May 6, 2021
SUBJECT: Compliance Evaluation Inspection
Cooleemee WWTP
NPDES Permit No. NC0024872
Davie County
Dear Mr. Lambert,
On March 23, 2021, Tricia Lowery, Jordan Burbage, and Gary Hudson, of this office, met
with Tim Smith, Operator in Responsible Charge (ORC), to perform a Compliance
Evaluation Inspection at the Cooleemee Wastewater Treatment Plant. This type of
inspection consists of two basic parts: an in -office file review and an on -site inspection of
the treatment facility. The attached EPA inspection form details the areas that were
evaluated during this inspection.
The inspection of the facility was satisfactory. If you have any questions regarding the
inspection or this report, please contact Gary Hudson or me at (336) 776-9800 or by email
at gary.hudson@ncdenr.gov or lon.snider@ncdenr.gov.
Sincerely,
Docu Signed by:
%n. l . n.lAts'
145B49E225C94EA...
Lon Snider
Regional Supervisor
Water Quality Regional Operations
Division of Water Resources
Attachments: EPA Water Compliance Inspection Report
cc: WSRO
LD_E
NORTH CAROLINA
Department of Environmental qua[
North Carolina Department of Environmental Quality j Division of Water Resources
Winston-Salem Regional Office 1450 West Hanes Mill Road, Suite 300 I Winston-Salem, North Carolina 27105
336.776.9800
United States Environmental Protection Agency
E PA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction
1 IN I
21IIIIII
Code NPDES yr/mo/day Inspection
2 IL I 3 I NC0024872 111 121 21/03/23 117
Type
1810I
IIIIIIIIIII
Inspector Fac Type
19I S I 2011
IIIIIIIIIII IIIIIII I IIIIII
P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
671 I 70I I 711 172 I N I 73I 1 74 71
I I
I I I I I I 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES Dermit Number)
Cooleemee WWTP
NC Hwy 801 S
Cooleemee NC 27014
Entry Time/Date
10:OOAM 21/03/23
Permit Effective Date
15/07/01
Exit Time/Date
12:OOPM 21/03/23
Permit Expiration Date
20/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Timothy Lamar Smith/ORC/336-284-6680/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Johnny Lambert,261 Chaffin St Mocksville NC 27028//336-753-6090/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Gary Hudson DWR/Division of Water Quality/336-776-9694/
Signature of
Managmeigned yn16Q A Reviewer Agency/Office/Phone and Fax Numbers Date
�Doc :
Lo, T. J,Ndcr 5/6/2021
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
31
NPDES yr/mo/day
NC0024872 111 121 21/03/23
117
Inspection Type
18 [j
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
*The current NPDES permit expired on June 30, 2020. A renewal application has been submitted, but
the issuance of the new permit has been delayed.
*On November 13, 2020, Tropical Storm Eta caused severe flooding and extensive damage to the
entire plant as well as the influent pump station.
*The following process control tests are performed by plant personnel: 30-minute settleability, MLSS,
MLVSS, and dissolved oxygen.
*Please be advised that the ORC or a designated Back-up ORC must visit the WWTP Monday thru
Friday, 5-days per week excluding weekends and holidays.
*Most of the records prior to December have been destroyed by the flood. The January DMR was
compared to the lab results data that was sent from the contract lab. No discrepancies were noted.
*The Influent Pump Station has been bypassed since the November flood. Contractors have been
working continuously to replace the damaged components.
*The mechanical bar screen has been bypassed due to the bypass pumping configuration.
*The WWTP has two secondary clarifiers. Both were in operation and appeared to be very well
maintained. The effluent in the weir troughs appeared to be very clear at the time of the inspection.
*The extended aeration basin appeared to be operating properly. The basin has two mixers and two
mechanical aerators. The mixers and aerators alternate with each other and run every other
30-minutes. The D.O. probe at the time of the inspection was reading 2.4 mg/I.
*The flow meter was calibrated on October 22, 2020.
*The right-of-way to the outfall pipe was clear and very well maintained. The effluent pipe was
submerged during the time of the inspection.
*The County has purchased a new effluent composite sampler. There was a thermometer laying on
the floor of the refrigerator that was not NIST certified. Please be advised that a NIST certified
thermometer placed in a liquid must be located in the sampler refrigerator and must be calibrated
annually with proof of calibration readily available for inspection.
*The replacement sampler was on back order at the time or the inspection. The operator collects
hourly grab samples.
Page# 2
Permit: NC0024872
Inspection Date: 03/23/2021
Owner - Facility: Cooleemee WWTP
Inspection Type: Compliance Evaluation
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The current NPDES permit expired on June 30, 2020. A renewal application has been
submitted, but the issuance of the new permit has been delayed.
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Yes No NA NE
Comment: On November 13, 2020, Tropical Storm Eta caused severe flooding and extensive damage
to the entire plant as well as the influent pump station.
The following process control tests are performed by plant personnel: 30-minute settleability
MLSS, MLVSS, and dissolved oxygen.
Please be advised that the ORC or a designated Back-up ORC must visit the WWTP
Monday thru Friday, 5-days per week excluding weekends and holidays.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
•
•
•
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 3
Permit: NC0024872
Inspection Date: 03/23/2021
Owner - Facility: Cooleemee WWTP
Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operatc
on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility classification'
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
❑ ❑ ■ ❑
▪ El El El
• ❑ ❑ ❑
▪ El El El
Comment: Most of the records prior to December have been destroyed by the flood. The January DMR
was compared to the lab results data that was sent from the contract lab. No discrepancies
were noted.
