June 12, 2017
Todd Clark, City Manager
City of Newton
P.0 Box 550
Newton, NC 28658
COOPER
Governor
MICHAEL S. REGAN
Secretary
S. JAY ZIMMERMAN
Director
Subject: Permit No. WQ0039273
City of Newton
Sewer Line Replacement Newton Conover High
School
Wastewater Collection System Extension Permit
Catawba County
Dear Mr. Clark:
In accordance with your application received June 9, 2017, we are forwarding herewith Permit No.
WQ0039273 dated June 12, 2017 to the City of Newton (Permittee) for the construction and operation
upon certification of the subject wastewater collection system extension. This permit shall be effective
from the date of issuance until rescinded and shall be subject to the conditions and limitations as specified
therein. This cover letter shall be considered a part of this permit and is therefore incorporated therein by
reference.
Please pay particular attention to the foil ov 'ing conditions contained within th
P
Condition II.1: This permit shall not be automatically transferable; a request must be made and approved.
Condition 11.4: Requires that the wastewater collection facilities be properly operated and maintained in
accordance with 15A NCAC 2T .0403 or any individual system -wide collection system
permit issued to the Permittee.
It shall be the responsibility of the Permittee to ensure that the as -constructed project meets the appropriate
design criteria and rules. Failure to comply may result in penalties in accordance with North Carolina
General Statute §143-215.6A through §143-215.6C, construction of additionalor replacement wastewater
collection facilities, and/or referral of the North Carolina -licensed Professional Engineer to the licensing
board.
State of North Carolina I Erna onmental Quality g Water Resources I Water Quality Regional. Operations
Mooresville Regional Office 1610 East Center Avenue, Suite 301 I Mooresville, North Carolina 3S115
704 663 1699
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the right' to
request an adjudicatory hearing upon written request within 30 days florin receipt of this permit. This
request must be in the form of a written petition, conforming to Chapter 15013 of North Carolina General
Statutes, and filed with the Office of Administrative Hearings, 6714 Mail Service Center, Raleigh, NC
27699-6714. Unless such demands are made, this permit shall be final and binding.
If you need additional information concerning this matter, please contact Ori Tuvia at (704) 235-2190 or
via e-mail at ori.tuviaraMcdenr.gov.
Sincerely,
by W. Core Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCHEQ
cc: Clarence Lockamy (P.E.) (E-copy)
Mooresville Regional Office Files
Water Resources Central Files
PERCS (E-copy)
Page 2 of 8
Environmental
Quality
STATE OF NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENTAL QUALITY
WASTEWATER COLLECTION SYSTEM EXTENSION PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General. Statutes of North
Carolina as amended, and other applicable Laws, Rules, and Regulations, permission is hereby
granted to the
City of Newton
Catawba County
for the construction and operation of approximately 622 linear feet of 8-inch gravity sewer, as
part of Sewer Line Replacement Newton Conover High School, and the discharge of 0 additional
gallons per day of collected wastewater into the City of Newton existing sewerage system,
pursuant to the application received June 9, 201.7, and in conformity with 15A NCAC 2T; the
Division's Gravity Sewer Minimum Design Criteria adopted February 12, 1996, as applicable;
the Division's Minimum. Design Criteria for the Fast -Track Permitting of Pump Stations and
Force Mains adopted June 1., 2000, as applicable; and other supporting data subsequently filed
and approved by the Department of Environment and Natural Resources and considered a part
of this permit.
This permit shall be effective from the date of issuan
the specified conditions and limitations contained therei
by W. Corey l asinger, Regional. Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
By authority of the Environmental Management Commission
Permit Number: WQ0439273
Permit Issued: June 12, 2017
cinded and shall be subject to
Page 3 of 8
SUPPLEMENT TO PERMIT COVER SHEET
City of Newton is hereby authorized to:
Construct, and then operate upon certification the aforementioned wastewater collection extension. The
sewage and wastewater collected by this system shall be treated in the City of Newton -Clark Creek
Wastewater Treatment Facility in accordance with Permit Number NC:0036196.
Permitting of this project does not constitute an acceptance of any part of the project that does not meet
1.5A NCAC 2T; the Division's Gravity Sewer Minimum Design Criteria adopted February 1.2, 1996, as
applicable; and the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations
and Force Mains adopted June 1., 2000, as applicable, unless specifically mentioned herein. Division
approval is based on acceptance of the certification provided by a North Carolina -licensed Professional
Engineer in the application. It shall be the Permittee's responsibility to ensure that the as -constructed
project meets the appropriate design criteria and rules.
Construction and operation is contingent upon compliance with the Standard Conditionsand any Special
Conditions identified below.,
. SPECIAL CONDITIONS
1) No flow in excess of the quantity permitted herein, 0 additional GPD, shall be made tributary to
the subject sewer system until an application for permit modification for an increase in flow has
been submitted to and approved by the Division, [15A NCAC 02T.0304 (b)].
II. STANDARD CONDITIONS
This permit is not transferable. In the event there is a desire for the wastewater collection facilities
to change ownership, or there is a name change of the Permittee, a formal permit request shall be
submitted to the Division accompanied by documentation from the parties involved, and other
supporting materials as may be appropriate. The approval of this request shall be considered on its
merits and may or may not be approved. [15A NCAC 02T.0104; G..S 143-215.1(d3)]
2. This permit shall become voidable unless the wastewater collection facilities are constructed in
accordance with the conditions of this permit; 15A NCAC 2T; the Division's Gravity Sewer
Minimum Design Criteria adopted February 12, 1996, as applicable; the Division's Minimum Design
Criteria for the Fast -Track Permitting of Purnp Stations and Force Mains adopted June 1, 2000, as
applicable; and other supporting materials unless specifically mentioned herein. [1.5A NCAC
02T.0110]
This permit shall be effective only with respect to the nature and volume of wastes described in the
application and other supporting data. [15A NCAC 02T .0110]
4. The wastewater collection facilities shall be properly maintained and operated at all times. The
Permittee shall maintain compliance with an individual system -wide collection system permit for the
operation and maintenance of these facilities as required by 15A NCAC 2T .0403. If an individual
permit is not required, the following performance criteria shall be met: [15A NCAC 02T .0108(b)1:
Page 4 of 8
a. ' The sewer system shall be effectively maintained and operated at all times to prevent discharge
to land or surface waters, and to prevent any contravention of groundwater standards or surface
water standards.
