HomeMy WebLinkAboutWQCS00123_Compliance Evaluation Inspection_20210324ROY COOPER
Governor
M[CHAEL 5. REGAN
secretary
S. DANIEL SMITH
Director
Amanda Berger
Aqua North Carolina Inc
202 Mackanan Ct
Cary, NC 27511-6447
NORTH CAROLINA
En viraru ien tar Quality
March 18, 2021
SUBJECT: Compliance Inspection Report
Woodlake Country Club Collection System
Collection System Permit No. WQCS00123
Moore County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Woodlake Country Club
Collection System on 3/17/2021. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in Collection System Permit No. WQCS00123.
The findings and comments noted during this inspection are provided in the enclosed copy of the
inspection report entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
The Woodlake Country Club Collection System is run by knowledgeable personnel with excellent record
Keeping. Improvement plans such as a Main Line Repair Schedule were readily available in addition to
maintenance logs and maps in ArcGIS format. The inspected pump stations were orderly operating properly.
All 12 duplex stations within the system are equipped with SCADA, and was functional for each of the
stations inspected. If pump alarms are triggered, there is a second light on all pumps that flashes, signaling
that SCADA has been activated to call/text staff.
DE
Nora. ti.a rj . r.. a Department of E n v roamer. ta: Q o-a :ty I Q :v s5a r. of Water Resources
Fa}ettev e Aeg:ora Off a 1225 Greer, Street, 5ute 714 I Fayetter;ie, North £sroEra 23301
91.7.-433-33
If you should have any questions, please do not hesitate to contact Danielle Simpson with the Water
Quality Regional Operations Section in the Fayetteville Regional Office at 910-433-3300 or via email at
danielle.simpson@ncdenr.gov.
Sincerely,
—Doc_uSiggnnedd by: Q
-5189C2D3DD5C42B...
J. Trent Allen, Regional Supervisor
Water Quality Regional Operations Section
Fayetteville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: WQS Fayetteville Regional Office (DS)
PERCS Compliance/Enforcement Unit
North CarolinaDepart anentofEnvironments] Qu ity I Division of Water Resources
Fayetteville Regional Off 1225 Green St reet, Suite 714 I Fayetteville, North Cafofma 28301
910-4333300
DocuSign Envelope ID: 8173B525-33D5-4E63-BE80-BA2B452F2FB3
Compliance Inspection Report
Permit: WQCS00123
SOC:
County: Moore
Region: Fayetteville
Effective: 05/02/18 Expiration: 03/31/26
Effective: Expiration:
Owner : Aqua North Carolina Inc
Facility: Woodlake Country Club Collection System
202 Mackanan Ct
Contact Person: Amanda Berger Title: Compliance Manager
Directions to Facility:
System Classifications: CS2,
Primary ORC: Jonathan Daniel Odom
Secondary ORC(s):
James Garvin Williams
On -Site Representative(s):
Related Permits:
Certification: 1008946
1009291
NC0061719 Aqua North Carolina Inc - Woodlake Country Club WWTP
Inspection Date: 03/17/2021
Primary Inspector: Danielle SiSig mped ysor
ocu
Secondary Inspectors):
'-A99 04FAED5. 494
Stepp teD Ia ed by:
Reason for Inspection: Routin
Rt6yuglebg.9445AM
10.14,v6eHe U� ovL
"-8C7638281DAB46D...
3/24/2021
Cary NC 275116447
Phone: 919-653-6965
Phone: 919-710-2074
910-783-6817
Exit Time: 12:30PM
3/18/2021 Phone: 910-433-3334
3/18/2021
Inspection Type: Collection System Inspect Non Sampling
'-9C DC42
Permit Inspection Type: Collection518
syste3mDD5manBagement and operation
Facility Status: Compliant
Question Areas:
▪ Miscellaneous Questions
II Capital Improvement Plan
▪ Inspections
▪ Lines
(See attachment summary)
Not Compliant
▪ General
▪ Map
▪ Spill Response Plan
▪ Manholes
▪ Sewer & FOG Ordinances
▪ Reporting Requirements
▪ Spills
▪ Pump Stations
Page 1 of 7
DocuSign Envelope ID: 8173B525-33D5-4E63-BE80-BA2B452F2FB3
Permit: WQCS00123 Owner - Facility:Aqua North Carolina Inc
Inspection Date: 03/17/2021
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
Inspection Summary:
The Woodlake Country Club Collection System is run by knowledgeable personnel with excellent record keeping and
documented maintenance. As a private collection system they go above and beyond by having detailed improvement plans
such a main line repair schedule. Detailed maps of the sewer system are in ArcGIS format.
