Loading...
HomeMy WebLinkAboutWQ0002056_Inspection_20210518Compliance Inspection Report Permit: WQ0002056 Effective: 05/04/20 SOC: Effective: County: Onslow Region: Wilmington Contact Person: Michael Smith Expiration: 06/30/26 Expiration: Title: Park Manager Owner : Ade 794 LLC Facility: Patriot Place MHP WWTF 145 Hubert Blvd Hubert NC 28539 Phone: 910-353-3433 Directions to Facility: Travel NC Hwy. 172 North through the MCB Camp Lejeune to the NC Hwy. 24 intersection. Go straight, and proceed approx. 0.25 miles to stop sign. Turn left on Hubert Boulevard (NCSR 1745), and travel approx. one mile. The WWTF is located on the right. System Classifications: SI, Primary ORC: Mikel Howard Seely Secondary ORC(s): On -Site Representative(s): Related Permits: Inspection Date: 05/18/2021 Primary Inspector: Geoff Kegley Secondary Inspector(s): Entry Time 01:OOPM Reason for Inspection: Routine Permit Inspection Type: Wastewater Irrigation Facility Status: Compliant ❑ Not Compliant Question Areas: ▪ Treatment Flow Measurement -Effluent ▪ Treatment Flow Measurement -Water Use Records ▪ Treatment Lagoons (See attachment summary) Certification: 1004691 Exit Time: 02:30PM Phone: 910-330-8011 Phone: Inspection Type: Compliance Evaluation ▪ Treatment Flow Measurement -Influent ▪ Treatment In End Use -Irrigation ▪ Miscellaneous Questions ▪ Record Keeping ▪ Treatment Flow Measurement Page 1 of 6 Permit: WQ0002056 Owner - Facility:Ade 794 LLC Inspection Date: 05/18/2021 Inspection Type : Compliance Evaluation Reason for Visit: Routine Inspection Summary: A routine compliance inspection of the Patriot Place Mobile Home Park WWTF was conducted on May 18, 2021. The purpose of the evaluation was to verify that the facility is operating in compliance with the conditions and limitations specified in Permit WQ0002056. Mike Seely-ORC and Jim Rowan -irrigation and maintenance staff were both present during the inspection. This facultative lagoon and irrigation system is permitted for 90,000gpd. Currently the flows are averaging approximately 20,000gpd. The 3 lagoons are hydraulically connected and the freeboard was 38 inches. Berms were maintained and had recently been mowed. Operational and maintenance records were well organized and the field was well maintained. There are 2 pump stations that are maintained by staff and they are visited daily and maintenance is documented. Please note that the Permittee is required to follow all requirements in 15A NCAC 02T . 0403 for deemed permitted collection systems. An Operator Designation form needs to be submitted to update the ORC and Backup ORC for this facility, a copy of this form was provided to the ORC during the inspection. The facility is compliant with Permit W00002056. Please review the comment section of the inspection report for more details. Page 2 of 6 Permit: WQ0002056 Owner - Facility:Ade 794 LLC Inspection Date: 05/18/2021 Inspection Type : Compliance Evaluation Reason for Visit: Routine Type Infiltration System Single Family Spray, LR Activated Sludge Spray, LR Activated Sludge Spray, HR Activated Sludge Drip, LR Recycle/Reuse Single Family Drip Reuse (Quality) Lagoon Spray, LR Treatment Are Treatment facilities consistent with those outlined in the current permit? Do all treatment units appear to be operational? (if no, note below.) Comment: Treatment Flow Measurement -Influent Is flowmeter calibrated annually? Is flowmeter operating properly? Does flowmeter monitor continuously? Does flowmeter record flow? Does flowmeter appear to monitor accurately? Comment: The flowmeter was calibrated on 4/30/2021 by Delta Systems. Treatment Flow Measurement -Water Use Records Is water use metered? Are the daily average values properly calculated? Comment: Treatment Flow Measurement -Effluent Is flowmeter calibrated annually? Is flowmeter operating properly? Does flowmeter monitor continuously? Does flowmeter record flow? Does flowmeter appear to monitor accurately? Comment: Record