b. A map of the sewer system shall be developed and shall be actively maintained.
c. An operation and maintenance plan including pump station inspection frequency, preventative
maintenance schedule, spare parts inventory and overflow response has been developed and
implemented.
d. Pump stations that are not connected to a telemetry system shall be inspected every day (i.e. 365
days per year). Pump stations that are connected to a telemetry system shall be inspected at least
once per week.
e. High -priority sewer lines shall be inspected at least once per every six months and inspections
documented.
f A general observation of the entire sewer system shall be conducted at least once per year.
g. Overflows and bypasses shall be reported to the appropriate Division regional office in
accordance with 15A NCAC 2B .0506(a), and public notice shall be provided as required by
North Carolina General Statute §143-215.1C.
h. A Grease Control Program is in place as follows:
1. For public owned collection systems, the Grease Control Program shall include at least
biannual distribution of educational tnaterials for both commercial and residential users and
the legal means to require grease interceptors at existing establishments. The plan shall also
include legal means for inspections of the grease interceptors, enforcement for violators and
the legal means to control grease entering the system from other public and private satellite
sewer systems.
2. For privately owned collection systems, the Grease Control Program shall include at least bi-
annual distribution of grease education materials to users of the collection system by the
permittee or its representative.
3 Grease education materials shall be distributed more often than required in Parts (1) and (2)
of this Subparagraph if necessary to prevent grease -related sanitary sewer overflows.
i. Right-of-ways and easements shall be maintained in the full easement width for personnel and
equipment accessibility.
j. Documentation shall be kept for Subparagraphs (a) through (i) of this Rule for a minimum of
three years with exception of the map, which shall be maintained for the life of the system.
5. The Permittee shall report by telephone to a water resources staff member at the Mooresville Regional
Office, telephone number (704) 663-1699, as soon as possible, but in no case more than 24 hours
following the occurrence or first knowledge of the occurrence of either of the following:
a. Any process unit failure, due to known or unknown reasons, that renders the facility
incapable of adequate wastewater transport, such as mechanical or electrical failures of
pumps, line blockage or breakage, etc.; or
b. Any SSO and/or spill over 1,000 gallons; or
c. Any SSO and/or spill, regardless of volume, that reaches surface water
Page 5 of 8
Voice mail messages or faxed information is permissible, but this shall riot be considered as the initial
verbal report. Overflows and spills occurring outside normal business hours may also be reported to
the Division of Emergency Management at telephone number (800) 858-0368 or (919) 733-3300.
Persons reporting any of the above occurrences shall file a spill report by completing and submitting
Part 1 of Form CS-SSO (or the most current Division approved form) within five days following first
knowledge of the occurrence. This report must outline the actions taken or proposed to be taken to
ensure that the problem does not recur. Part 11 of Form CS-SSO (or the most current Division
approved form) can also be completed to show that the SSO was beyond control. [G.S. 143-
215.1C(a1)]
6, Construction of the gravity sewers, pump stations, and force mains shall be scheduled so as not to
interrupt service by the existing utilities nor result in an overflow or bypass discharge of wastewater
to the surface waters of the State. [15A NCAC 02T.0108(b)]
7, Upon completion of construction and prior to operation of these permitted facilities, the completed
Engineering Certification form attached to this permit shall be submitted with the required supporting
documents to the address provided on the form. A complete certification is one where the form is
fully executed and the supporting documents are provided as applicable. Any wastewater flow made
tributary to the wastewater collection system extension prior to completion of this Engineer's
Certification shall be considered a violation of the permit and shall subject the Permittee to
appropriate enforcement actions.
If the permit is issued to a private entity with an Operational Agreement, then a copy of the
Articles of Incorporation, Declarations/Covenants/Restrictions, and Bylaws that have been
appropriately filed with the applicable County's Register of Deeds office shall be submitted
with the certification.
A complete certification is one where the form is fully,executed and the supporting documents are
provided as applicable. Supporting documentation shall include the following:
a. One copy of the project construction record drawings (plan & profile views of sewer lines &
force mains) of the wastewater collection system extension. Final record drawings should be
clear on the plans or on digital media (CD or DVD disk) and are defined as the design drawings
that are marked up or annotated with after construction. information and show required buffers,
separation distances, material changes, etc,
b. One copy of the supporting applicable design calculations including pipe and pump sizing,
velocity', pump cycle times, and level control settings, pump station buoyancy, wet well storage,
surge protection, detention time in the wet well, and force main, ability to flush low points in
force mains with a pump cycle, and downstream sewer capacity analysis. If a portable power
source or pump is dedicated to multiple stations, an evaluation of all the pump stations' storage
capacities and the rotation schedule of the portable power source or pump, include travel
timeframes, shall be provided.
c. Changes to the project that do not result in non-compliance with this pet r iit, regulations, or the
Minimum Design Criteria should be clearly identified on the record drawings, on the certification
in the space provided, or in written summary form.
