Person: Michael Smith
Expiration: 06/30/26
Expiration:
Title: Park Manager
Owner : Ade 794 LLC
Facility: Patriot Place MHP WWTF
145 Hubert Blvd
Hubert NC 28539
Phone: 910-353-3433
Directions to Facility:
Travel NC Hwy. 172 North through the MCB Camp Lejeune to the NC Hwy. 24 intersection. Go straight, and proceed approx. 0.25
miles to stop sign. Turn left on Hubert Boulevard (NCSR 1745), and travel approx. one mile. The WWTF is located on the right.
System Classifications: SI,
Primary ORC: Mikel Howard Seely
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Inspection Date: 05/18/2021
Primary Inspector: Geoff Kegley
Secondary Inspector(s):
Entry Time 01:OOPM
Reason for Inspection: Routine
Permit Inspection Type: Wastewater Irrigation
Facility Status: Compliant ❑ Not Compliant
Question Areas:
▪ Treatment Flow Measurement -Effluent
▪ Treatment Flow Measurement -Water
Use Records
▪ Treatment Lagoons
(See attachment summary)
Certification: 1004691
Exit Time: 02:30PM
Phone: 910-330-8011
Phone:
Inspection Type: Compliance Evaluation
▪ Treatment Flow Measurement -Influent
▪ Treatment
In End Use -Irrigation
▪ Miscellaneous Questions
▪ Record Keeping
▪ Treatment Flow Measurement
Page 1 of 6
Permit: WQ0002056 Owner - Facility:Ade 794 LLC
Inspection Date: 05/18/2021 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Inspection Summary:
A routine compliance inspection of the Patriot Place Mobile Home Park WWTF was conducted on May 18, 2021. The
purpose of the evaluation was to verify that the facility is operating in compliance with the conditions and limitations specified
in Permit WQ0002056. Mike Seely-ORC and Jim Rowan -irrigation and maintenance staff were both present during the
inspection.
This facultative lagoon and irrigation system is permitted for 90,000gpd. Currently the flows are averaging approximately
20,000gpd. The 3 lagoons are hydraulically connected and the freeboard was 38 inches. Berms were maintained and had
recently been mowed.
Operational and maintenance records were well organized and the field was well maintained. There are 2 pump stations that
are maintained by staff and they are visited daily and maintenance is documented. Please note that the Permittee is
required to follow all requirements in 15A NCAC 02T . 0403 for deemed permitted collection systems.
An Operator Designation form needs to be submitted to update the ORC and Backup ORC for this facility, a copy of this
form was provided to the ORC during the inspection.
The facility is compliant with Permit W00002056. Please review the comment section of the inspection report for more
details.
Page 2 of 6
Permit: WQ0002056 Owner - Facility:Ade 794 LLC
Inspection Date: 05/18/2021 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Type
Infiltration System
Single Family Spray, LR
Activated Sludge Spray, LR
Activated Sludge Spray, HR
Activated Sludge Drip, LR
Recycle/Reuse
Single Family Drip
Reuse (Quality)
Lagoon Spray, LR
Treatment
Are Treatment facilities consistent with those outlined in the current permit?
Do all treatment units appear to be operational? (if no, note below.)
Comment:
Treatment Flow Measurement -Influent
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Does flowmeter appear to monitor accurately?
Comment: The flowmeter was calibrated on 4/30/2021 by Delta Systems.
Treatment Flow Measurement -Water Use Records
Is water use metered?
Are the daily average values properly calculated?
Comment:
Treatment Flow Measurement -Effluent
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Does flowmeter appear to monitor accurately?
Comment:
Record Keeping
Is a copy of current permit available?
Yes No NA NE
•
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
❑ ❑ • ❑
Yes No NA NE
❑ ❑ • ❑
❑ ❑ • ❑
Yes No NA NE
• ❑ ❑ ❑
Page 3 of 6
Permit: WQ0002056 Owner - Facility:Ade 794 LLC
Inspection Date: 05/18/2021 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Are monitoring reports present: NDMR?
NDAR?
Are flow rates less than of permitted flow?
Are flow rates less than of permitted flow?
Are application rates adhered to?
Is GW monitoring being conducted, if required (GW-59s submitted)?
Are all samples analyzed for all required parameters?
Are there any 2L GW quality violations?
Is GW-59A certification form completed for facility?
Is effluent sampled for same parameters as GW?
Do effluent concentrations exceed GW standards?
Are annual soil reports available?
# Are PAN records required?
# Did last soil report indicate a need for lime?
If so, has it been applied?
Are operational logs present?
Are lab sheets available for review?
Do lab sheets support data reported on NDMR?
Do lab sheets support data reported on GW-59s?
Are Operational and Maintenance records present?
Were Operational and Maintenance records complete?
Has permittee been free of public complaints in last 12 months?
Is a copy of the SOC readily available?
No treatment units bypassed since last inspection?
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ • ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
❑ ❑ ❑ •
Comment: Operational and maintenance records were well organized. EnviroChem is the contract lab
performing the required analyses.
End Use -Irrigation
Are buffers adequate?
Is the cover crop type specified in permit?
Is the crop cover acceptable?
Is the site condition adequate?
Is the site free of runoff / ponding?
Is the acreage specified in the permit being utilized?
Is the application equipment present?
Is the application equipment operational?
Is the disposal field free of limiting slopes?
Yes No NA NE
• ❑ ❑ ❑
❑ • ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page 4 of 6
Permit: WQ0002056 Owner - Facility:Ade 794 LLC
Inspection Date: 05/18/2021 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Is access restricted and/or signs posted during active site use?
Are any supply wells within the CB?
Are any supply wells within 250' of the CB?
How close is the closest water supply well?
Is municipal water available in the area?
# Info only: Does the permit call for monitoring wells?
Are GW monitoring wells located properly w/ respect to RB and CB?
Are GW monitoring wells properly constructed, including screened interval?
Are monitoring wells damaged?
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
❑ ❑ ❑ •
❑ • ❑ ❑
Comment: Groundwater monitoring records (GW-59s) for the last couple of years were reviewed and were
consistently compliant. Monitoring wells are sealed with water tight caps and locked. The
irrigation field was recently mowed and in good condition and irrigation was observed during
the inspection. Every other row is irrigated at a time and then alternated for the next spray
event. Application measurement is by pump run times.
TREATMENT LAGOON 1
Treatment Lagoons
Lagoon Type
Primary/Secondary
Influent structure
Banks/berms (seepage and erosion)
Vegetation (excessive vegetation on banks/berms)
Liner
Liner Type
Baffles/curtains
Freeboard Marker
Required freeboard
Actual freeboard
Are increments clearly marked on gauge at adequate intervals?
Has the water level gauge been surveyed w/ respect to lowest point on dike? wall?
No Evidence of overflow
Acceptable color
Floating mats
Yes No NA NE
None
Primary
❑ ❑ ❑ •
24
Inches
38
Inches
• ❑ ❑ ❑
❑ ❑ ❑ •
Page 5 of 6
Permit: WQ0002056 Owner - Facility:Ade 794 LLC
Inspection Date: 05/18/2021 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Excessive solids buildup
Aerators/mixers
Effluent structure
Lagoon cover
❑ ❑ • ❑
❑ ❑ • ❑
Page 6 of 6