HomeMy WebLinkAboutNC0001406_Inspection_20080201Michael F. Easley, Governor
William G. Ross Jr., Secretary
North Carolina Department of Environment and Natural Resources
• Coleen H. Sullins, Director
Division of Water Quality
Alan Thornton
Town n of Erwin
PO Box 549
Erwin NC 28339
SUBJECT:
February 1, 2008
January 24, 2008 Compliance Evaluation Inspection
Town of Erwin
Erwin WWTP #2
Permit No: NC0001406
Harnett County
Dear Mr. Thornton:
Enclosed please fmd a copy of the Compliance Evaluation Inspection form from the inspection conducted on January 24, 2008.
The Compliance Evaluation Inspection was conducted by Mark Brantley, Environmental Chemist, of the Fayetteville Regional
Office. The facility.was found to be in Compliance with permit NC0001406. As a -reminder, preservation of the Waters of the
State can only be achieved through consistent NPDES Permit compliance.
Comments
•
The Division of Water Quality understands the Town and Harnett County are still working on a deal to transfer
ownership of this facility. Please remember that a written response is due in the Fayetteville Regional Office by
January 31, 2008 from the letter sent to the town dated January 7, 2008 in which a tentative timeline was requested.
Also quarterly reports are to be submitted with updates until this facility is transferred to Harnett County or its permit
is rescinded.
• The Division recognizes the challenges this facility has in chlorinating and dechlorinating the effluent, but also
encourages the town to continue using chlorine tablets and dechlor tablets. This should help the facility to better meet
its NPDES permit limits for fecal and chlorine.
Please refer to the enclosed inspection report for additional observations and comments. If you or your staff'have any
questions, please call me at 910-433-3327.
cc: Billy Weldon Addison, ORC
Central Files
,Fayetteville Files
Sincerely,
Q
Mark Brantley
Environmental Chemist
Surface Water Protection Section
Fayetteville Regional Office
NonrthCarolina
Naturally
North Carolina Division of Water Quality/Aquifer Protection Section 225 Green St./ Suite 714 Fayetteville, NC 28301 Phone (910) 433-3300
FAX (910) 486-0707 Internet h2o.enr.state.np.us Customer Service 1-877-623-6748
An Equal Opportunity/Affirmative Action Employer — 50% Recycled/10% Post Consumer Paper
United States Environmental Protection Agency
E PA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection
1 I NI 2 151 31 NC0001406 111 121 08/01/24 117
Type Inspector Fac Type
181 CI 191 sI 201
1 1 1 1 1 I I 1 111111166
Remarks
2111111111 I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1111 II II
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
671 169 70 12 I 711 DI 721 2 I 731
I 174 . 751 I I I I I I 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Erwin WWTP #2
411 S 20th St
Erwin NC 28339
Entry Time/Date
01:00 PM 08/01/24
Permit Effective Date
07/10/01
Exit Time/Date
01:30 PM 08/01/24
Permit Expiration Date
11/09/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Billy Weldon Addison/ORC/910-892-2948/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Alan Thornton,PO Box 549 Erwin NC 28339//910-897-6663/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Operations & Maintenance • Records/Reports - • Self -Monitoring Program
Facility Site Review
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
.Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Mark Brantley FRO WQ//910-433-3300 Ext.727/
New dew 1 • ?y - a 5
Signature of Management Q Reviewer Agency/Office/Phone and Fax Numbers Date % �%
Belinda S Henson ` v FRO WQ//910-433-3300 Ext.726/ a -l.%0
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page # 1
NPDES,
NC0.001406
I11• 121
yr/mo/day
08/01/24
117
Inspection Type
18ICI
(cant.) 1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Comments
• The Division of Water Quality understands the Town and Harnett County are still -working on a deal to
transfer ownership of this facility. Please remember that a written response is due in the Fayetteville
Regional Office by January 31, 2008 from the lettersentto the town dated January 7, 2008 in which a -
tentative timeline was requested. Also quarterly reports are to be submitted with updates until this facility is
transferred to Harnett County or its permit is rescinded.