Prior to Certification (Final or Partial): Permit modifications are required for any changes resulting
in non-compliance with this permit (including pipe length increases of 10% or greater, increased
flow, pump station design capacity design increases of 5% or greater, and increases i.n the
number/type of connections), regulations, or the Minimum Design Criteria. Requested modifications
Page 6 of 8
or VarianOs to the Minimum Design Criteria will be reviewed on a case -by -case basis and each on
its own merit. Please note that variances to the Minimum Design Criteria should be requested and
approved during the permitting process prior to construction. After -construction requests are
discouraged by the Division and may not be approved, thus requiring replacement or repair prior to
certification & activation. [15A NCAC 02T .0116]
8, Gravity sewers installed greater than ten percent below the minimum required slope per the Division's
Gravity Sewer Minimum Design Criteria shall not be acceptable and shall not be certified until
corrected. If there is an unforeseen obstacle in the field where all viable solutions have been
examined, a slope variance can be requested from the Division with firm supporting documentation.
This shall be done through a permit modification with fee. Such variance requests will be evaluated
on a case -by -case basis. Resolution of such request shall be evident prior to completing and
submitting the construction certification. [ 15A NCAC 021..0105(0j
9, A copy of the construction record drawings shall be maintained on file by the Permittee for the life
of the wastewater collection facilities. [15A NCAC 02T .0116]
10. Failure to abide by the conditions and limitations contained in this permit; 15A NCAC 2T; the
Division's Gravity Sewer Design Criteria adopted February 12, 1996, as applicable; the Division's
Minimum Design Criteria for the Fast -Track Permitting of Pump Station and Force Mains adopted
June 1, 2000, as applicable; and other supporting materials may subject the Permittee to an
enforcement action by the Division, in accordance with North Carolina General Statutes §143-215.6A
through §143-215.6C, construction of additional or replacement wastewater collection facilities,
and/or referral of the North Carolina -licensed Professional Engineer to the licensing board, [15A
NCAC 02T .0104; 15A NCAC 02T .0108(b-c)]
11. In the event that the wastewater collection facilities fail to perform satisfactorily„ including the
creation of nuisance conditions, the Permittee shall take immediate corrective action, including those
as may be required by this Division, such as the construction of additional or replacement facilities.
[15A NCAC 02T .0110; 15A NCAC 02T .0108(b)]
12. The issuance of this permit shall not exempt the Permittee from complying with any and all statutes,
rules, regulations, or ordinances that may be imposed by the Division any other Federal, State, or
Local government agencies which have jurisdiction or obtaining other permits which maybe required
by the Division or any other Federal, State, of Local government agencies. [G.S. 143-215.1(b)]
Page 7 of 8
FAST TRACK SEWER ENGINEERING C
R
FICATION
PERMITTEE: CITY OF HICKORY
PERMIT #: WQ0039273
PROJECT: SEWER LINE REPLACEMENT NEWTON CONOVER HIGH SCHOOL
ISSUE DATE: JUNE 12, 2017
This project shall not be considered complete nor allowed to operate in accordance with standard
Condition 7 of this permit until the Division has received this Certification and all required supporting
documentation. It should be submitted in a manner that documents the Division's receipt. Send the
required documentation to the Regional Supervisor, Water Quality Regional Operations Section at the
address noted in the page footer.
Any wastewater flow made tributary to the wastewater collection system extension prior to completion
of this Certification shall be considered a violation of the permit and shall subject the Permittee to
appropriate enforcement actions. The Permittee is responsible for tracking all partial certifications up
until a final certification is received by the Division. A Final Certification shall be a complete set of
record drawings and design calculations regardless of whether partials have been submitted.
PERMITTEE'S CERTIFICATION
I, the undersigned agent for the Permittee, hereby state that this project has been constructed pursuant to
the applicable standards & requirements, the Professional Engineer below has provided applicable
design/construction information to the Permittee, and the Permittee is prepared to operate & maintain the
wastewater collection system permitted herein or portions thereof.
Printed Name, Title
Signature Date
ENGINEER'S CERTIFICATION
, as a duly registered Professional En neer in the State of North Carolina,
having been authorized to observe (0 periodically, E weekly, U full time) the construction of the
project name and location as referenced above for the above Permittee hereby state that, to the best of my
abilities, due care and diligence was used in the observation of the construction such that the construction
was observed to be built within substantial compliance of this permit; 15A NCAC 02T; the Division of
Water Resources' (Division) Gravity Sewer Minimum Design Criteria adopted February 12, 1996, as
applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and
Force Mains adopted June 1, 2000, as applicable; and other supporting materials.
North Carolina Professional Engineer's Seal w/signature & date:
E Final
El Partial (include description)
Certification Comments/Qualifiers (attach if necessary):
NC DWR — Water Quality Regional Operations Section 610 East Center Avenue, Suite 301, Mooresville, NC 28115
Mooresville Regional Office Phone: {704) 663-1699 FAX: (704)-633-6040
THE
WOOTEN
COMPANY
1430 6 Old Lenoir Road NW
Hickory, NC 28601
828.322.5533
Fax 828.322.5242
June 7, 2017
Mr. Ori Tuvia
N.C. Division of Water Quality
Mooresville Regional Office
610 E. Center Avenue
Mooresville„ NC 28115
RE:
Application for Gravity Sewers, Pump Stations, and Force Mains for:
Sanitary Sewer. Extension
Sewer Line Replacement - Newton Conover High School
Newton, NC
TWC Project No.: 3095-AS
Mr. Tuvia:
Thank you for speaking with me on Wednesday regarding the sewer line
replacement project in Newton. As 1 mentioned, an existing clay sewer line that
was installed almost 90 years ago has collapsed and is in need of repairs. The
City has decided that it is best to reinstall this line and re-route it away from its
current location beneath the stadium seating at the Newton/Conover High School.
