Loading...
HomeMy WebLinkAboutWQCSD0258_Regional Office Historical File Pre 2018FIL ROY COOPER Cover -riot MICHAEL S. REGAN Secretary S. DANIEL SMITH Director NORTH CAROLINA Environmental Quality CERTIFIED MAIL #: 7018 0360 0002 2099 8184 RETURN RECEIPT REQUESTED July 21, 2020 Clarissa Jennings -Reid, Mayor Town of Kingstown 2014 Kingston Rd Kingstown, NC 28150 SUBJECT: NOTICE OF VIOLATION Tracking Number: NOV-2020-DV-0254 Sanitary Sewer Overflows - April 2020 Collection System Permit No. WQCSD0258 Kingstown Collection System Cleveland County Dear Mrs. Reid: The self -reported Sanitary Sewer Overflow (SSO) 5-Day Report submitted by Town of Kingstown indicates violations of permit conditions stipulated in the subject permit and North Carolina G.S. 143-215.1. Violations include failing to effectively manage, maintain, and operate the subject collection system so that there is no SSO to the land or surface waters and making an outlet to waters of the State for purposes of G.S. 143-215.1(a)(1), for which a permit is required. Specific incident(s) cited in the subject report include the following: Incident Start Duration Number Date (Mins) Location Cause Total Vol Total Surface Vol Water (Gals) (Gals) DWR Action 202001285 4/30/2020 75 1023 West Zion Church Road/Kingstown Pump Station Inflow and Infiltration 1,125 1,125 Notice of Violation �E�J e3' a' =- _ J =_>. i ;a-n: 1 ete.-s.e_-• _ _ �..' ��tt i ��' Darter Site"^1 I t.'- .r.•• _rc• 115 A Remedial actions, if not already implemented, should be taken to correct the above noncompliance. Please submit a written response to this Notice of Violation. Your response is to be received by the regional office within 60 business days following receipt of this violation. Please include any additional documentation about this incident(s) in the response. The submittal will be considered in determining whether the Division will assess a civil penalty for the cited violations. If you have any questions, please do not hesitate to contact Michael Meilinger or me with the Water -Quality Section -`"" ''" ' "^ --via email at michael.meilinger@ncdenr.gov or c0 p^ O ru rU :..n m c0 o to rt a) Q. tD 33J IO 1VNOI938 317lASIrO SOaOM f OZOZ S 0 ES aMalaN300NICI3A1303 0 0 r.: r r— rn Z fl z i z N 0.1 0 rr: m Z —o (-n O U.S. Postal Service! CERTIFIED MAIL° RECEIPT ' Domestic Mail Only co .30 oM For de(liivve}ry information, visit our website at www.usps.come. Certified Mail Fee-./// 5 $ Extra Services & Fees (check box, add ;teas appropriate) ❑ Retum Receipt (hardcopy) $ ❑ Retum Receipt (electronic) $ ❑certified Mall Restricted Delivery $ ['Adult Signature Required $ [(Adult Signature Restricted Delivery $ $' Clarissa Jennings -Reid, Mayor Town of Kingstown 2014 Kindston Rd. g Kingstown, NC 28105 NOV-2020-DV-0254 WOCSD0250 PS Form 3800, April 2015 PSN 7530-02-000-9047 N Imo, Postmark Here ligned by: '681 AF27425... Basinger, Regional Supervisor ality Regional Operations Section le Regional Office f Water Resources, NCDEQ See Reverse for Instructions Ds.sR^`e .:f C. y^.^.e. .3 .Le t'. I ., vs:r. C,.6 � es:'7es Reg _. _ �'fr I c1- _63 Ce .c`.. errs. ... to ? 1 r•', .-�. =. N.:r:r r E .=ii� FILE ROY COOPER Governor MICHAEL S. REGAN Secretor S. DANIEL SMITH NORTH CAROLINA Director Environmental Quality CERTIFIED MAIL #: 7016 1370 0000 2592 0577 RETURN RECEIPT REQUESTED May 21, 2020 Clarence Withrow, Mayor Town of Kingstown 2014 Kingston Rd Kingstown, NC 28150 SUBJECT: NOTICE OF VIOLATION Tracking Number: NOV-2020-DV-0254 Sanitary Sewer Overflows - April 2020 Collection System Permit No. WQCSD0258 Kingstown Collection System Cleveland County Dear Mr. Withrow: The self -reported Sanitary Sewer Overflow (SSO) 5-Day Report submitted by Town of Kingstown indicates violations of permit conditions stipulated in the subject permit and North Carolina G.S. 143-215.1. Violations include failing to effectively manage, maintain, and operate the subject collection system so that there is no SSO to the land or surface waters and making an outlet to waters of the State for purposes of G.S. 143-215.1(a)(1), for which a permit is required. Specific incident(s) cited in the subject report include the following: Incident Start Duration Number Date (Mins) Location Cause Total Vol Total Surface Vol Water (Gals) (Gals) DWR Action 202001285 4/30/2020 75 1023 West Zion , Inflow and Infiltration 1,125 1,125 Notice of Violation Church Road/Kingstown Pump Station Nert Cn o' 3 Department pfEnvronrneht C,? ha?rLy I D- on of Water Rey Ur..