HomeMy WebLinkAboutNC0043176_Inspection_20091214Beverly Eaves Perdue
Governor
A.TA
NCDENR
North Carolina Department of -Environment and Natural Resources
Division of Water Quality
Coleen H. Sullins Dee Freeman
Director Secretary
December 14, 2009
Ronald D Autry, City Manager
City of Dunn _
P.O. Box 1065 - .
Dunn, NC 28335
SUBJECT: November 20, 2009 Compliance Evaluation Inspection
City of Dunn
Dunn WWTP
Permit No: NC0043176
Harnett County
Dear Mr. Autry:
Enclosed please find a copy of the Compliance Evaluation Inspection form from the inspection conducted on November
20, 2009. The Compliance Evaluation. Inspection was conducted by Mark Brantley, Environmental Chemist, of the
Fayetteville Regional Office. The cooperation of Donrie Dukes, Grade IV ORC, Dishon -Allen, Grade IV Back-up ORC,
and Gary Barefoot, Grade II Operator/Maintenance Staff, was greatly appreciated. The facility was found to be in
Compliance with permit NC0043176.. As a reminder, preservation of the Waters of the State can only be achieved
through consistent NPDES Permit compliance.
- COMMENTS
• Facility was clean and neat in appearance at the time of the inspection.
• Facility has successfully switched from a gas chlorination/de-chlorination to a liquid chlorination/de-
chlorination.
Please refer to the enclosed inspection report for additional observations and comments. If you or your staff have any
questions, please call me at 910-433-3327.
Sincerely,
Mark,:Biantley ;; i .
Environmental Chemist
Surface Water Protection Section
Fayetteville Regional Office
cc: Donrie Eldridge Dukes, ORC
Central Files
Fayetteville. Filesr.1
NorthCarolina
Naturally
North Carolina Division of Water Quality/Aquifer Protection Section 225 Green St./ Suite 714 Fayetteville, NC 28301 Phone (910) 433-3300
FAX (910) 486-0707 Internet: h2o.enr.state.nc.us Customer Service 1-877-623-6748
An Equal Opportunity/Affirmative Action Employer— 50% Recycled/10% Post Consumer Paper
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection
1 INI 2 151 31 NC0043176 111 121 09/11/20 117
Type Inspector Fac Type
181 CI 191 SI 201
Remarks
211111111111111111111111111111111111111111111111166
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
671 169 - 70 13 I 71 I N I 721 NI 731
I 174 751 I I I I I I 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Dunn WWTP
Susan Tart Rd
Dunn NC 28335
Entry Time/Date
10:00 AM 09/11/20
Permit Effective Date
07/02/01
Exit Time/Date
12:30 PM 09/11/20
Permit Expiration Date
11/09/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Donrie Eldridge Dukes/ORC/910-892-8162/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Ronald D Autry,PO Box 1065 Dunn NC 28335//910-892-2633/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement • Operations & Maintenance • Records/Reports
Self -Monitoring Program • Sludge Handling Disposal • Facility Site Review
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary).
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Maqr/kk Brantleyf,i FRO WQ//910-433-3300 Ext.727/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
Belinda S HensonC ^4 FRO WQ//910-433-3300 Ext.726/ I a JL4_ 69
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page # 1
NPDES
NC0043176
I11 121
yr/mo/day
09/11/20
17
Inspection Type
18101
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
COMMENTS
Facility was clean and neat in appearance at the time of the inspection.
Facility has successfully switched from a gas chlorination/de-chlorination to a liquid
chlorination/de-chlorination.
Page # 2
Permit: NC0043176 Owner - Facility: Dunn WWTP
Inspection Date: 11/20/2009 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ■ n . n n
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge ■ n n n
Judge, and other that are applicable?
Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new application? n n ■ n
Is the facility as described in the permit? ■ n n .n
# Are there any special conditions for the permit? n n ■ n
Is access to the plant site restricted to the general public? ■ n ❑ ❑
Is the inspector granted access to all areas for inspection? ■ n n n
Comment:
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? ■ n ❑ n
Is all required information readily available, complete and current? ■ n n n
Are all records maintained for 3 years (lab. reg. required 5 years)? ■ n n n
Are analytical results consistent with data reported on DMRs? ❑ ❑ ❑ ■
Is the chain -of -custody complete? n n n ■
Dates, times and location of sampling - n
Name of individual performing the sampling n
Results of analysis and calibration ❑
Dates of analysis n
Name of person performing analyses n
Transported COCs
Are DMRs complete: do they include all permit parameters? n- n n ■
Has the facility submitted its annual compliance report to users and DWQ? ■ n n n
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift? n n ■ n
Is the ORC visitation log available and current? ■ n n n
Is the ORC certified at grade equal to or higher than the facility classification? ■ n n n
Is the backup operator certified at one grade less or greater than the facility classification? ■ n n n
Is a copy of the current NPDES permit available on site? ■ n n n
Page # 3
Permit: NC0043176
Inspection Date: 11/20/2009
Owner - Facility: Dunn wMTP
Inspection Type: Compliance Evaluation
Record Keeping.
Facility has copy of previous year's Annual Report on file for review?`
Comment:
Flow Measurement -'Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment:' Flow meter was last calibrated in April 2009.