Therefore, on behalf of the City of Newton, we are sending you the following
documents for your review and approval for the above -referenced project:
One (1) original and one (1) copy of the FTA 04-16 pen it application w/
appendices;
o A ®- Cover Letter
• B - Application Form (FTA 04-16)
c C - Application Fee
• D - Project Narrative
c E - Flow Tracking/Acceptance Form (FTSE 04-16)
• F - Site Maps
a G - Existing Permit - (N/A - Not Included)
• H - Power Reliability Plan --- (N/A - Not Included)
c 1 _ Certificate of Public Convenience/Necessity - (N/A -- Not Included)
• J .- Operational Agreements (N/A - Not Included)
One (1) check for $480.00 made payable to NCDEQ;
This project replaces approximately 600 L.F. of an existing, failing sewer line.
No new services are to be connected thus there will be no increase in wastewater
flow as a result of this project.
Sewer 1 inc Re l eernent
City, of` Newton, N
Page 2 of2
The City is currently by -pas.. pumping the waste Hato around the collapsed
section of pipe and securing a qualified contractor to install the line. They will
begin construction on the replacement lime as soon as approval is ee °d from
your office..
l t t the above in anon is sufficient fear your refiie ; however, if you should
have any questions or require additional in.ft anon„ please do not hesitate to
contact us.
Best Regards,
THE WOOTEN COMPANY
1a
nee 1
ckarny, P.
Enclosures: As noted above
co: Dusty Wentz, Director o Public Works and Utilities, City of Claremont
TWC File.
Dtvsion of Water Resources
State of North Carolina
Department of Environmental Quality
Division of Water Resources
15A NCAC 02T .0300 — FAST TRACK SEWER SYSTEM EXTENSION APPLICATION
FTA 04-16 & SUPPORTING DOCUMENTATION
Application Number: (12 73o be completed by DWR)
Al! items ust be completed or the application will be returned
APPLICANT INFORMATION:
1. Applicant's name: City of Newton (company, municipality, HOA, utility, etc.)
?. Applicant type: 11 lndividual LJ Corporation El General Partnership LJ Privat y-Owned Public Utility
0 Federal 0 State/County Municipal 0 Other
3. Signature authority's name: Todd Clark per 15A NCAC 02T,,,1)1(16(b)
Title: City Manager
4. .Applicant's mailing address: P.O. Box 550
City; Newton State: NC Zip: 28658-
5. Applicant's contact information:
Phone number: (82) 695-4259 Email Address: tcIarknewtonncgoy
11. PROJECT INFORMATION:
I. Project name: Sewer Line Replacement - Newton Conover High School
Application/Project status:
Proposed (New Permit) 0 Existing 'Permit/Project
If a modification, provide the existing permit number; WQOO and issued date:
If new construction but part of a master plan, provide the existing permit number: WQOO,,
3, County where project is located; Catawba
4. Approximate Coordinates (Decimal Degrees): Latitude: 35.680' Longitude: -81..223''
5. Parcel ID (if applicable): 373008990557
(or Parcel ID to closest downstream sewer)
111, CONSULTANT INFORMATION:
I. Professional Engineer: Clarence M. Lockanv, PE
Firrn: The Wooten Company
Mailing address: 1430-B Old Lenoir Road
City: Newton State: NC Zip: 28601-
Phone number: (828) 322-5533 Email Address: clockamyikthewoote, company.com
License 'Number: 9297
IV. WASTEWATER TREATMENT FACILITY (WWTF) INFORMATION:
1. Facility Name: Clark Creek WWTP Permit Number: NC 0036196
Owner Name: City of Newton
V. RECEIVING DOWNSTREAM SEWER INFORMATION (if different than WWTF):
I, Permit Nurnber(s): WQ
Downstream (Receiving) Sewer Size: inch
System Wide Collection System Permit Nand:wits) (if ap_plicablej: WQCS000444
Owner Name(s): City of _Newton
FORM: FTA 04-16 Page 1 of 5
GENERAL REQUIREMENTS
I. lithe Applicant is a Privately -Owned Public Utility, has a Certificate of Public Convenience and Necessity been
0 Yes 0No ZNA
2. lithe Applicant is a Developer of lots to be sold, has a Dcyclopet's .:„lperittloriaAgreeinent (PAM, DiA) been attached?
0 Yes []No EN/A
3. If the Applicant is a 1 tome'Property ners' Association. Ims all Operational Agreementif ORM. HOA) been attached?
E) Yes 0No ZNA
4. Origin of wastewater: (check all that apply):
Residential Owned
0 Residential Leased
0 School preschool / day care
0 Food and drink facilities
0 Businesses / offices / factories.
0 Retail (stores, centers, malls)
Z Retail with food preparationlservice
Ej Medical dental veterinary facilities
Church
LI Nursing Home
Nature of Wastewater : 100 °,4 Domestic/Commercial _9/0 Commercial
°,/ii industrial (See 15A NCAC 02T .0103(0.1)
Is there a Pretreatment Program in effect?
Yes E No
6. Has a flow: reduction been approved under I 5A NCAC 02T 01 144)?
If Yes, Provide a co,p of flow reductio oval letter
7. Summarize wastewater generated by project:
Establishment Type (see 02T.0114(fl)
Replacement Project - NO NEW FLOW
.ached?
Ej Car Wash
0 Hotel andlor Motels
El Swimming Pool /Clubhouse
LIi swimmina Pool/Filter Backwash
E Other (Explain in Attachment)
Yes El No
Daily Design Flow No. of Units
gal!
galgal
gat
Total GPD
See t 5A N('...,NC 02T ,01141.bhAt),10(1): and Le1t2t to caveats to wa.stewater design flow rates (i.e,, minimum flow per
dwelling; proposed unknown non-residential development uses: public access facilities located near high public use
areas; and residential .propert) located south or east of the Atlantic Intracoastal Waterway to be used as vacation rentals
as defined in
Per 15A NCAC 021 .0114(c), design flow rates for establishments not identified [in table OA NCAclitt2IFJT1 141 shall
be determined using available flow data, water using fixtures, occupancy or operation patterns, and other measured data.