- - I•°var__r ._ R'- -'e Dfc- I c10 Ear tenter Avenu_.5o,t_ 301 I Moo :a.r:,_, rth zro'inz 22;115 Remedial actions, if not already implemented, should be taken to correct the above noncompliance. Please submit a written response to this Notice of Violation. Your response is to be received by the regional office within 60 business days following receipt of this violation. Please include any additional documentation about this incident(s) in the response. The submittal will be considered in determining whether the Division will assess a civil penalty for the cited violations. If you have any questions, please do not hesitate to contact Michael Meilinger or me with the Water Quality Section in the Mooresville Regional Office at 704-663-1699 or via email at michael.meilinger©ncdenr.gov or corey.basinger@ncdenr.gov. r- r- 0 U.S. Postal Service"' CERTIFIED MAIL° RECEIPT Domestic Mall Only For delivery information, visit our website at www.us om®. F ] C A L USE Certified Mall Fee Extra Services & Fees (check box, add fee as appropriate) ❑ Retum Receipt (hardcopy) $ ❑ Retum Receipt (electronic) $ ❑Certified Mall Restricted Delivery $ Adult Signature Required $ Adult Signature Restricted Delivery $ Postage Tot $ Set uP'ttE Ciry IUWIV VrtklIVbJIUV 2014 KINGSTON ROAD KINGSTOWN NC 28150 ATTN: CLARENCE WITHROW, MAYOR Dwr/mm 5/21/2020 PS Form 3800, April 2015 PSN7530-02-000-9047 at 7_ ,- v. Cl. ECEIVEDINCDCPaRiD Gv CO It PI na See Reverse for Instructions WQROS OFFICE tJ ESVILLE REGIONAL O to to ort y: for I4A3... isinger, Regional Supervisor ty Regional Operations Section Regional Office Vater Resources, NCDEQ ND at., Cars ;na u partnt nt of En, ronrrer, s+^u I D'v=_nn oflWater Resauro s r esv :eR_5one'Gaff.,_ 1610caCenter 301I r sv o.NorthCaroiine28115 704-SC3-169 9 ROY COOPER Governor MICHAEL S. REGAN Secretnry S. DANIEL SMITH Director srArE • NORTH CAROLINA Environmental Qualify CERTIFIED MAIL #: 7018 0360 0002 2099 7965 RETURN RECEIPT REQUESTED April 22, 2020 Clarence Withrow, Mayor Town of Kingstown 2014 Kingston Rd Kingstown, NC 28150 SUBJECT: NOTICE OF VIOLATION Tracking Number: NOV-2020-DV-0152 Sanitary Sewer Overflows - February 2020 Collection System Permit No. WQCSD0258 Kingstown Collection System Cleveland County Dear Mr. Withrow: FILE The self -reported Sanitary Sewer Overflow (SSO) 5-Day Report submitted by Town of Kingstown indicates violations of permit conditions stipulated in the subject permit and North Carolina G.S. 143-215.1. Violations include failing to effectively manage, maintain, and operate the subject collection system so that there is no SSO to the land or surface waters and making an outlet to waters of the State for purposes of G.S. 143-215.1(a)(1), for which a permit is required. Specific incident(s) cited in the subject report include the following: Incident Start Duration Number Date (Mins) Location Cause Total Vol Total Surface Vol Water (Gals) (Gals) DWR Action 202000458 2/6/2020 290 1623 W Zion Church Severe Natural 12,700 12,700 Notice of Violation Rd (Kingstown LS) Condition Severe Natural Condition e c _.3 ..ff _=a ,.enter _. i;._.... :3r_. u Remedial actions, if not already implemented, should be taken to correct the above noncompliance. Please submit a written response to this Notice -of Violation. Your response is to be received by the regional office within 60 business days following receipt of this violation. Please include any additional documentation about this incident(s) in the response. The submittal will be considered in determining whether the Division will assess a civil penalty for the cited