Keeping Is a copy of current permit available? Yes No NA NE • Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Yes No NA NE ❑ ❑ • ❑ Yes No NA NE ❑ ❑ • ❑ ❑ ❑ • ❑ Yes No NA NE • ❑ ❑ ❑ Page 3 of 6 Permit: WQ0002056 Owner - Facility:Ade 794 LLC Inspection Date: 05/18/2021 Inspection Type : Compliance Evaluation Reason for Visit: Routine Are monitoring reports present: NDMR? NDAR? Are flow rates less than of permitted flow? Are flow rates less than of permitted flow? Are application rates adhered to? Is GW monitoring being conducted, if required (GW-59s submitted)? Are all samples analyzed for all required parameters? Are there any 2L GW quality violations? Is GW-59A certification form completed for facility? Is effluent sampled for same parameters as GW? Do effluent concentrations exceed GW standards? Are annual soil reports available? # Are PAN records required? # Did last soil report indicate a need for lime? If so, has it been applied? Are operational logs present? Are lab sheets available for review? Do lab sheets support data reported on NDMR? Do lab sheets support data reported on GW-59s? Are Operational and Maintenance records present? Were Operational and Maintenance records complete? Has permittee been free of public complaints in last 12 months? Is a copy of the SOC readily available? No treatment units bypassed since last inspection? • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ • ❑ ❑ • ❑ ❑ ❑ ❑ ❑ ❑ • • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ ❑ • ❑ ❑ ❑ • Comment: Operational and maintenance records were well organized. EnviroChem is the contract lab performing the required analyses. End Use -Irrigation Are buffers adequate? Is the cover crop type specified in permit? Is the crop cover acceptable? Is the site condition adequate? Is the site free of runoff / ponding? Is the acreage specified in the permit being utilized? Is the application equipment present? Is the application equipment operational? Is the disposal field free of limiting slopes? Yes No NA NE • ❑ ❑ ❑ ❑ • ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Page 4 of 6 Permit: WQ0002056 Owner - Facility:Ade 794 LLC Inspection Date: 05/18/2021 Inspection Type : Compliance Evaluation Reason for Visit: Routine Is access restricted and/or signs posted during active site use? Are any supply wells within the CB? Are any supply wells within 250' of the CB? How close is the closest water supply well? Is municipal water available in the area? # Info only: Does the permit call for monitoring wells? Are GW monitoring wells located properly w/ respect to RB and CB? Are GW monitoring wells properly constructed, including screened interval? Are monitoring wells damaged? • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ • ❑ ❑ Comment: Groundwater monitoring records (GW-59s) for the last couple of years were reviewed and were consistently compliant. Monitoring wells are sealed with water tight caps and locked. The irrigation field was recently mowed and in good condition and irrigation was observed during the inspection. Every other row is irrigated at a time and then alternated for the next spray event. Application measurement is by pump run times. TREATMENT LAGOON 1 Treatment Lagoons Lagoon Type Primary/Secondary Influent structure Banks/berms (seepage and erosion) Vegetation (excessive vegetation on banks/berms) Liner Liner Type Baffles/curtains Freeboard Marker Required freeboard Actual freeboard Are increments clearly marked on gauge at adequate intervals? Has the water level gauge been surveyed w/ respect to lowest point on dike? wall? No Evidence of overflow Acceptable color Floating mats Yes No NA NE None Primary ❑ ❑ ❑ • 24 Inches 38 Inches • ❑ ❑ ❑ ❑ ❑ ❑ • Page 5 of 6 Permit: WQ0002056 Owner - Facility:Ade 794 LLC Inspection Date: 05/18/2021 Inspection Type : Compliance Evaluation Reason for Visit: Routine Excessive solids buildup Aerators/mixers Effluent structure Lagoon cover ❑ ❑ • ❑ ❑ ❑ • ❑ Page 6 of 6