8. Wastewater generated by project: 0 GPD (per 15.A NCAC 02T .01 I. 4)
Do not include future flows or previously permitted allocations
lfpenTlitled flow is zero, indicate why:
0 Pump Station or Gravity Sewer where flow: will be permitted in subsequent permits that connect to this line
0 Flow has already been allocated in Permit Number,
E Rehabilitation or replacement of .existing sewer with no new flow expected
0 Other (Explain):
Page 2 of 5
roum: 1TA 04-16
Vil. GRAVITY SEWER DESIGN CRITERIA (If Applicable) - 02T .0305 & ,M DC (Gravity Sewtis1:
1. Summarize gravity sewer to be permitted.:
Size (inches)
8
Length (feet)
Material
622
PVC-SDR 21
Section 11 & 111 of the MDC for Permitting of Gravity Sewers contains .information related to design criteria
Section III contains information related to minimum slopes for gravity sewer(s)
Oversizing lines to meet minimum slope requirement is not allowed and a violation of the MDC
VIII. PUMP STATION DESIGN CRITERIA (if Applicable) — 02T .0305 & MDC (Pump Stations/ForceMains:
COMPLETE FOR EACH PUMP STATION INCLUDED IN THIS PROJECT
1. Pump station number or name: N/A
2 Approximate Coordinates (Decimal Degrees): Latitude: . Longitude: -
3, Design flow of the pump station: millions gallons per day (firm capacity)
4. Operational point(s) of the pump(s): gallons per minute at feet total dynamic head (TDH)
5. Summarizethe force main to be permitted. (for this Pump Station):
Size (inches)
Length (feet) Material
6. Power reliability in accordance with 15Al_ CAC„02„1,L))105111)(1):
El Standby power source or pump with automatic activation and telemetry - 15A NCAC 02T .030.5(h)(1)(13):
Required for all pump stations with an average daily flow greater than or equal to 15,000 gallons per day
Must be permanent to facility
Or if the pump station has an average daily flow less than 15,000 gallons per day:
El Portable power source with manual activation, quick -connection receptacle and telemetry - 1 5A NCAC 02T
.0305(h)(1)(C)
or
El Portable pumping unit with plugged emergency pump connection and telemetry - 15A NCAC 02T .0305(h)(1)(C):
It shall be demonstrated to the Division that the portable source is owned or contracted by the applicant (draft agreement)
and is compatible with the station.
If the portable power source or pump is dedicated to multiple pump stations, an evaluation of all the pump stations'
storage capacities and the rotation schedule of the portable power source or pump. including travel timeframes, shall be
provided in the case of a multiple station power outage.
FORM: FTA 04- I.6 Page 3 of 5
PP. Pr
I. Does the project comply with all separations found ink.5A 0.31,0305(B &(g)
. SETBACKS & SEPARATIONS — (02B .0200 & 15,4 NCAC 02T .0305(t)):
/ 15A NCAC 02T.0305(f) contains minimum separations that shall be provided for se v yste
Setback Parameter*
Storm sewers and other utilities not listed below (vertical)
ater mains (vertical -water over sewer including in benched tren
ater mains (horizontal)
Reclaimed water lines (vertical - reclaimed over sewer)
Reclaimed water lines (horizontal reclaimed over sewer)
**Any private or public water supply source, including any: was, WS-I waters of Class 1 o
Class 11 impounded reservoirs used as a ourceofdkinter
e
**Waters classified WS (except WS-I or WS-V), B, SA, ORW, FIQW, or SB from normal
high water (or tide elevation) and wetlands (see item IX..2)
**Any other stream, lake, impoundment, or ground water lowering and surface drainage
ditches
Anv buildino foundation
Any basement
Top slope of embankment or cuts of 2 t'eetor more vertical heigl
Drainage: systems and interceptor drams
Any swimming .pools
L Final earth grade (vertical)
Se aration Re
24 inches
18 inches
Yes LI No
10 feet
18 inches
2 feet
1006
10 feet
5 feet
feet
5 feet
10 feet
36 inches
I5A NCAC 02T.0305(z) contains alternatives where separations On 021/0305(t) cannot be achieved.
**Stream classifications can be identified using the Division's NC Surface Water Classifications ‘veficiage
If noncompliance with 02/t09L(1) or/(()/,„ see Section X of this application
2.. Does the project comply with separation requirements for wetlands? (50 feet of separation) LI Yes Eli No
r See the Division's draft separation requirements for situations vhere separation cannot be meet,
No variance is required if the alternative design criteria specified is utilized in design and construction
;(- As built documents should reference the location of areas effected
3. Does the project comply with setbacks found in the river basin rules per I5A NC.4' 02 B .0200?
'This would include Trout Buffered Streams per I5A NC/\„C' 213.0202
4. Does the project require coveragelauthorization under a 404 Nationwide or
individual permits or 401 Water Quality Certifications?
:;•(- Information can be obtained from the 401 & Buffer Permittingflranch
N/A
No N/A
Yes No
5. Does project comply with 15A Nt. AC 021,0105(c16) (additional permitslcertifications)? Yes U No
Per 15A NCTA(.:/..0:2: r,Q1951016), directly related environmental permits or certification applications are being prepared, have
been applied for. or have been obtained, Issuance of this permit is contingent on issuance of dependent permits (erosion and
sedimentation control plans, stormwater management plans, etc.).
6. Does this project include any sewer collection lines that are deemed, "high -priority?"
Per 1„.,SA.,IN(22,!:,,C jarP4/02, "high -priority sewer" means "any aerial sewer, sewer contacting surface waters, siphon, or sewer
positioned parallel to streambanks that is subject to erosion that undermines or deteriorates the sewer.