violations. If you have any questions, please do not hesitate to contact Michael Meilinger or me with the Water Quality Section in the Mooresville Regional Office at 704-663-1699 or via email at michael.rneilinger©ncdenr.gov or corey.basinger@a ncdenr.gov. IT' ru ru D o o ,o ,r9 a f` 0 0 Sincerely, cuSigned by: o ru • U) ru Ul 'U.S. Postal Service"' CERTIFIED MAIL° RECEIPT Domestic Mail Only For delivery information, visit our website at www.usps.com®. FIIIA L U S E Extra Services & Fees (check box, add fee as appropriate) ❑ Retum Receipt (hardcopy) $ ['Return Receipt (electronic) $ ❑ Certified Mall Restricted Delivery $ ❑ Adult Signature Required $ ❑ Adult Signature Restricted Delivery $ Postage Tot s 8i City , ostrrhirk' TOWN OF KINGSTOWN 2014 KINGSTON ROAD KINGSTOWN NC 28150 ATTN: CLARENCE WITHROW, MAYOR Dwr/mm 4/22/2020 CC681 AF27425... !y Basinger, Regional Supervisor )uality Regional Operations Section fille Regional Office of Water. Resources, NCDEQ PS Form 3800, April.2015. PSN 7530-02-000-9047 See Reverse for Instructions DES, N,Drtr, :a.: na 7ecurtrne t :f Era roar.erta. Qi.a I D.•.:;•;n of Wutei ncaourc.s eF=',•,r; Dff_a3 E.e0terAverce._,te3::1I l.',=._a, _,N.:,rt.'. ter: 2°115 by /' '' • f r ar44' - ------1M-MCAC-O2T-:0403 - PERMITTING BY REGULATION Permittee: Awl. Trac!ding #: WQCSDO'7 g' Date: iko-,I.Ss . •POC Phone: POC: - (a) Collection systems having an actual, permitted or Division approved average daily flow less than 200,000 gallons per day are deemed permitted pursuant to Rule .0113 of this Subchapter provided the system meets the criteria in Rule .0113 of this Subchapter and all specific criteria required in this Rule: / rS �® . 5 ys r S .• S un` 7�� se., REMARKS' •• p (1) The sewer system is effectively maintained and operated at all times to prevent discharge to land or surface waters, and to prevent any contravention of groundwater standards or surface water standards. . f/ l co �.�� ��/' ` ", 14,0r l( toy (2) A map of the sewer system has been developed and is actively maintained . . (3) An operation and maintenance plan including. pump station inspection frequency., preventative maintenance • schedule, spare parts inventory and overflow response has been developed and implemented. - (4) Pump stations that are not connected to a telen etry system (Le., remote alarm system) are inspected by the permittee or its representative every day (i.e., 365 days per • year). Pump stations that are connected too telemetry system are inspected at least once per week.- ,/ fll// - . �U, d1/4r � ' - • j ✓ —01` reo1 (5) High -priority sewers are inspected by the permittee or its representative at least once every six-months.and inspections are documented. . . . . (6) A general observation by the permittee or its representative of the entire sewer system is conducted at least once per year. ✓• .. • - Overflows and bypasses are reported to -the appropriate Ct) yp P Division regional' office in accordance -with 15A NCAC 02B .0506(a), and public notice is provided as required by G_S. 143-215,1 C. . 1 i%Z • 3 Q) 5 f , a � � _� �-I�v ` � u�, .( - 1 -S F 0 7 � 0 9-4 A Grease Control Program is in place as follows` . 7� (A) For publicly owned collection systems, ttie Grease Control Program shall include at least bi-annual distribution of educational materials for both commercial and residential and .the legal means to require grease interceptors fore new construction and retrofit if necessary, of grease at existing establishments. The plan shall also include legal means for inspections of the grease _ interceptors; enforcement for violators and the legal means to control grease entering the system from other public and private satellite sewer systems. . V S P� f �, c T �� (,�0 . .I-S 10 54 . din, w �� l� • • I.users —(n . 6'interceptors IO c, (B) For privately owned collection systems, the Grease include least bi-annual distribufier • .