Loading...
HomeMy WebLinkAboutWQ0042382_Application (FTSE)_20210329Permit Number WQ0042382 Program Category Non -discharge Permit Type Gravity Sewer Extension, Pump Stations, & Pressure Sewer Extensions Primary Reviewer dean.hunkele Coastal SWRule Permitted Flow Facility Central Files: APS _ SWP _ 3/16/2021 Permit Tracking Slip Status Project Type In review New Project Version Permit Classification A Individual Permit Contact Affiliation Facility Name Major/Minor Region Aurora Place Minor Wilmington Location Address County Brunswick Facility Contact Affiliation Owner Owner Name Owner Type Brunswick County Government - County Owner Affiliation John Nichols PE PO Box 249 Dates/Events Bolivia NC 2842202, Scheduled Orig Issue App Received Draft Initiated Issuance 3/5/2021 Regulated Activities Outfall Waterbody Name Malpass Engineering & Surveying, P. C. 1134 Shipyard Blvd. Wilmington, NC 28412 Phone: 910-392-5243 Fax: 910-392-5203 License No. C-2320 March 5, 2021 To: Dean Hunkele NCDEQ Re: Aurora Place ECEIV= MAR 0 5 2021 We are submitting a Fast -Track Application (FTA 04-16) for the above referenced project. The following items are provided: original and copy of the application form, $480 application fee, copy of approval letter from Brunswick County, original and copy of Flow Tracking/Acceptance for Sewer Extension Application (FTSE 04-16), two copies of the Sanitary Sewer Narrative, two copies of a color 8.5"xl 1" Aerial Map, and two copies of a color 8.5"xl 1" of USGS Topographic Map. See Sanitary Sewer Narrative for project description. Thanks, Justin C. Bishop, P.E. Aurora Place Sanitary Sewer Narrative Description: Travel 1.32 miles south on US-17 (Ocean Hwy E) from the intersection of US-17 & NC- 87 (George II Hwy SE). Turn right on S.R. 1406 (Bell Swamp Rd NE) and travel 0.87 miles to the site. The site is located on the north side of Bell Swamp Rd NE. The proposed sanitary sewer system is to serve 221 (4 bedroom) units. The flow required is 61,880 GPD based on a reduced flow rate of 70 gpd/bedroom (140 gpd/lot min.) since the flow goes to the West Brunswick Regional W WTF which has that approved reduced flow rate. There is 8,024.10 LF of 8" public sanitary sewer gravity main, 356 LF of 8" public sanitary sewer force main (direction drill), and 4,591 LF of 6" public sanitary sewer force main being proposed for this project. The length of the gravity sewer main is based on the distance from inside wall of manhole to inside wall of manhole. The pump station is a duplex station. The pumps are 30 horsepower, and the pumping rate is 490 gpm at 124 TDH when pumping alone at initial service. The proposed 6" force main will discharge into an existing 16" sanitary sewer force main along the east side of US-17. Approvals, as/if required, will be obtained to permanently fill some of the 404 wetlands on the site, and to permanently fill the isolated wetlands. Therefore, 4 locations where the public sanitary sewer gravity main would have crossed wetlands, will not cross wetlands. Those 4 areas will be greater than 10 feet from the new wetland lines. 71.05 LF of the 153.92 LF of the proposed public sanitary sewer gravity main from SSMH-2 to SSMH-21 is within 10 feet of, or crosses, wetlands. The public sanitary sewer gravity main from SSMH-2 to SSMH-21 will meet water main standards (15A NCAC 18C) for materials, testing methods and acceptability standards. 224 LF (along Bell Swamp Connection) of the public sanitary sewer force main is within 10 feet of, or crosses, wetlands. The public sanitary sewer force main will meet water main standards (15A NCAC 18C) for materials, testing methods and acceptability standards. State of North Carolina Department of Environmental Quality DWR Division of Water Resources 15A NCAC OTT .0300 — FAST TRACK SEWER SYSTEM EXTENSION APPLICATION Division of Water Resources FTA 04-16 & SUPPORTING DOCUMENTATION Application Number: WI w q l (m be completed by DwR) All items must be completed or the application will be returned I. APPLICANT INFORMATION: 1. Applicant's name: Brunswick County (company, municipality, HOA, utility, etc.) 2. Applicant type: ❑ Individual ❑ Corporation ❑ General Partnership ❑ Privately -Owned Public Utility ❑ Federal ® State/County ❑ Municipal ❑ Other 3. Signature authority's name: William L. Pinnix per 15A NCAC 02T .0106(b) Title: Director of En ine eering 4. Applicant's mailing address: P.O. Box 249 City: Bolivia State: NC Zip: 28422- 5. Applicant's contact information: Phone number: (2U0 253-2408 Email Address: William.Pinnix()a,brunswickcountync.gov 11. PROJECT INFORMATION: 1. Project name: Aurora Place 2. Application/Project status: ® Proposed (New Permit) ❑ Existing Permit/Project If a modification, provide the existing permit number: W000 and issued date: If new construction but part of a master plan, provide the existing permit number: W000 3. County where project is located: Brunswick 4. Approximate Coordinates (Decimal Degrees): Latitude: 34.1164' Longitude:-78.1235' 5. Parcel ID (if applicable): Portion of 09700029 (or Parcel ID to closest downstream sewer) III. CONSULTANT INFORMATION: 1. Professional Engineer: Justin C. Bishop License Number: 036232 Firm: Malpass Engineering & Surveying, P.C. Mailing address: 1134 Shipyard Blvd City: Wilmington State: NC Zip: 28412 Phone number: (910) 392-5243 Email Address: justinbishop@bizec.rr.com IV. WASTEWATER TREATMENT FACILITY (WWTF) INFORMATION: 1. Facility Name: West Brunswick Regional WWTF Permit Number: W00023693 Owner Name: Brunswick County V. RECEIVING DOWNSTREAM SEWER INFORMATION (if different than WWTF): I. Permit Number(s): WQ i203a,(z7LI Downstream (Receiving) Sewer Size: 16 inch System Wide Collection System Permit Number(s) (if applicable): WQCS o0i,8� Owner Name(s): Brunswick County FORM: FTA 04-16 Page 1 of 5 VI. GENERAL REQUIREMENTS I. If the Applicant is a Privately -Owned Public Utility, has a Certificate of Public Convenience and Necessity been attached? ❑ Yes ❑No ®N/A 2. If the Applicant is a Developer of lots to be sold, has a Developer's Operational Aereement (FORM: DEV I been attached? ❑ Yes ❑No ®N/A 3. If the Applicant is a Home/Property Owners' Association has an Operational Aareement (FORM HOA) been attached? ❑ Yes ❑No ®N/A 4. Origin of wastewater: (check all that apply): ® Residential Owned ❑ Retail (stores, centers, malls) ❑ Car Wash ❑ Residential Leased ❑ Retail with food preparation/service ❑ Hotel and/or Motels ❑ School / preschool / day care ❑ Medical / dental / veterinary facilities ❑ Swimming Pool /Clubhouse ❑ Food and drink facilities ❑ Church ❑ Swimming Pool/Filter Backwash ❑ Businesses / offices / factories ❑ Nursing Home ❑ Other (Explain in Attachment) 5. Nature of wastewater: 100 % Domestic/Commercial % Commercial _ % Industrial (See 15A NCAC 02T .0103(20)) "Is there a Pretreatment Program in effect? ❑ Yes ❑ No 6. Hasa flow reduction been approved under 15A NCAC 02T .0114(f)? ®Yes ❑ No ➢ If yes, provide a copy of flow reduction approval letter 7. Summarize wastewater generated by project: Establishment Type (see 02T.0114(t)) Daily Design Flow'.b No. of Units Flow Single -Family Residential (4 bedroom) 280 gal/lot 221 61,880 GPD gal/ GPD gal/ GPD gal/ GPD gal/ GPD gal/ GPD Total 61,880 GPD a See 15A NCAC 02T 0114(b) (d) (e)(I) and (e)(2) for caveats to wastewater design flow rates (i.e., minimum flow per dwelling; proposed unknown non-residential development uses; public access facilities located near high public use areas; and residential property located south or east of the Atlantic Intracoastal Waterway to be used as vacation rentals as defined in G.S. 42A-4). b Per 15A NCAC 02T .0114(c), design flow rates for establishments not identified [in table 15A NCAC 02T.01 141 shall be determined using available flow data, water using fixtures, occupancy or operation patterns, and other measured data. 8. Wastewater generated by project: 61 880 GPD (per 15A NCAC 02T .0114) i Do not include future flows or previously permitted allocations If permitted flow is zero, indicate why: ❑ Pump Station or Gravity Sewer where flow will be permitted in subsequent permits that connect to this line ❑ Flow has already been allocated in Permit Number: ❑ Rehabilitation or replacement of existing sewer with no new flow expected ❑ Other (Explain): FORM: ETA 