HomeMy WebLinkAboutWQCSD0630_Regional Office Historical File Pre 2018CLEVELAND COUNTY
H EALTH D EPARTMENT
tiOQCsfl O(030
c0/5 eo643
AdH
LEACHATE RELEASE DUE TO BROKEN PIPE LOCATED IN SERVICE ROAD THAT WAS BREACHED ON
SUNDAY, APRIL 19, 2015 BETWEEN THE HOURS OF 7:19 PM AND 7:30 AM MONDAY, APRIL 20,
2015. THIS TIME FRAME WAS DETERMINED BASED ON OUR DATA SHOWING AN INCREASE IN
FLOW DUE TO NO RESISTANCE OF HEAD PRESSURE IN THE FORCE MAIN.
Time: 7:30 AM, April 20, 2015 pump turned off.
Time: 7:59 AM, April 20, 2015 leachate line capped off.
Time: 9:00 AM, April 20, 2015 reconstruction of service road began.
Time: 8:50 AM, April 21, 2015 the pipe replacement began.
Time: 7:30 PM, April 21, 2015 Leachate line was repaired.
Time: 9:00 AM, April 22, 2015 the leachate line was re -pressured for test, no leaks were detected.
Time: 10:19 AM, April 22, 2015 the pumping system was turned back on and set for automaticrelease
schedule determined by the City of Shelby's Waste Treatment Department. `�)G OO�Y`J33?
Time: 1:30 PM, April 22, 2015 service road installation and leachate repair completed.
FACTS:
• RAINFALL DATA FROM 4-17-2015 TO 4-20-2015 IS 4.5 INCHES OF RAIN RECORDED
• ESTIMATED GALLONS OF LEACHATE RELEASED 18,937.95
• ENCLOSED YOU WILL FIND PHOTOS TO SUPPORT THIS REPORT
SUBMITTED APRIL 30, 2015 BY Sam M. Lockridge, III SOLID WASTE DIRECTOR
Connecting the Best
�.-s of the Carolinas
++ ° jf\ir'
315 E. Grover St. • Shelby, NC 28150-`3998 (704) 484-5100 • Fax (704) 484-5220
A
k
A
r
1
vato-r,iikk. •e"
ir r .{ �J i h. e�
f
• *i: i ,, i
.163
.13
1
Airport Road LancriH at Road WASHOU1
fit
o Qleearth miles
krn
A
Cleveland County, NC Piint Map
Page 1 d 1
Cleveland County, NC
pfscjalMer: The information contained on this,page is taken from aerial mapping. fax mapping„,andpuplie records and is NOT to be censtruecf or
used .aa a survey or legal description', Only a licensed professional land suryeyOr can legally cletermine'preciselocations, elevations, length and
directionof a line, and areas.
Google Maps
Page 1 of 1
Googie
This version of Google Maps is updating soon. Le arn-FAIMeDilartidP details that are visible on the
screen,..use_the l'Print" link next to the map.
awzra-th,----.77-crcer,-Rracrtrelrust.r9x e
Department
:DLzer Ritx;.'14 Dr
, Challenger 3 Golf
• Amuse.rnent Park
?ie,ccvs
- -fir4oti
Bf.r cr+
Cer.
iigas 1, •
2s,
114371
119371
•
0
Case Farms
Feed Mill
Cleveland
County Landfill
„.09ort
Cleveland County,
Animal Shelter.'—
.•
. ,
Map data at,;915 Goolire - 41,
https://maps.google.com/maps?ris=com.mierosoft:en-us:IE-SearchBox&oe&gws_rd—ss18‘... 4/23/2015
State of North Carolina
Department of Environment
and Natural Resources
Division of Water Quality
James B. Hunt, Jr., Governor
Bill Holman, Secretary
Kerr T. Stevens, Director
May 9, 2000
R.L. Alexander, County Manager
Cleveland County Health Department
315 E. Grover Street
Shelby, North Carolina 28150-3998
Dear Mr. Alexander:
AVA
NCDENR
NORTH CAROL! NA DEPARTMENT OF
ENVIRONMENT AND N7Tu.:'.FM;E)„URCES
+:``'t'., "? fit'.,:'' _irJR':s��'F;=J
NAY R,0 2000
Subject: Permit No. WQ0017771
Animal Shelter and Leachate
Pump Station
Cleveland County Health
Department
Wastewater Collection System
Cleveland County
In accordance with your application received December 9, 1999, and additional information received
January 10, 2000, March 13, 2000, April 4, 2000, April 18, 2000, April 24, 2000, May 2, 2000, and May 5,
2000, we are forwarding herewith Permit No. WQ0017771 dated May 9, 2000, to the Cleveland County
Health Department for the construction and operation of the subject wastewater collection extension. This
permit shall be effective from the date of issuance until rescinded and shall be subject to the conditions and
limitations as specified therein.