• Control Program shall at grease education materials to users of the collection system by the or its representative. , . permittee (C) Grease education materials shall be.distributed more • often than required in Parts (A) and (B) of this Subparagraph if necessary to prevent grease -related sanitary sewer overflows. ./ v - - . • (9) Right-of-ways and easements are maintained in the full easement width for personnel and equipment accessibility. " GQ, I" of 4/— -e.., (10) Documentation shall be kept for Subparagraphs (a)(1) —__....i, I..vM nf+hie Pula fry a minimum of three years with - -#11 .q;C- lI 1720 -/kr9S Pump Station Inspection Checklist Name: • ii2,C Address: 2.ois Rai # Pumps - • Working Run Time - W.eather: . Signage: • YES NO Housekeeping: l.Secure: • Wet Well Floats: Debris:. Working High Water Float Telemetry: • SCADA: AudioNisual: Is alarm systeM tested, How often: • I.nspection Logs: Emergency Power Type: Portable • Juick Connect. nsite Fuel - G ScheduleNender - resting Schedule: 3ackflow: Nei -flow Piping: 3ypass Pumping: • nspection Schedule: omments/ ObserVations: dtvq/10- co)-(01/1 Pump Station InspeCtion Checklist Name: Kiv135,171wV\ S ' Address: C,23 7-iw avkiet-t. #Punlps - Working 1 2 2 Run rune - Weather: Signage: 'Housekeeping: ! .Secure: Wet Well Floats: Debris: . Working High Water Float telemetry:_. SCADA. • YES z NO AudioNisuat Is alarm system tested, How often: Inspection Logs: Emergency Power. Type: Portable • Duick Connect: .- resting Schedule: 3ackflow: t. Fuel -9'e,S4 Schedule/Vender - tiretk-1 )verflow Piping: 3ypass Pumping: nspection Schedule: ;omments/ Observations: ( 2018 Kingstown Sewer Records Report Sewer Line Maintenance & Repair- 0 in 2018 Preventative Maintenance- 1.7 miles in 2018 (18.4 % of Kingstown System) ROW Maintenance- 5.3 miles in 2018 Sewer Camera- 0 miles in 2018 Acoustic Testing- 0 miles in 2018 Manhole Inspections- 67 in 2018 Manhole Maintenance & Repair- 0 in 2018 2019 Kingstown Sewer Records Report (8.28.2019) Sewer Line Maintenance & Repair- 0 in 2019 Preventative Maintenance- 0.7 miles in 2019 (7.6 % of Kingstown System) ROW Maintenance- 5.1 miles in 2019 Sewer Camera- 0.2 miles in 2019 Acoustic Testing- 0 miles in 2019 Manhole Inspections- 140 in 2019 Manhole Maintenance & Repair- 0 in 2019 Water Resources Environmental Quality May 4, 2017 Mr. David Hux, Assistant Utilities Director City of Shelby Post Office Box 207 Shelby, North Carolina 28151-0207 Subject: Compliance Evaluation Inspection Permittee: Kingstown Collection System Permit No. WQCSD0258 Cleveland County Dear Mr. Hux: 1 ., ROY COOPER Governor MICHAEL S. REGAN Secretary S. JAY ZIMMERMAN Director '1. Mr. Barry Love of the Mooresville Regional Office of the NC Division of Water Resources (DWR or the Division) conducted a compliance evaluation inspection (CEI) of the Kingstown wastewater collection system (WWCS) on April 24, 2017. The assistance of all those present during the inspection was greatly appreciated. A copy of the inspection report is attached for your records and inspection findings are summarized below. Site/System Review 2. The following system components were inspected: a. Two pump stations were inspected with no problems being found. b. Four manholes were inspected with no problems being found. c. Two sections of right-of-way were inspected with no problems being found. 3. As you are aware, owners of deemed permitted collection systems must comply with all rules listed under NC Administrative Code 15A NCAC 02T .0400, et seq. Kingstown's compliance status with each of these rules is summarized below: a. 15A NCAC 02T .0403(a)(1): Requires that the system be effectively maintained and operated at all times to prevent discharge to land or surface waters and any contravention of ground or surface water standards. Observations: There have been no overflows in this system in the past several years. The last occurred on 07/1/2011 due to grease. This system appears to be well maintained and operated. Compliance Status: Compliant -=�Nothing Compares:=-.._r State of North Carolina i Environmental Quality I Water Resources I Water Quality Regional Operations Mooresville Regional Office 1610 East Center