04-16 Page 2 of 5 VIL GRAVITY SEWER DESIGN CRITERIA (if Applicable) - 02T .0305 & MDC (Gravity Sewers): 1. Summarize gravity sewer to be permitted: Size (inches) Length (feet) Material 8 7,864.10 PVC 8 160.00 DIP ➢ Section II & III of the MDC for Permitting of Gravity Sewers contains information related to design criteria ➢ Section III contains information related to minimum slopes for gravity sewer(s) ➢ Oversizing lines to meet minimum slope requirement is not allowed and a violation of the MDC VII1. PUMP STATION DESIGN CRITERIA (If Applicable) — 02T .0305 & MDC (Pump Stations/Force Mains): COMPLETE FOR EACH PUMP STATION INCLUDED IN THIS PROJECT 1. Pump station number or name: Sunset Estates 2. Approximate Coordinates (Decimal Degrees): Latitude: 34.1175' Longitude:-78.1249' 3. Design flow of the pump station: 0.0658 millions gallons per day (firm capacity) 4. Operational point(s) of the pump(s): 490 gallons per minute at 124 feet total dynamic head (TDH) 5. Summarize the force main to be permitted (for this Pump Station): Size (inches) Length (feet) Material 6 4,524 PVC 6 67 DIP 8 (Directional Drill) 356 HDPE 6. Power reliability in accordance with 15A NCAC 02T .0305(h)(1): qOk ® Standby power source or pump with automatic activation and telemetry - 15A NCAC 02T .0305(h)(1)(B)_ ➢ Required for all pump stations with an average daily flow greater than or equal to 15,000 gallons per day ➢ Must be permanent to facility Or if the pump station has an average daily flow less than 15,000 gallons per day: ❑ Portable power source with manual activation, quick -connection receptacle and telemetry - 15A NCAC 02T .0305(h)(1)(C) or ❑ Portable pumping unit with plugged emergency pump connection and telemetry - 15A NCAC 02T .0305(h)(1)(C): ➢ It shall be demonstrated to the Division that the portable source is owned or contracted by the applicant (draft agreement) and is compatible with the station. ➢ If the portable power source or pump is dedicated to multiple pump stations, an evaluation of all the pump stations' storage capacities and the rotation schedule of the portable power source or pump, including travel timeframes, shall be provided in the case of a multiple station power outage. FORM: FTA 04-16 Page 3 of 5 IX. SETBACKS & SEPARATIONS - (02B .0200 & 15A NCAC 02T.0305(f)): 1. Does the project comply with all separations found in 15A NCAC 02T.0305(f) & W ➢ 15A NCAC 02T.0305(f) contains minimum separations that shall be provided for sewer systems: ® Yes [-]No Setback Parameter* Separation Required Storm sewers and other utilities not listed below (vertical) I$ 24 inches Water mains (vertical -water over sewer including in benched trenches) 18 inches Water mains (horizontal) 10 feet Reclaimed water lines (vertical - reclaimed over sewer) 18 inches Reclaimed water lines horizontal - reclaimed over sewer) 2 feet **Any private or public water supply source, including any wells, WS-1 waters of Class 1 or Class II impounded reservoirs used as a source of drinking water 100 feet **Waters classified WS (except WS-I or WS-V), B, SA, ORW, HQW, or SB from normal high water (or tide elevation) and wetlands (see item IX.2) 50 feet **Any other stream, lake, impoundment, or ground water lowering and surface drainage ditches 10 feet Any building foundation 5 feet Any basement 10 feet Top slope of embankment or cuts of 2 feet or more vertical height 10 feet Drainage systems and interceptor drains 5 feet Any swimming pools 10 feet Final earth grade (vertical) 36 inches ➢ 15A NCAC 02T.0305(g) contains alternatives where separations in 02T.0305(f) cannot be achieved. ➢ **Stream classifications can be identified using the Division's NC Surface Water Classifications webnage ➢ If noncompliance with 02T.0305(fl or (g), see Section X of this application �asSi�i as W�- � 10 � w�Fiand7 c 2. Does the project comply with separation requirements for wetlands? (50 feet of separation) ® Yes ❑ No ❑ N/A ➢ See the Division's draft separation requirements for situations where separation cannot be meet ➢ No variance is required if the alternative design criteria specified is utilized in design and construction ➢ As built documents