Pump Station - Influent Yes No NA NE
Is the pump wet well free of bypass lines or structures? ❑ • ❑ ❑
Is the wet well free of excessive grease? • ❑ ❑ ❑
Are all pumps present? ❑ • ❑ ❑
Are all pumps operable? ❑ • ❑ ❑
Are float controls operable? ❑ • ❑ ❑
Is SCADA telemetry available and operational? ❑ ❑ • ❑
Is audible and visual alarm available and operational? ❑ ❑ ❑ •
Comment: The Influent Pump Station has been bypassed since the November flood. Contractors have
been working continuously to replace the damaged components.
Bar Screens Yes No NA NE
Type of bar screen
a.Manual ❑
b.Mechanical •
Are the bars adequately screening debris? ❑ ❑ • ❑
Is the screen free of excessive debris? ❑ ❑ • ❑
Is disposal of screening in compliance? ❑ ❑ • ❑
Is the unit in good condition? ❑ ❑ • ❑
Comment: The mechanical bar screen has been bypassed due to the bypass pumping configuration.
Grit Removal
Type of grit removal
a.Manual
Yes No NA NE
Page# 4
Permit: NC0024872
Inspection Date: 03/23/2021
Owner - Facility: Cooleemee WWTP
Inspection Type: Compliance Evaluation
Grit Removal
b.Mechanical
Is the grit free of excessive organic matter?
Is the grit free of excessive odor?
# Is disposal of grit in compliance?
Comment:
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth)
Yes No NA NE
❑ ❑ • ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
Comment: The WWTP has two secondary clarifiers. Both were in operation and appeared to be very
well maintained. The effluent in the weir troughs appeared to be very clear at the time of the
inspection.
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Surface
Is the basin free of dead spots? • ❑ ❑ ❑
Are surface aerators and mixers operational? • ❑ ❑ ❑
Are the diffusers operational? ❑ ❑ • ❑
Is the foam the proper color for the treatment process? • ❑ ❑ ❑
Does the foam cover less than 25% of the basin's surface? • ❑ ❑ ❑
Is the DO level acceptable? • ❑ ❑ ❑
Is the DO level acceptable?(1.0 to 3.0 mg/I) • ❑ ❑ ❑
Comment: The extended aeration basin appeared to be operating properly. The basin has two mixers
and two mechanical aerators. The mixers and aerators alternate with each other and run
every other 30-minutes. The D.O. probe at the time of the inspection was reading 2.4 mg/I.
Page# 5
Permit: NC0024872
Inspection Date: 03/23/2021
Owner - Facility: Cooleemee WWTP
Inspection Type: Compliance Evaluation
Aeration Basins
Disinfection -Gas
Are cylinders secured adequately?
Are cylinders protected from direct sunlight?
Is there adequate reserve supply of disinfectant?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1000-
If yes, then when was the RMP last updated?
Comment:
Yes No NA NE
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
❑ • ❑ ❑
❑ ❑ • ❑
De -chlorination Yes No NA NE
Type of system ? Gas
Is the feed ratio proportional to chlorine amount (1 to 1)? • ❑ ❑ ❑
Is storage appropriate for cylinders? • ❑ ❑ ❑
# Is de -chlorination substance stored away from chlorine containers? ❑ ❑ • ❑
Comment:
Are the tablets the proper size and type? ❑ ❑ • ❑
Are tablet de -chlorinators operational? ❑ ❑ • ❑
Number of tubes in use?
Comment:
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting? • ❑ ❑ ❑
Is flow meter calibrated annually? • ❑ ❑ ❑
Is the flow meter operational? • ❑ ❑ ❑
(If units are separated) Does the chart recorder match the flow meter? • ❑ ❑ ❑
Comment: The flow meter was calibrated on October 22, 2020.
Effluent Pipe Yes No NA NE
Page# 6
Permit: NC0024872
Inspection Date: 03/23/2021
Owner - Facility: Cooleemee WWTP
Inspection Type: Compliance Evaluation
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Yes No NA NE
• ❑ ❑ ❑
▪ El El El
❑ ❑ • ❑
Comment: The right-of-way to the outfall pipe was clear and very well maintained. The effluent pipe wa:
submerged during the time of the inspection.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The County has purchased a new effluent composite sampler. There was a thermometer
laying on the floor of the refrigerator that was not NIST certified. Please be advised that a
NIST certified thermometer placed in a liquid must be located in the sampler refrigerator and
must be calibrated annually with proof of calibration readily available for inspection.
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Comment:
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Yes No NA NE
❑ ❑ ❑ •
❑ ❑ ❑ •
❑ ❑ ❑ •
❑ ❑ ❑ •
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 7
Permit: NC0024872
Inspection Date: 03/23/2021
Owner - Facility: Cooleemee WWTP
Inspection Type: Compliance Evaluation
Laboratory Yes No NA NE
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ ❑ •
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ ❑ •
Comment:
Influent Sampling
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is sampling performed according to the permit?
Yes No NA NE
❑ • ❑ ❑
❑ ❑ • ❑
❑ ❑ • ❑
Comment: The replacement sampler was on back order at the time or the inspection. The operator
collects hourly grab samples.
Pumps-RAS-WAS
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 8