• The Division recognizes the challenges this facility has in chlorinating and dechiorinating the effluent, but
also encourages the town to continue using chlorine tablets and dechlor tablets. This should help the: facility
to better meet its NPDES permit limits for fecal and chlorine.
Page #"
Permit: NC0001406 Owner - Facility: Erwin WWTP #2
Inspection Date: 01/24/2008 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ■ n n n
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge n n • n
Judge, and other that are applicable?
Comment:
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment:
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/< of the sidewall depth)
Comment
Aeration Basins
Mode of operation
Type of aeration system
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Yes No NA NE
n n■n.
■ nnn
n n■n
■ nnn
■ nnn
Yes No NA NE
■ nnn
■ nnn
■ nnn
■ nnn
■ nnn
■ nnn
■ nnn
■ nnn
■ nnn
■ nnn
nn.n■
Yes No NA NE
Ext. Air
Surface
■ nnn
■nnn
nnNn
Page # 3
Permit: NC0001406 Owner - Facility: Erwin WWTP #2
Inspection Date: 01/24/2008 Inspection Type: Compliance Evaluation
Aeration Basins
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0. mg/I)
Comment: Only one of the surface aerators is in operation:
De -chlorination
Type of system ?
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Comment:
Are the tablets, the proper. size and type?
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment: Currently chlorine tablets are being placed in the trough at theend of the
aeration basin. Flow is less than 10,000 gallons per day.
Pumps-RAS-WAS
Are pumps in place?
Are pumps operational?
'Are there adequate spare parts and supplies on site?
Comment:
Disinfection -Tablet
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Number of tubes in use?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Comment: A tube feeder is placed at the discharge point in the effluent trough. Flow
is less than 10,000 gallons a day.
Effluent Sampling
Yes No NA NE
innn
■ nnn
■ nnn
■ nnn
Yes No NA NE
Tablet
D0.r
n n■n
n n■n
■ nnn
n n■n
Yes No NA NE
■ nnn
■ nnn
n nn:
Yes No NA NE
n n■n
■ nnn,,
■ nnn
n n■n
n nn■
Yes No NA NE
Page # 4
Permit: NC0001406 Owner - Facility: Erwin WWTP #2
Inspection Date: 01/24/2008 Inspection Type: Compliance Evaluation
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? n n ■ n
Is sample collected below all treatment units? ■ n ❑ n
Is proper volume collected? ■ n n n
Is the tubing clean? n n ■ n
Is proper temperature set for sample storage (kept at 1.0 to 4.4 degrees Celsius)? n n ■ n
Is the facility sampling performed as required by the permit (frequency, sampling type representative)? n n ■ n
Comment: Since the flow is so small a series of grab samples are collected
throughout the day to make a composite sample.
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, and sampling location)? n n n ■
Comment: Facility is a member of the Cape Fear River Basin Association.
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? ■ n n n
Is all required information readily available, complete and current? ■ ❑ n n
Are all records maintained for 3 years (lab. reg. required 5 years)? ■ n ❑ n
Are analytical results consistent with data reported on DMRs? n n n ■
Is the chain -of -custody complete? ■ ri n n
Dates, times and location of sampling ■
Name of individual performing the sampling ■
Results of analysis and calibration ■
Dates of analysis ■
Name of person performing analyses ■
Transported COCs ■
Are DMRs complete: do they include all permit parameters? ■ n n n
Has the facility submitted its annual compliance report to users and DWQ? ■ n n n
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift? n n ■ n
Is the ORC visitation log available and current? ■ n n n
Is the ORC certified at grade equal to or higher than the facility classification? • n n n
Is the backup operator certified at one grade less or greater than the facility classification? ■ n n n
Is a copy of the current NPDES permit available on site? ■ n n n
Page # - 5
Permit: NC0001406 Owner- Facility: Erwin WWTP #2
Inspection Date: 01/24/2008 Inspection Type: Compliance Evaluation
Record Keeping
Facility has copy of previous year's Annual Report on file for review?
Comment:
Yes No NA NE
■nnn
Page # 6