Please note that if any other sewer connections other then the one contained within this permit are
made to the two-inch line servicing the Mabry property, then the line becomes a pressure sewer and must be
permitted by. the Division. This includes single building "taps" or any other pressure line connections. When
an additional tie is made to this two-inch line is needed please submit PSSA 10/99 or later pressure sewer
application as a modification to this permit. Please pay special attention to Condition 15 in which the
Division is requiring a clean -out be placed at the end of two-inch line servicing the Mabry property, since the
two feet per second velocity requirement is not met by the submitted design. Condition 16 requires both the
leachate and the animal shelter pump station be equipped with the following safety devices: audible and visual
high water alarms, and telemetry for each pump station. The Permittee and the Design Engineer is reminded
of Permit Condition 11.e. which requires three feet of cover for all force mains and sewers permitted herein.
Permitting of this project does not constitute an acceptance of any part of the plans and specifications
that do not meet 15A NCAC 2H .0200 and the Division of Water Quality's Gravity Sewer Minimum Design
Criteria adopted February 12, 1996 unless specifically mentioned herein. Division approval is based on the
acceptance of the certification provided by a N.C. Professional Engineer on Page 6 -of the subject permit
application form. It shall be the permittee's responsibility to ensure the plans and specifications meet the
appropriate design criteria and rules. Failure to comply may result in penalties in accordance with North
Carolina General Statute 143-215.6A — 143-215.6C, construction of additional facilities, and/or referral of the
N.C. Professional Engineer to the licensing board.
1617 Mail Service Center, Raleigh, North Carolina 27699-1617 Telephone (919) 733-5083 Fax (919) 715-6048
An Equal Opportunity Affirmative Action Employer 50% recycled/10% post -consumer paper
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
RALEIGH
WASTEWATER COLLECTION PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as amended,
and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
CLEVELAND COUNTY HEALTH DEPARTMENT
Cleveland County
FOR THE
construction and operation of approximately 284 linear feet of eight -inch gravity sewer, a 12.8-GPM pump station
with duplex pumps which must operate simultaneously, on -site audible and visual high water alarms external to
any structure, an autodialer, a portable generator, a manual transfer switch and approximately 1,300 linear feet of
two-inch force main to serve the Animal Shelter;
a 45-GPM pump station with a single pump, on -site audible and visual high water alarms external to any
structure, an autodialer, and approximately 7,600 linear feet of three-inch force main to serve the Leachate Pump
Station;
a 12-GPM pump station with a simplex pump, on -site audible and visual high water alarms external to any
structure, 24 hours of wastewater storage, and approximately1,450 linear feet of two-inch force main with clean
outs and , and approximately 1000 linear feet of 1.5-inch force main with water tight ferrous encasement pipe for
all pipe without a bury depth of 36-inches that is not ferrous itself to serve a single residence on property of
Franklin Mabry;
the discharge of 18,910 GPD of collected domestic and leachate wastewater into the City of Shelby's existing
sewerage system, pursuant to the application received December 9, 1999, and in conformity with the project plan,
specifications, and other supporting data subsequently filed and approved by the Department of Environment and
Natural Resources and considered a part of this permit.
This permit shall be 'effective from the date of issuance until rescinded and shall be subject to the following
specified conditions and limitations:
1. This permit shall become voidable unless the facilities are constructed in accordance with the conditions of
this permit, 15A NCAC 2H .0200, the Division of Water Quality's Gravity Sewer Minimum Design
Criteria adopted February 12, 1996, the approved plans and specifications, and other supporting data unless
specifically mentioned herein.
2. This permit is effective only with respect to the nature and volume of wastes described in the application
and other supporting data.
3. The facilities must be properly maintained and operated at all times.
1