Avenue, Suite 301 i Mooresville, North Carolina 28115 704-663-1699 b. 15A NCAC 02T .0403(a)(2): Requires that a map of the wastewater collection system be developed and actively maintained. Observations: A copy of the map was available at the time of inspection. Compliance Status: Compliant c. 15A NCAC 02T .0403(a)(3): Requires that an operation and maintenance (O&M) plan be developed and implemented, which includes pump station inspection frequency, preventative maintenance schedule, spare parts inventory and overflow response. Observations: The system appeared to be well maintained with protocol set up to address any needs. Compliance Status: Compliant d. 15A NCAC 02T .0403(a)(4): Requires that the permittee or its representative inspect pump stations that are not connected to a telemetry system (i.e., remote alarm system) every day (i.e., 365 days per year) and pump stations that are connected to a telemetry system at least once per week. Observations: Records showed that both pump stations are inspected on a weekly basis and are well maintained. Compliance Status: Compliant e. 15A NCAC 02T .0403(a)(5): Requires that the permittee or its representative inspect high -priority sewers (HPS - as defined in 15A NCAC 02T .0402(2)) at least once every six months and document the inspections. Observations: There are no high -priority lines on this system. Compliance Status: NA f. 15A NCAC 02T .0403(a)(6): Requires that the permittee or its representative conduct a general observation of the entire wastewater collection system at least once per year. Observations: Annual observations of the entire system should be conducted and documented. This appears to be met through right-of-way maintenance, line cleaning and other maintenance checks. Compliance Status: Compliant. g. 15A NCAC 02T .0403(a)(7): Requires .that overflows and bypasses from the system be reported to the Division's Mooresville Regional Office in accordance with 15A NCAC 02B .0506(a), and that public notice must be provided as required by G.S. 143-215.1C. Observations: This system had a SSO on 07/01/11. This SSO was reported but didn't require public notice since 318 gallons reached the stream. The NC regulations and statutes, which cover the reporting requirements for SSOs, are found in NC Administrative Code 15A NCAC 02B .0506(a) and NC General Statute 143-215.1 C, respectively. You may access the NC regulations online at the NC Office of Administrative Hearings (OAH) website at: http://www.oah.state.nc.us/rules/ and the NC General Statutes online at the NC General Assembly's website at: http://www.ncga.state.nc.us/gascripts/Statutes/StatutesTOC.p1. You may wish to review them to ensure you are fully familiar with all requirements. When reporting SSOs to DWQ, you must call the Mooresville Regional Office (MRO) at 704-663-1699 during normal business hours. If outside normal business hours, you must report the spill to the NC Division of Emergency Management at 1-800-858-0368. Please note that all reportable SSOs must be reported within 24 hours of the occurrence, or first knowledge, of the SSO. Please also note that voice mail or faxed messages are not considered as the initial verbal report. You must talk to and report the spill to a live person. Compliance Status: Compliant h. 15A NCAC 02T .0403(a)(8): Requires that a grease control program be developed and implemented as follows: 1. For privately owned collection systems, the Grease Control Program shall include at least bi-annual distribution of grease education materials to users of the collection system by the permittee or its representative. 2. Grease education materials shall be distributed more often than required above if necessary to prevent grease -related sanitary sewer overflows. Observations: Shelby provides bill stuffers to the Town of Kingstown to send out. Shelby also provides grease education materials at local festivals which cover the Kingstown area. Kingstown is required to adopt Shelby's grease rules. Compliance Status: Compliant. i. 15A NCAC 02T .0403(a)(9): Requires that right-of-ways (ROW) and easements be maintained in the full easement width for personnel and equipment accessibility. r Observations: The right-of-ways inspected were found to be well maintained. Compliance Status: Compliant. j. 15A NCAC 02T .0403(a)(10): Requires that documentation be kept for all activities you undertake to comply with the requirements of 15A NCAC 02T .0403, subparagraphs .