should reference the location of areas effected 3. Does the project comply with setbacks found in the river basin rules per 15A NCAC 0213.0200? ❑ Yes ❑ No ® N/A ➢ This would include Trout Buffered Streams per 15A NCAC 213.0202 4. Does the project require coverage/authorization under a 404 Nationwide or ® Yes ❑ No individual permits or 401 Water Quality Certifications? ➢ Information can be obtained from the 401 & Buffer Permitting Branch 5. Does project comply with 15A NCAC 02T.0 I 05(c)(6) (additional permits/certifications)? ® Yes [-]No Per 15A NCAC 02T.0105(c)(6), directly related environmental permits or certification applications are being prepared, have been applied for, or have been obtained. Issuance of this permit is contingent on issuance of dependent permits (erosion and sedimentation control plans, stormwater management plans, etc.). 6. Does this project include any sewer collection lines that are deemed "high -priority?" Per 15A NCAC 02T.04021 "high -priority sewer" means "any aerial sewer, sewer contacting surface waters, siphon, or sewer positioned parallel to streambanks that is subject to erosion that undermines or deteriorates the sewer. ❑ Yes ® No ❑ N/A ➢ If yes, include an attachment with details for each line, including type (aerial line, size, material, and location). High priority lines shall be inspected by the permittee or its representative at least once every six -months and inspections documented per 15A NCAC 02T.0403(a)(5) or the permitee's individual System -Wide Collection permit. FORM: FTA 04-16 Page 4 of 5 X. CERTIFICATIONS: I. Does the submitted system comply with 15A NCAC 02T, the Minimum Design Criteria for the Permitting of Pump Stations and Force Mains (latest version), and the Gravity Sewer Minimum Design Criteria (latest version) as applicable? ® Yes ❑ No If No, complete and submit the Variance/Alternative Design Request application (VADC 10-14) and supporting documents for review. Approval of the request is required prior to submittal of the Fast Track Application and supporting documents. 2. Professional Engineer's Certification: attest that this application for (Professional Engineer's name from Application Item Ill.1.) A(A,40ra Plate has been reviewed by me and is accurate, complete and consistent with the information supplied in the plans, specifications, engineering calculations, and all other supporting documentation to the best of my knowledge. I further attest that to the best of my knowledge the proposed design has been prepared in accordance with the applicable regulations, Gravity Sewer Minimum Design Criteria for Gravity Sewers (latest version), and the Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains (latest version). Although other professionals may have developed certain portions of this submittal package, inclusion of these materials under my signature and seal signifies that I have reviewed this material and have judged it to be consistent with the proposed design. NOTE — In accordance with General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may include a fine not to exceed $10,000, as well as civil penalties up to $25,000 per violation. North Carolina Professional Engineer's seal, signature, and date: `gt��gii �Z I�-2021 *• uc grtAl.' 03t~232 ; 3. Applicant's Certification per 15A NCAC 02T .0106(b): 1, W i 1 I i n L Y 1`n n i X� V t U N ( D'I C n a i r01 attest that this application for (Signature Authority's nam & title from Application Itena I.3.) Awo/a P I ace has been reviewed by me and is accurate and complete to the best of my knowledge. I understand that if all required parts of this application are not completed and that if all required supporting documentation and attachments are not included, this application package is subject to being returned as incomplete. I understand that any discharge of wastewater from this non - discharge system to surface waters or the land will result in an immediate enforcement action that may include civil penalties, injunctive relief, and/or criminal prosecution. I will make no claim against the Division of Water Resources should a condition of this permit be violated. I