Weekly inspections and functionality tests are run on each pump station. There is also documentation of previous camera
inspections, smoke tests, CCTV inspections/pipe cleaning. Recently, one of the HPLs for this system was bored under the
lake. Any updates to HPLs are reflected in GIS accordingly. The spill response plan includes information such as 24-hour
contact numbers, cleanup and mitigation procedures, access to contractors, response time, and spill assessment
guidelines.
Right-of-ways and aerial lines were all maintained with no visible issues. Gravity sewer cleaning and jetting were organized,
with 10,970.4 feet being cleaned in 2020. Manholes appeared in good order with no signs of depressions or overflows
surrounding them. There was a bit of debris in the manhole across from lift station #10 (Daphne), potentially due to low flow,
but is worth keeping an eye on. Several lift stations were inspected and all were in good working order. All 12 duplex
stations within the system are equipped with SCADA, and was functional for each of the stations inspected. If pump alarms
are triggered, there is a second light on all pumps that flashes, signaling that SCADA has been activated to call/text staff.
Page 2 of 7
DocuSign Envelope ID: 8173B525-33D5-4E63-BE80-BA2B452F2FB3
Permit: WQCS00123 Owner - Facility:Aqua North Carolina Inc
Inspection Date: 03/17/2021
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
General
Is there a properly designated primary ORC and at least one back-up of proper grade?
Are logs being reviewed by the system management or owner on a regular basis?
# What is that frequency?
# Are there any issues being addressed currently or any in the planning stages?
Is there a specific pump failure plan available for all pump stations?
Does plan indicate if pump parts/new pumps are in spare parts/equipment inventory?
Are new/significantly upgraded pump stations equipped with anti -corrosion materials?
Does the permittee have a copy of their permit?
# Is permit expiring within the next 6 months?
If Yes, has the Permittee applied for renewal?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Weekly basis
▪ ❑ ❑ ❑
❑ ❑ • ❑
• ❑ ❑ ❑
❑ • ❑ ❑
❑ ❑ • ❑
Comment: The permit expires on 03/31/2026. There have not been any new or significantly upgraded pump
stations recently added. Spare parts and equipment are inventoried with a designated contractor
Sewer and FOG Ordinances
Is Sewer Use Ordinance (SUO) or other Legal Authority available?
Does it appear that the Sewer Use Ordinance is enforced?
Is there a Grease Control Program that legally requires grease control devices?
What is the standard grease trap cleaning requirement in the FOG ordinance?
Is Grease Control Program enforced via periodic inspections/records review?
Is action taken against violators?
# Have satellite systems adopted an equivalent or more stringent ordinance?
Is grease/sewer education program documented with req'd customer distribution?
# Are other types of education tools used like websites, booths, special meetings, etc?
If Yes, what are they? (This can reduce mailing to annual.)
Website
Comment: Noncompliance/violators will ultimately lead to increased sewer costs for all residents.
Capital Improvement Plan
Has a Capital (CIP) or System Improvement Plan been developed and adopted?
Is it designated for wastewater only or does it have a dedicated section?
Does CIP cover three to five year period of earmarked improvements?
Does CIP include description of project area?
Does CIP include description of existing facilities?
Does CIP include known deficiencies?
Does CIP include forecasted future needs?
Comment: Documentation of plans and upgrades, as well as a main line repair schedule.
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ • ❑ ❑
N/A
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
❑ ❑ • ❑
❑ ❑ • ❑
Page 3 of 7
DocuSign Envelope ID: 8173B525-33D5-4E63-BE80-BA2B452F2FB3
Permit: WQCS00123 Owner - Facility:Aqua North Carolina Inc
Inspection Date: 03/17/2021
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
Map
Is there a overall sewer system map?
Does the map include:
Pipe Type (GS/FM)
Pipe sizes
Pipe materials (PVC, DIP, etc)
Pipe location
Flow direction
Approximate pipe age
Pump station ID, location and capacity
# Force main air release valve location & type
# Location of satellite connections
Is the map being updated for changes/additions within 1 year of activation?
Comment: ArcGIS is used for sewer system mapping.
Reporting Requirements
# Have there been any sewer spills in the past 3 years?
If Yes, were they reported to the Division if meeting the reportable criteria?
If applicable, is there documentation of press releases and public notices issued?
Is an Annual Wastewater Performance Report being filed with the Division, if required?
Is the report being made available to all its sewer customers?
# How is it being made available?
Comment: There have not been any sewer spills in the past three years.
Inspections
Are adequate maintenance records maintained?
Are pump stations being inspected at the required frequency?
# Is at least one complete functionality test conducted weekly per pump station?
Is there a system or plan in place to observe the entire system annually?
Is the annual inspection documented?
# Does the system have any high -priority lines/locations?
Are inspections of HPL documented at least every 6 months?
Are new lines being added to the HPL list when found or created?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
• ❑ ❑ ❑
Yes No NA NE
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
N/A
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: HPLs are inspected weekly. When found or created, new lines are added to the HPL list regularly
via updates in ArcGIS. Pump stations are inspected weekly with a complete functionality test,
documented on logs found at each pump station.