LI Yes Z No Z NIA
If yes, include an attachment with details for each line, including type (aerial line, size, material, and locanon)
High priority lines shall be inspected by the permittee or its representative at least once every six -months and
inspections documented. per 15A NCAC 02T.0403(a)(5) or the perinitee's individual System -Wide Collection permit.
FORM: ETA 04-16 Page 4 of 5
r
ERTIFICATIONS:
Does the submitted system comply with 15A NciAci02I, the Minimum Desion Criteria for the Permittiu& of Punix Stations
andtotice Mains (latest version), and the Gravity Sewer Minimum Design Criteria (latest version.) as applicable?
Yes
E] No
If No, complete and submit the Variance Alternative Design Request application (VADC 10-14) and supporting documents
for review. Approval of the request is required prior to submittal of the Fast Track Application and supporting
documents.
Professional Engineer's Certification:
attestatiesi that this application for
(Professional Engineer's name from Application item 111.1.)
has been reviewed by me and is accurate, complete and consistent with the information supplied in the plans, specifications,
engineering calculations, and all other supporting documentation to the best of my knowledge. 1 further attest that to the best
of my knowledge the proposed design has been prepared in accordance with the applicable regulations, Gravity Sewer
Minimum Design Criteria for Gravity Sewers (latest version), and the Minimum Design Criteria for the Fast -Track
Permitting of Pump Stations and Force Mains (latest version). Although other professionals may have developed certain
portions of this submittal package, inclusion of these materials under my signature and seal signifies that 1 ha.ve reviewed this
material and have judged it to be consistent with the proposed design.
NOTE ----- In accordance with General Statutes 143-215.6.A and 143-215.6B, any person who knowingly makes any false
statement, representation, or certification in any application package shall he guilty of a Class 2 misdemeanor, which may
include a fine not to exceed $1.0,000, as well as civil penalties up to S25,000 per violation.
North Carolina Professional Engineer's seal, signature, and date:
3. Applicant's Certification per 15A NC.AC 021 0106(b)
c• r
let attest that this application for
(Signature Authorft,y's name & titic from A lication Item 1,3.)
has been reviewed by rite and is accurate and complete to the best of my knowledge,. 1. 'understand that if all required parts of
this .application are notcompleted and that if all required supporting documentation and attachments are not included, this
application package is subject to being returned as incomplete. I understand that any discharge of wastewater from this non -
discharge system to surface waters or the land will result in an immediate enforce-ment action that may include civil penalties,
injunctive relief, and/or criminal prosecution, 1 will make no claim against the Division of Water Resources should a
condition of this permit be violated. 1 also understand that Wall required parts of this application package are not completed.
and that if all required supporting information and attachments are not included, this application package will he returned to
me as incomplete,
NOTE — In accordance with General Statutes 135,62..-N and 143-215.6B„ any person 1,VIto knowingly makes any false
stateinent, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may
include a time not to exceed $10,000 as well as civil penalties up to S25,000 per violation,
FORM: Et A 04-16
Page 5 of
Project Narrative
for the
Sewer Line Replacement
Newton -Conover High School
City of Newton
Catawba County, North Carolina
JUNE 2017
Prepared By:
THE WOOTEN COMPANY
1430E Old Lenoir Road
Hickory, NC 28601
License No. F-0115
A.
DESCRIPTION
F PROJECT
PurooselLocat on of Project
The City of Newton owns and maintains an existing 8-inch gravity sewer collection line. which crosses the
Newton -Conover High School property on N, Ashe Avenue (A street map is included to show the
location), The line is a clay pipe that was installed around 1930, The line crosses beneath the football field
bleachers and the school's running track. The line also runs within a few feet of the base of an 80 feet tall
field lighting pole.
A portion of the line has collapsed and repairs are needed immediately. Due to the age, condition and
location of the existing 'Pine the City wishes to replace the line rather than rehabilitate through the us of a
CIPP liner or other means. Instead a new line is to be installed to by-pass the football field and lights.
TYPE OF DEVELOPMENT
Proposed Project
The proposed replacement sewer will consist of the following ite
• -623 LF of 8-inch PVC SDR-21.gravity sewer,
• Remova.l and replacement of an existing brick manhole;
• 1 new, additional precast concrete sewer manhole;
• Connection of one existing sewer service to the new line;
• Connection of the new 8-inch gravity sewer to an existing sewer manhole by means of
an inside drop structure;
• Abandoning the existing gravity line by means of billing it with flowable concrete fill;
• Associated appurtenances and site work;
sect is essentially a maintenance project which. will generate no new wastewa
Treatment
Wastewater collected frog
Newton's Clark Creek WWTP„ The
to the City'.s treatment facility.
is now and will continue to be treated at the City of
ct will not include any im:provem.ents or direct impacts
Sewer Line Replacement — Newton/Conover High School
Newton, NC
June 2017
State of North Carolina
Department of Environmental Quality
Division of Water Resources
Tracking/Acceptance for Sewer Extension Applications
iorkision 4z0- Water ilescqtycc-i;.
(IFTSE 04-16)
Entity Requesting Allocation: City of Newton
Project Name for which flow is being requested: Sewer Line Replace. N/C High School.
Afore than one FTSE may he required,fOr a single proft,Tt tithe owner of the WWTP is not roponsible,lr all pump
.stations along the route of the proposed lvastewater flow,
.1. Complete this section only if you. are the owner of the wastewater treatment plant.
a. WVITP 'Facility Name: ClarkCreek WWTP
b. WW-FP Facility Permit #: NC 00361%
c. WW-FP facility's -permitted flow
Allflows are in MGD
5,0
d. Estimated obligated flow not yet tributary to the WWTP 0
e. WWTP facility's actual avg„ flow
f, Total flow for this specific request
g. Total actual and obligated flows to the facility
h. Percent of permitted flow used.