(a)(1) through (a)(9), for a minimum of three years, with the exception of the map, which shall be maintained for the life of the system. Observations: Required records are kept. Compliance Status: Compliant Please take special note of the comments in each section of the inspection report for areas which may need to be improved upon or addressed. If you have any questions regarding this letter please give me or Barry Love a call at 704-663-1699. Sincerely, �-Ja W. Corey Basinger, Regional Supervisor Mooresville Regional Office Water Quality Regional Operations Section Division of Water Resources, NCDEQ Attachments: 1. BIMS Inspection Report CC: 1 IR@; Central Files PERCS Unit Town of Kingstown w Compliance Inspection Report Permit: WQCSD0258 Effective: 07/06/07 Expiration: Owner : Town of Kingstown SOC: Effective: Expiration: Facility: Kingstown Collection System County: Cleveland Region: Mooresville Contact Person: Clarence Withrow Directions to Facility: Title: Mayor Phone: 704-484-9776 System Classifications: Primary.ORC: Certification: Phone: Secondary ORC(s): On -Site Representative(s): Related Permits: NC0024538 City of Shelby - First Broad River WWTP Inspection Date: 04/24/2017 Entry Time 10:OOAM Exit Time: 02:30PM Primary Inspector: Barry F Love Phone: 704-663-1699 Ext.263 Secondary Inspector(s): Reason for Inspection: Routine Inspection Type: Collection System Inspect Non Sampling Permit Inspection Type: Deemed permitted collection system management and operation Facility Status: II Compliant ❑ Not Compliant Question Areas: • Miscellaneous Questions ▪ Records • Pump Station (See attachment summary) ▪ Performance Standards ▪ Monitoring & Rpting Reqmts ▪ Manhole • Operation & Maint Reqmts • Inspections II Lines Page: 1 Permit: WQCSD0258 Owner - Facility:Town of Kingstown Inspection Date: 04/24/2017 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Inspection Summary: Page: 2 Permit: WQCSD0258 Owner - Facility: Town of Kingstown Inspection Date: 04/24/2017 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Inspections Are maintenance records for sewer lines available? Are records available that document pump station inspections? Are SCADA or telemetry equipped pump stations inspected at least once a week? Are non-SCADA/telemetry equipped pump stations inspected every day? Are records available that document citizen complaints? # Do you have a system to conduct an annual observation of entire system? # Has there been an observation of remote areas in the last year? Are records available that document inspections of high -priority lines? Has there been visual inspections of high -priority lines in last six months? Comment: System contains two pump stations which are inspected weekly. Monitoring and Reporting Requirements Are copies of required press releases and distribution lists available? Are public notices and proof of publication available? # Is an annual report being prepared in accordance with G.S. 143-215.1C? # Is permittee compliant with all compliance schedules in the permits? If no, which one(s)? Comment: Operation & Maintenance Requirements Are all log books available? Does supervisor review all log books on a regular basis? Does the supervisorhave plans to address documented short-term problem areas? What is the schedule for reviewing inspection, maintenance, & operations logs and problem areas? Are maintenance records for equipment available? Is a schedule maintained for testing emergency/standby equipment? What is the schedule for testing emergency/standby equipment? Do pump station logs include: Inside and outside cleaning and debris removal? Inspecting