HomeMy WebLinkAboutNC0035904_Technical Assistance_20040419Michael F. Easley, Governor
William G. Rosa Jr., Secretary
North Carolina Department of Environment and Natural Resources
Alan W. Klimek; P.E. Director
Division of Water
May10,2004
William N Stovall, PE
NC Department of Correction
4216 Mail Service Ctr
Raleigh NC 27699
SUBJECT: April 19, 2004 Technical AssistanceInspection
NC Department of Correction
McCain.Correctional Hospital WWTP
Permit No: NC0035904
Hoke Cotinty.
-Dear-Mr. Stovall, PE:
Enclosed please find a copy of the Technical AssistanceInspectionform from the inspection conducted on
April 19, 2004. The Technical Assistance Inspection was conducted by Don Register of the Fayetteville
Regional Office. The facility was found to be in Compliance with permit NC0035904.
Please refer to the enclosed inspection report for additional observations and comments. If you or your staff"
have any questions, please call me at 910-486-1541.
Sincerely,
Don Register
cc: Darrel C Cockman, ORC
Central Files -
Fayetteville :Files
1617 Mail Service Center Raleigh, NC 27699-1617 (919) 733-7015 "Customer Service :. 1 800 623-7748
:DE
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection
1 12
, 2 15I 31 NC0035904 111 121 '.04/04/19 117
Type Inspector Fac Type
18 pi19 U 2011
I I I I I I I I I I I I II.166
-f
Remarks
211 I I I I I I I I I I I I I I I IIIII11111IIIIII
Inspection Work Days Facility Self -Monitoring Evaluation Rating 131 QA Reserved
67 I 7.0 1 69 70 U 71 1-1 721 tv I I1 174 751 1 1 1 1 1 1 1 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
McCain Correctional Hospital WWTP
NC Highway 211
Mccain NC 28361
Entry Time/Date
01:30 PM 04/04/19
Permit Effective Date
99/12/01
Exit Time/Date
03:30 PM 04/04/19
Permit Expiration Date
04/07/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Darrel C Cockman/ORC/910-944-2351/
///
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
William N Stovall, PE,4216 Mail Service Ctr Raleigh NC Contacted
27699//919-716-3419/9197163978 Yes
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Records/Reports 1 Self -Monitoring Program Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Don Register FRO WQ//91048615411726/910-486-0707
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
NPDES
NC0035904
11 12
yr/mo/day
04/04/19
117
Inspection Type
18
(cont.) 1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Facility was having a problem with low ph's on the effluent and aereation basin. The clarifier was
completely brown/turbid with no floc separation. The aeration basin had high dissolved oxygen (6-7mg/1) &
very' low ammonia nitrogen values. The aereation basin is a retrofit from a previous trickle filter with a
detention time of three days. It has three floating aereators and the operator was operating all three because
of the mixed liquor solids (4000mg/1) were settling in the basin when turned off. The effluent was in
noncompliance with total suspended solids on the day of technical assistance.
RECOMMENDATION: 1) immediately lower dissolved oxygen (d.o.) to less than 1 mg/1 to cause the activated
sludge to denitrify (this will stop nitrification and will cause the ph to rise) 2) order timers for the
aereators so they can be programed to operate at various times so overaereation will not occur.(d.o. should
range from 1-2 mg/1) 3) Increase sludge wasting until the effluent ammonia nitrogen increases(since ammonia
removal is not required by the permit). This lower MLSS will be where you will want to operate the aeration
basin mixed liquor suspended solids in the future. •
Follow-up:This facility had the recommended timers ordered dnd installed by the end of the month, the other
recommendations were followed and compliance with the permit was resumed in the month of May.
Permit: NC0035904 Owner - Facility: NC Department of Correction - McCain Correctional Hospital WWTP
Inspection Date: 04/19/04 Inspection Type: Technical Assistance
Record KReping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Are sampling and analysis data adequate and include:
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Plant records are adequate, available and include
O&M Manual
As built Engineering drawings
Schedules and dates of equipment maintenance and repairs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility classification?
Is a copy of the current NPDES permit available on site?
Is the facility description verified as contained in the NPDES permit?
Does the facility analyze process control parameters, for example: MLSS, MCRT, Settleable Solids, DO, Sludge
Judge, pH, and others that are applicable?
Facility has copy of previous year's Annual Report on file for review?
Comment:
Yes No NA NF
• ❑ ❑ ❑
. 000
• ❑ ❑ ❑
❑ ❑❑■
❑ ❑ ❑•
0
0
0
0
O
• ❑ ❑ ❑
0
0
1 ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑•❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
• '❑ ❑ ❑
■ ❑❑❑
▪ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ❑ ■