also understand that if all required parts of this application package are not completed and that if all required supporting information and attachments are not included, this application package will be returned to me as incomplete. NOTE — In accordance with General Statutes 143-215.6A and 143-215.613, any person who knowingly makes any false statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may include a fine not to exceed $10 000 as well as civil penalties up to $25,000 per violation. Signature: Ulu , 1 %>j P� Date: 3— FORM: FTA 04-16 Page 5 of 5 State of North Carolina i)n t,ioii ui Ct.t�n•r 1(r �, i. i:rc r, Department of Environmental Quality Division of Water Resources Flow Tracking for Sewer Extension Applications (FTSE 10-18) Entity Requesting Allocation: Brunswick County Public Utilities Project Name for which flow is being requested: Aurora Place More than one FTSE nray be required for a single project if the owner of the WWTP is not responsible for all pump stations along the route of the proposed wastewater flow. I. Complete this section only if you are the owner of the wastewater treatment plant. a. WWTP Facility Name: WEST BRUNSWICK WWRF b. WWTP Facility Permit #: WQ 0023693 c. WWTP facility's permitted flow d. Estimated obligated flow not yet tributary to the e. WWTP facility's actual avg. flow f. Total flow for this specific request g. Total actual and obligated flows to the facility It. Percent of permitted flow used All flows are in MGD 6.000 WWTP 0.1368 3.507 0.06188 3.705 61.7% II. Complete this section for each pump station you are responsible for along the route of this proposed wastewater flow. List pump stations located between the project connection point and the WWTP: (A) (B) (C) (D)=(B+C) (E)=(A-D) Design Average Approx. Obligated, Pump Pump Daily Current Not Yet Total Current Station Station Firm Flow** Avg. Daily Tributary Flow Plus (Name or Pennit Capacity, * (Finn / pt), Flow, Daily Flow, Obligated Available Number) No. MGD MGD MGD MGD Flow Capacity*** Bolivia WQ0016490 0.6048 0.2420 0.0044 0.1852 0.t896 0.0524 * The Firm Capacity (design flow) of any pump station is defined as the maximum pumped flow that can be achieved with the largest pump taken out of service. ** Design Average Daily Flow is the firm capacity of the pump station divided by a peaking factor (pf) not less than 2.5, per Section 2.02(A)(4)(c) of the Minimum Design Criteria. *** A Planning Assessment Addendum shall be attached for each pump station located between the project connection point and the WWTP where the Available Capacity is < 0. Downstream Facility Name (Sewer): Ric&Creek Forcemain Downstream Permit Number: WQ0032674 Page I of 6 FTSE 10-18 III. Certification Statement: I William L. Pinnix, P.E. certify to the best of my knowledge that the addition of the volume of wastewater to be permitted in this project has been evaluated along the route to the receiving wastewater treatment facility and that the flow from this project is not anticipated to cause any capacity related sanitary sewer overflows or overburden any downstream pump station en route to the receiving treatment plant under normal circumstances, given the implementation of the planned improvements identified in the planning assessment where applicable. This analysis has been performed in accordance with local established policies and procedures using the best available data. This certification applies to those items listed above in Sections I and Il plus all attached planning assessment addendums for which I am the responsible party. Signature of this form certifies that the receiving collection system or treatment works has adequate capacity to transport and treat the proposed new wastewater. Signing Official Signature D I )< t E, I rLK Title of Signing Official 311►P,ozl Date Page 2 of 6 FTSE 10-18 _BELL SWAMP 125 L-25- PROPOSED SUNSET ESTATES �-• �f1 _ _/`' PUMP STATION i _. -� PROPOSED 8"- PUBLIC GRAVITY -- SEWER MAIN PROPOSED�� 6" PUBLIC -- FORCE MAIN \ I A USGS QUADRANGLES '� 7 BOLIVIA, NC & DOWNSTREAM CONNECTION POINT FUNSTON, NC 2016 i (EX. 16" FM)-- SCALE: 1"=600' (APPROX.) THIS IS NOT A SURVEY. `