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Is the site free-of'excessive foaming in the tank?
# Is the odor -acceptable?
# Is tankage available forproperly waste sludge?
Comment:
Solids Handling -Equipment
Is the equipment operational? -
Is the chemical feed equipment operational? •
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum' filters?
Is the Site free of sludge buildup on belts and/or rollers of filter press? _
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
Comment: Unit was not in operation at the time of the inspection.
Pump Station - Effluent
Is the pump wet well free of bypass lines or structures?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry available and operational? -
Yes No NA 'NE ,
■ nnn
Yes No NA NE
■ nnn
nnn■
Yes No -NA NE
■ nn.n
■ nnn
■ nnn
:nn.n
■nnn,=.
Yes No NA NE
■ nnn
■ n n- n
■ nnn
p n ■-n...
nn■n
n•n■n
■ nnn
Yes No NA NE
■ n-nn.
■ nnn
■ nnn
■ nnn.
nn.n
Page # 4
Permit: NC0043176
Owner - Facility: Dunn'WWTP
Inspection Date: 11/20/2009 Inspection Type: Compliance Evaluation
Pump Station - Effluent
Is audible and visual alarm available and operational?
Comment: .
Pump Station - Influent
Is the pump wet well free of bypass lines or structures?
Is the wet well free of excessive grease?
Are all pumps present?.
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry available and operational?
Is audible and visual alarm available and operational?
Comment:
Bar Screens
Type of bar screen
a. Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment:
Grit Removal
Type of grit removal
a.Manual
b.Mechanical
Is the grit free of excessive organic matter?
Is the grit free of excessive odor?
# Is disposal of grit in compliance?
Comment:
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Yes No NA NE
■ nnn
Yes No NA NE
■ nnn
■nnn
■ nnn
■nnn
■ nnn,
n n■n
n nn■
Yes No NA NE
n
■
■ nnn
■ nnn
■ nnn
■ nnn
Yes No NA NE
n
■
■ nnn
■ nnn
■ nnn
Yes No NA NE
■ nnn
Page # 5
Permit: NC0043176 Owner - Facility: Dunn WWTP
Inspection Date: 11/20/2009
/ Inspection Type: Compliance Evaluation
Secondary Clarifier
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately 'A of the sidewall depth)
Comment: The sludge blanket in all three clarifiers was 6'.
Aeration Basins
Mode of operation
' Type of aeration system
Is the basin free of dead spots?
Are surface aerators and mixers operational? -
Are the, diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/I)
Comment:
De -chlorination
Type of system ?
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Are the tablets the proper size and type?
Comment: Facility recently converted their gas de -chlorination equipment to a liquid
bisulfite de -chlorination system.
Yes No NA NE
■ nn.n
■nnn
■ nnn
■ nnn
■ nnn
■ [Inn
■ nnn
■ El n
■ nnn
■ nnn
Yes No NA NE
Ext. Air
Diffused
'■nnn,
nn■n
■ nnn
■ nnn
■ nnn
■ nnn
■ nnn
Yes No NA NE
•
Liquid
■ nnn
■ nnn
■ nnn
n n ■ n
Page # 6
Permit: NC0043176 • Owner - Facility: Dunn WWTP
Inspection Date: 11/20/2009 Inspection Type: Compliance Evaluation
De -chlorination
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment:
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Comment:
Pumps-RAS-WAS
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
Comment:
Disinfection -Liquid
Is there adequate reserve supply of disinfectant?
(Sodium Hypochlorite) Is pump feed system operational?
Is bulk storage tank containment area adequate? (free of leaks/open drains)
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Comment: Facility has recentley converted their gas chlorination equipment to a liquid
sodium hypochlorite system.
Influent Sampling
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Yes No NA NE
n n■n
Yes No NA NE
■ nnn
■ nnn
■ nnn
n nn■
■ nnn
n nn■
■ nn•n
Yes No NA NE
■ nnn
■ nnn
• nnn
Yes No NA NE
■ nnn
■ nnn
■ nnn
■nnn
■ n n
■ nnn
Yes No NA NE
n il ■n
■ nn•n
■ nnn
Page # 7
Permit: NC0043176
Inspection Date:11/20/2009
Owner - Facility: Dunn wMTP
Inspection Type: Compliance Evaluation
Influent Sampling Yes No NA NE
Is the tubing clean? ■ n n n
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? • n n n
Is sampling performed according to the permit? mi n n ❑
Comment:. Influent sampler temperature was at 4 degrees Celsius.
Effluent Sampling Yes No. NA NE
Is composite sampling flow proportional? ■ ❑ n n
is sample collected below all treatment units? ■ n n n
Is proper volume collected? ■ n n n
Is the tubing clean? ■ n n n
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? ■ n n n
Is the facility sampling performed as required by the permit (frequency, sampling type representative)? ■ 0 n n
Comment: Effluent sampler temperatue was at 3 degrees Celsius.
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, and sampling location)? n n • ❑
Comment: Facility is a member of the Middle Cape Fear River Basin Assembly which
has a MOA with the Division of Water Quality to conduct upstream and downstream
sampling for various faicilities.
J
Page # 8