Spill Response Action Plan
Is a Spill Response Action Plan available?
Yes No NA NE
Page4of7
DocuSign Envelope ID: 8173B525-33D5-4E63-BE80-BA2B452F2FB3
Permit: WQCS00123 Owner - Facility:Aqua North Carolina Inc
Inspection Date: 03/17/2021
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
Is a Spill Response Action Plan available for all personnel?
Does the plan include:
24-hour contact numbers
Response time
Equipment list and spare parts inventory
Access to cleaning equipment
Access to construction crews, contractors, and/or engineers
Source of emergency funds
Site sanitation and cleanup materials
Post-overflow/spill assessment
Does the Permittee appear to respond within 2 hours of first knowledge of a spill?
Comment:
Spills
Is system free of known points of bypass?
If No, describe type of bypass and location
Are all spills or sewer related issues/complaints documented?
# Are there repeated overflows/problems (2 or more in 12 months) at same location?
# If Yes, is there a corrective action plan?
Comment: No repeated overflows/problems at the same location in the past 12 months.
Lines/Right-of-Ways/Aerial Lines
Please list the Lines/Right of Ways/Aerial Lines Inspected:
The HPLs were inspected, as well as several right-of-ways.
Are right-of-ways/easements maintained for full width for access by staff/equipment?
If No, give details on temporary access:
Is maintenance documented?
Are gravity sewer cleaning records available?
Has at least 10% of lines older than 5 yrs been cleaned annually?
Were all areas/lines inspected free of issues?
Comment: In 2020, 10,970 feet were cleaned/jetted.
Manholes
Please list the Manholes Inspected:
Several manholes were inspected throughout the inspection.
Are manholes accessible?
# Are manhole covers/vents above grade?
Are manholes free of visible signs of overflow?
Are manholes free of sinkholes and depressions?
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Page5of7
DocuSign Envelope ID: 8173B525-33D5-4E63-BE80-BA2B452F2FB3
Permit: WQCS00123 Owner - Facility:Aqua North Carolina Inc
Inspection Date: 03/17/2021
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
Are manhole covers present?
# Are manholes properly seated?
# Are manholes in good condition?
# Are inverts in good condition?
Is flow unrestricted in manholes?
Are manholes free of excessive amounts of grease?
Are manholes free of excessive roots?
Are manholes free of excessive sand?
Are manhole vents screened?
Are vents free of submergence?
Are manholes free of bypass structures or pipes?
Comment:
Pump Stations
Please list the Pump Stations Inspected:
Pump stations inspected include Woodlake #4, #5, #7, and #10 (Cranes Cove, River Birch, Applewood and
Daphne).
# Number of duplex or larger pump stations in system
# Number of vacuum stations in system
# Number of simplex pump stations in system
# Number of simplex pump stations in system serving more than one building
How many pump/vacuum stations have:
# A two-way "auto polling" communication system (SCADA) installed?
# A simple one-way telemetry/communication system (auto -dialer) installed?
For pump stations inspected:
Are they secure with restricted access?
Were they free of by-pass structures/pipes?
Were wet wells free of excessive grease/debris?
# Do they all have telemetry installed?
Is the communication system functional?
Is a 24-hour notification sign posted ?
Does the sign include:
Owner Name?
Pump station identifier?
# Address?
Instructions for notification?
24-hour emergency contact numbers?
Are audio and visual alarms present?
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
12
0
0
0
12
0
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page6of7
DocuSign Envelope ID: 8173B525-33D5-4E63-BE80-BA2B452F2FB3
Permit: WQCS00123 Owner - Facility:Aqua North Carolina Inc
Inspection Date: 03/17/2021
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
Are audio and visual alarms operable?
# Is there a backup generator or bypass pump connected?
If tested during inspection, did it function properly?
Is the back-up system tested at least bi-annually under normal operating conditions?
# Does it have a dedicated connection for a portable generator?
# Is the owner relying on portable units in the event of a power outage?
# If Yes, is there a distribution plan?
If Yes, what resources (Units/Staff/Vehicles/etc) are included in Plan?
All pump stations rely on portable generators in the event of a power outage. These generators are stored
with a local contractor until needed.
# Does Permittee have the approved percentage of replacement simplex pumps?
Is recordkeeping of pump station inspection and maintenance program adequate?
Do pump station logs include at a minimum:
Inside and outside cleaning and debris removal?
Inspecting and exercising all valves?
Inspecting and lubricating pumps and other equipment?
Inspecting alarms, telemetry and auxiliary equipment?
Comment: All pump stations rely on portable generators in the event of a power outage.
• ❑ ❑ ❑
❑ ❑ • ❑
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