2.1
0,0
2,1
42%
11. Complete this section for each pump station you are responsible for along the route of this
proposed wastewater flow,
List pump stations located between the project connection point and
Pump
Station
(Name or
Number)
N/A
Firm
Capacity,
MGD
(A)
Design
Average Daily
Flow**
(Firm / pt),
MGD
Approx,
Current Avg,
Daily Flow,
MGD
(B) (C)
Obligated,
Not Vet
Tributary
Daily Flow,
MGD
the WWII):
MHO -EC) (E)=(A-D)
Total Current
Flow Plus
Obligated
Flow
* The Firm Capacity of any pump station is defined as the maximum pumped . o
can be achieved with the largest pump taken out of service.
** Design Average Daily Flowis the firm capacity of the pump station divided by a peaking
factor (pt) not less than .2.5.
*** A Planning Assessment Addendum shall be attached for each pump station located
between the project connection point and the WIVTP where the Available Capacity is < O.
Available
Capacity***
Downstream Facility Name (Seer): City of Newton
Downstream Permit Number: WQCS 000444
that
Page 1 (-4'6
1 [SF 04-16
cation
the voll
receiving
certify tc the best . knowledge that the addition of
n be pe -titted in this project has been evaluated along the route to the
Trent facility and that the flow from this project is not anticipated to
cause any capacity related sanitary seer overflows or overburden any downstream pump station
en route to the receiving treatment plant under nor°r al circumstancesgiven the irnplet .tentation
of the planned improvements identified in the planning assessment rrthere applicable. This
analysis has been performed in accordance with Meal established policies and procedures using
the best available data. This certification applies to those items listed above in Sections I and 1:I
plus all attached planning assessment addendums for wihich 1 rtrrr the responsible party.
Signature cif this than indicates acc ptanc cif this wastewater ater flow.,
ng latsitre
Pat
Legend
nom Proposed 8" Gravity
- Existing 6" to 1 a" Gravity
Existing 12" Gravity
CITY OF NEWTON
SEWER LINE REPLACEMENT
NEWTON-CONOVER HIGH SCHOOL
CATAWBA COUNTY
JUNE 2017
QUAD No. 035081 F2
Feet
800
T! IF WOOTEN COMPANY
CATA A Geospatial
Inforrnation Services
Real Estate Search
1 in=400ft
Parcel: 373008990557, 338 W 15TH ST NEWTON, 28658
Owners: NEWTON CONOVER CITY SCHOOL BOARD OF EDUCATION,
Owner Address: 605 N ASHE AVE
Values - Building(s): $8,362,300, Land: $549,400, Total: $8,911,700
This rnaplreport product was prepared from the Catawba County, NC Geospatial Information Services. Catawba County has made substantial efforts
to ensure the accuracy of location and labeling information contained on this map or data on this report. Catawba County promotes and recommends
the independent verification of any data contained on this map/report product by the user. The County of Catawba, its employees. agents, and
personnel, disclaim, and shall not be held liable for any and all damages, Voss or liability, whether direct, indirect or consequential which arises or may
arise from this map/report product or the use thereof by any person or entity.
Copyright 20t4 Catawba County NC
G6/07/2017
Perms Number
003927'3
Central Files: APS SWP
6/9/2017
Tracking Slip
Progra
Non (i
Perms Type
Gravity Sewer Extension, Pump Stations. & Pressure Se r Extensions
Primary Reviewer
oratuvla
Coastal SVVRale
Permitted Row
0
I"acda
statue
n review
Version
A
Project Type
New Project
Permit lass'
Individual
carton
Facility Name
Sewer Line Replacement Newton/ novel- High School
Location Address
Faculty Contact Aation
Region
Mooresville
County
Catawba
Owner Name
City of Newton
Dot EVE
nts
ryrig Issue
6/12/2017
App Received Draft Initiated
6/9/2017
Re-utia#ed Activities
Food ptreparatian, other
Retail
Bola
Sttbdtvssitan
Wastewater I cam)
+'aterbody Name
SchedUled
Issuance
Pub' tr N
Owner Type
Government - Mon
Owner Affiliation
E Todd Clark
City Manager
PO Box 550
Newton
jpal
lr ue Effective
6/12/2017 6l12/2017
Regaa rt n 1Receivett Events,
NC
Expiration
Additi al information requested
Additua nal lnfrrrnatton re' €wd
Streattattadex Number tastrera C
Water Res°
ENVIRONMENTAL. QUA(m.@T'"
July 31, 2017
Todd Clark, City Manager
City of Newton
P.O Box 550
Newton, NC 28658
SUBJECT: Partail Engineering Certification Acknowledgement
Sewer Line Replacement Newton Conover High School
Permit No. WQ0039273
Perrnitee: City of Newton
County: Catawba
Dear Mr. Clark:
ROY COOPER.
Governor
AU, S. REGAN
Se retary+
S. JAY ZIMMERMAN
Director
The Division of Water Resource's Mooresville Regional Office received the final engineering
certification with record drawings for the subject sewer extension project on 7/31/2017. Enclosed
is a certification page for your records. A full review of the certification materials may or may not
be conducted. It is assumed that receipt of this certification indicates compliance with all
regulations, design criteria and the permit. However, if a full technical review is conducted, you
will be notified of any items of non-compliance.
Please be reminded that the Permittee is responsible for keeping a copy of the final record drawings
for the life of the project. If you have not received such copy from your consultant, please contact
them immediately to obtain a copy.
Lastly, you are receiving this letter because the Division has you listed as the responsible party. If
this permitted system is no longer owned by you or your company, please complete Form PNOCF
since the permit is not automatically transferable, Form PNOCF can be downloaded from
http://portal.nccienr.org/web/wgiswwp/ps/cs/pnoc from the Collection Systems Applications page.
