Loading...
HomeMy WebLinkAboutNC0034754_authorization to construct_19890628State of North Carolina Department of Natural Resources and Community Development Division of Environmental Management 512 North Salisbury Street • Raleigh, North Carolina 27611 James G. Martin, Governor William W. Cobey, Jr., Secretary June 28, 1989 Tony Garrison, Facilities Manager Comm/Scope, Inc. P.O. Box 199 Catawba, NC 28609 R. Paul Wilms Director Subject: Permit No. NC0034754 Authorization to Construct Comm/Scope, Inc. Catawba County Dear Mr. Garrison: A letter of request for an Authorization to Construct was received April 19, 1989 by the Division and final plans and specifications for the subject project have been reviewed and found to be satisfactory. Authorization is hereby granted for the construction of 10,000 GPD "extended aeration" wastewater treatment facility which will consist of a bar screen, a 10,000 aeration tank, a 3,000 gallon clarifier, a 1,211 gallon sludge holding tank, two (2) 191 cfm blowers, a 434 gallon chlorine contact tank with tablet chlorination, a 108 gallon post aeration tank, a totalizer flow meter and all associated valves, piping, and appurtenance to serve Comm/Scope, Inc. in Catawba County. This Authorization to Construct is issued in accordance with Part III, paragraph B of the NPDES Permit No. NC0034754 issued January 3,1989, and shall be subject to revocation unless the wastewater treatment facilities are constructed in accordance with the conditions and limitations specified in Permit No. NC0034754. Upon 50% completion of the subject facilities the Permittee must employ a certified wastewater operator in accordance with Part III paragraph C of the referenced permit The sludge generated from these treatment facilities must be disposed of in accordance with G.S. 143-215.1 and in a manner approvable by the North Carolina Division of Environmental Management. The Mooresville Regional Office, telephone number 704/663-1699 shall be notified at least twenty-four (24) hours in advance of backfilling of the installed system, so that an in -place inspection can be made. Such notification to the Regional Supervisor shall be made during the normal office hour from 8:00 a.m. until 5:00 p.m. on Monday through Friday, excluding State holidays. Pollution Prevention Pays P.O. Box 27687, Raleigh, North Carolina 27611-7687 Telephone 919-733-7015 An Equal Opportunity Affirmative Action Employer In event the facilities fail to perform satisfactorily in meeting its NPDES permit effluent limits, the permittee shall take such immediate corrective action as may be required by this Division, including the construction of additional wastewater treatment and disposal facilities. Upon completion of construction and prior to operation of this permitted facility, a certification must received from a professional engineer certifying that the permitted facility has been installed in accordance with the approved plans and specifications. Mail the Certification to the Permits and Engineering Unit, P.O. Box 27687, Raleigh, NC 27611-7687. A copy of the approved plans and specifications shall be maintained on file by the Permittee for the life of the permit. One (1) set of approved plans and specifications is being forwarded to you. If you have any questions or need additional information, please contact Mr. William Barlow, telephone number 919/733-5083. Sincerely, R. Paul Wilms cc: Catawba County Health Department Mooresville Regional Office Peimit No. NC0034754 Engineer's Certification I, , as a duly registered Professional Engineer in the State of North Carolina, having been authorized to observe (periodically/weekly/full time) the construction of the project, for the (Project) (Name or Location) hereby state that, to the best of my (Project Owner) abilities, due care and diligence was used in the observation of the project construction such that the construction was observed to be built within substantial compliance and intent of the approved plans and specifications. Signature Registration No. Date