and exercising all valves? Inspecting and lubricating pumps and other equipment? Inspecting alarms, telemetry and auxiliary equipment? Is there at least one spare pump for each pump station w/o pump reliability? Yes No NA NE • ❑ ❑ ❑ 11000 • ❑ ❑ ❑ ❑ ❑•❑ • ❑ ❑ ❑ ▪ ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ E1❑ ❑ ❑■❑ • Yes No NA NE ❑ ❑ ❑• ❑ ❑ ❑ ❑ ❑ 1 ❑ O 0110 Yes No NA NE e❑❑❑ ■ ❑❑❑ MI ❑ ❑ ❑ ■ ❑❑❑ • ❑ ❑ ❑ weekly • ❑ ❑ ❑ 11 ❑ ❑ ❑ • ❑ ❑ ❑ 1000 ❑ ❑ 11 ❑ Page: 3 Permit: WQCSD0258 Owner - Facility: Town of Kingstown Inspection Date: 04/24/2017 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Operation & Maintenance Requirements Are maintenance records for right-of-ways available? Are right-of-ways currently accessible in the event of an emergency? Are system cleaning records available? Has at least 10% of system been cleaned annually? What areas are scheduled for cleaning in the next 12 months? Is a Spill Response Action Plan available? Does the plan include: 24-hour contact numbers Response time Equipment list and spare parts inventory Access to cleaning equipment Access to construction crews, contractors, and/or engineers Source of emergency funds Site sanitation and cleanup materials Post-overflow/spill assessment Is a Spill Response Action Plan available for all personnel? Is the spare parts inventory adequate? Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ U ❑ ❑ ❑ MI ❑ ❑ ❑ • ❑ ❑ ❑ ■ ❑❑❑ ▪ ❑ ❑ ❑ • ❑ ❑ ❑ ■ ❑❑❑ ❑ ❑ ❑IN ❑ ❑ ❑ ❑ ® ❑ ❑ ❑ ❑❑❑■ ▪ ❑ ❑ ❑ Comment: Pump stations are well maintained with thorouqh records to document this. 1.03 miles (11%) of line was cleaned this past year. Generators are tested on a weekly basis. Performance Standards Is Public Education Program for grease established and documented? What educational tools are used? Shelby operates system and provides flyers to Kingstown to mail out. Shelby also does education at local festivals which cover the Kingstown area. Is Sewer Use Ordinance/Legal Authority available? Does it appear that the Sewer Use Ordinance is enforced? Is Grease Trap Ordinance available? Is Septic Tank Ordinance available (as applicable, i.e. annexation) List enforcement actions by permittee, if any, in the last 12 months Has an acceptable Capital Improvement Plan (CIP) been implemented? Does CIP address short term needs and long term Vmaster plan\" concepts? Does CIP cover three to five year period? Does CIP include Goal Statement? Does CIP include description of project area? Yes No NA NE ■ ❑❑❑ ❑ ❑ ❑ 1:11110111 • ❑ ❑ ❑ ❑ ❑ ❑• ❑ ❑■❑ ❑ ❑■❑ ❑❑■❑ 1:11111111=1 ❑ ❑ . ❑ Page: 4 Permit: WQCSD0258 Owner - Facility:Town of Kingstown Inspection Date: 04/24/2017 Inspection Type : Collection System Inspect Non Sampling Reason for Visit:. Routine Performance Standards Yes No NA NE Does CIP include description of existing facilities'? 0 0 NI 0 Does CIP include known deficiencies? 0 ❑ • 0 Does CIP include forecasted future needs? 0 ❑ 11 ❑ Is CIP designated only for wastewater collection and treatment? 0 0 • 0 Approximate capital improvement budget for collection system? Total annual revenue for wastewater collection and treatment? CIP Comments Is system free of known points of bypass? • 0 0 0 If no, describe type of bypass and location Is a 24-hour notification sign posted at ALL pump stations? • ❑ ❑ 0 # Does the sign include: Instructions for notification? • ❑ ❑ 0 Pump station identifier? • ❑ ❑ 0 24-hour contact numbers • 0 0 ❑ If no, list deficient pump stations # Do ALL pump stations have an "auto polling" feature/SCADA? 