Should you have any questions, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at
ori.tuvia(ncdenr.gov.
Sincerely,
Ori Tuvia, nvironrnentarEngineer
Mooresville Regional Office
Division of Water Resources, DEQ
cc: Mr. Slade Harvin P.E. E-copy)
Central Files
MRO
State of North Carolina Eavironr nta Quaiit ', ti1 ater Resources
610 E. Center Avenue, Suite 301, Moores e NC 28115
Phone: 704663-16991Internet; wwvw.nctianr.gc3v
FASTTRA '' Sl ll lN)NIEIER.fNG CERilflt AT
PERMITTEE: CITY OF itnefifilt' t) TO
PERMIT #: WQ0039273
PROJECT: SEWER LINE REPLACEMENT N
ISSUE DATE: JUNE 12, 2017
TON CONOVER HIGH SCI IO L
This project shall not be considered complete nor allowed to operate in accordance with standard
Condition 'i of this permit until the Division has received this Certification and all required supporting
documentation, It should be submittedin a manner that documents the Division's receipt. Send the
required documentation to the Regional Supervisor, Water Quality Regional Operations Section at the
address noted in the page footer.
Any wastewater flow made tributary to the wastewater collectton system extension prior to completion
of this Certification shall be considered a violation of tfte permit and shall subject the Permittee to
appropriate enforcement actions. The Permittee is responsible for tracking all partial certifications up
until a final certification is received by the Division. A Final Certification shall be a complete set of
record drawings and design calculations regardless of whether partials have been submitted.
PRMIT'rEE's CERTIFICATION
1, the undersigned agent fot'the Permittee, hereby state that this project has been constructed pursuant to
the applicable standards & requirements, the Professional Engineer below has provided applicable
design/construction information to the Permittee, and the Permittee is prepared to operate & maintain the
wastewater collection systertt permitted herein orrtio
raga ael.116
Iced Name, Title
MAIN
ec
ENGINEER'S CERTIFICATION
as a duly registeredProfessional Et sneer in t State of North Carolina,
having been authorised to observe ( periodically, El weekly, U full time) the construction of the
project name and location as referenced above for the above Permittee hereby state that, to the best of my
abilities, due care and diligence was used in the observation of the construction such that the construction
was observed to be built within substantial compliance of this permit; 1 SA NCAC 02T; the Division of
Water Resources' (Division) Gravity Sewer Minimum Design Criteria adopted. February 12, 1996, as
applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and
Force Mains adopted June 1, 2000, as applicable; and other supporting materials,
North Candirsa Professional Engineers Seal w/signature & date:
[] Final Ej Partial (Include description)
Certification ComenentslQu
7a'iR7wAt_ C1-rt.7sFZc4-77car+
444113 t f 7r1 L [ x r'i
7� 1Z4. Pal vvE
fnec
7�CGv4�r�� Tt-i't
Fca
"^t4,vAr /p
F-/rz-cou4$4 ►.' I SE4a11.r
Tit 13''pAsS }j,.I?2PP/4, A Fir.-.c76 CS(2.7 Z. -E.d4I of,
7tcWtzri prtaw x c anti, lit S`-31-3 x.re c.A.Ct ,cas.c.
NC OWR -- Water Quality Regional Operations Sectt+arr 610 East Center Avenue, Suite 301, MooresvPle, NC 7S115
tvloaresviile Re anal Office Phone; (704) 663-1699 FAX: (704),633-6O40
ROY COOPER
Governor
MICHAEL S. REGAN
Secretory
Water Resoury„:es
S. JAY ZIMMERMAN
Director
As built check list (reference 2T .0300)
Reviewed By: Ori Tuvia
Review Date: 7/31/2017
Project Name: Sewer Line Replacement Newton Conove Pa a
WQ#: WQ0039273
1) As -built has been signed, sealed, and dated by an N,C. PE Yes [1:No
2) Adequate infortnation related to sewer lines :
Note that per the 2T and MDC, there is a minimum 8" for public gravity or minimum 6" for
private gravity, Three (3) feet minimum cover shall be provided for all sewers unless ferrous
material pipe is specified. Manholes shall be installed: at the end of each line, at all changes in
grade, size, or alignment, at all intersections, and at distances not greater than 425 feet, minimum
diameter of manholes shall be 4 feet (48 inches). Yes Nor—IN/A
Proper cleaning capabilities was verified (see email)
3) Adequate information related to pump stations:
Ensure power reliability option is selected (15A NCAC 02T.0305(h)). P Yes 111 No E N/A
4) Is Project design is in accordance with (see section B.13 of FTA 12-12)
15A NCAC 02T Gravity Sewer Minimum Design Criteria (latest version) Minimum Design
Criteria for Permitting of Pump Stations and Force Mains (latest version), Yes No N/A
If no, a variance approval is required per the requirements of I5A NCAC 02T.0105(b)
Applicant must submit TWO copies of the plans, specifications, and calculations
Contact the Central Office to discuss the variance request to determine a course of action.
The central office will review the variance request, and if approvable, specific language
regarding the variance will be forwarded to the Regional Office reviewer to incorporate into the
permit. A copy of the variance letter (or email correspondence) should be kept with the
application file.
5) Project contains high priority lines (I 5A NCAC 02T .0402(2)) E Yes No
If Yes, insure that the permit contains the necessary condition related to high priority lines 15A
NCAC 02T.0403 (a)(5)
6) Is the Sewer As -built length within 10% of the fast track applied Length?
( I Original length of pipe — As built length I / Original length) < 10%.
If no application need to be modified
Yes —I No
State of North Carolina I Environmental Quality Water Re,5Qurces !Water Quality Regional Operations
Mooresville Reonal Office 6 10 East Center Avenue, Suite 301 Mooresvil le, North Carolina 28115
704 663 1699