00010 Number of pump stations 2 Number of pump stations that have SCADA 0 Number of pump stations that have simple telemetry 2 Number of pump stations that have only audible and visual alarms 0 Number of pump stations that do not meet permit requirements 0 # Does the permittee have a root control program? ❑ 0 ® 0 # If yes, date implemented? Describe: Comment: Shelby operates/maintains the system for Kingstown and requires local government to adopt their rules for grease. Records Are adequate records of all SSOs, spills and complaints available? Are records of SSOs that are under the reportable threshold available? Do spill records indicate repeated overflows (2 or more in 12 months) at same location? If yes, is there a corrective action plan? Is a map of the system available? Does the map include: Yes No NA NE • ❑ ❑ ❑ ❑ ❑ • ❑ ❑ ❑ II ❑ ❑ ❑ • ❑ • ❑ ❑ ❑ Page: 5 Permit: WQCSD0258 Owner - Facility:Town of Kingstown Inspection Date: 04/24/2017 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Records Yes No NA NE Pipe sizes 11 ❑ ❑ ❑ Pipe materials •❑ ❑ ❑ Pipe location 11000 Flow direction 11000 Approximate pipe age 00011 Number of service taps •❑ ❑ ❑ Pump stations and capacity 11000 If no, what percent is complete? List any modifications and extensions that need to be added to the map # Does the permittee have a copy of their permit? ❑ ❑ 1 ❑ Comment: ABOVE PETTY RD PS - Lines/Rig ht-of-Ways/Aeriel Lines Is right-of-way accessible for emergency? Is right-of-way free of sinkholes or depressions? Is line/right-of-way free of evidence of leakage? # Are there areas of exposed line? # Is any exposed line constructed of ductile iron or other approved material? Are water crossing and supports in good condition? # Is right-of-way free of non -utility motorized traffic? Is line free of visible damage? # Are there siphons in this system? If yes, are they maintained and documented? Comment: Right-of-way appeared to be well maintained. AT KINGSTOWN PS - Lines/Right-of-Ways/Aerie) Lines Is right-of-way accessible for emergency? Is right-of-way free of sinkholes or depressions? Is line/right-of-way free of evidence of leakage? # Are there areas of exposed line? # Is any exposed line constructed of ductile iron or other approved material? Are water crossing and supports in good condition? # Is right-of-way free of non -utility motorized traffic? Yes No NA NE ® ❑ ❑ ❑ 11000 ■❑❑❑ O 0110 O 0110 ❑ ❑ l ❑ 111000 • ❑ ❑ ❑ O 0011 Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ 11000 ❑ ❑ 1 ❑ O 0110 ❑ ❑■❑ 1000 Page: 6 Permit: WQCSD0258 Owner - Facility: Town of Kingstown Inspection Date: 04/24/2017 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine AT KINGSTOWN PS - Lines/Right-of-Ways/Aeriel Lines Is line free of visible damage? # Are there siphons in this system? If yes, are they maintained and documented? Comment: Right-of-way appeared to be well maintained. KINGSTOWN - Pump Station Pump station type Are pump station logs available? Is it accessible in all weather conditions? # Is general housekeeping acceptable? Are all pumps present? Are all pumps operable? Are wet wells free of excessive debris? Are upstream manholes free of excessive debris/signs of overflow? Are floats/controls for pumps/alarms operable? Is "auto polling" feature/SCADA present? Is "auto polling" feature/SCADA operational? Is simple telemetry present? Is simple telemetry operational? Are audio and visual alarms present? Are audio and visual alarms operable? Is the Pump station inspected as required? Are backflow devices in place? Are backflow devices operable? Are air relief valves in place? Are air relief valves operable? # Is an emergency generator available? Can the emergency generator run the pumps? Is the pump station equipped for quick hook-up? Is the generator operable? # Is fuel in tank and sufficient? Is the generator inspected according to their schedule? Is a 24-hour notification sign posted? Does it include: Yes No NA NE • ❑ ❑ ❑ ❑ ❑ ❑ • Yes No NA NE Duplex • ❑ ❑ ❑ ■ ❑❑❑ ▪ ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ El ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ I ❑ ❑ ❑ 1N ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ▪ ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ IN ❑ ❑ ❑ IN ❑ ❑ ❑ II II ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ III ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ II ❑ ❑ ❑ • ❑ ❑ ❑ Page: 7 Permit: WQCSD0258 Owner - Facility: Town of Kingstown Inspection Date: 04/24/2017 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine KINGSTOWN - Pump Station Instructions for notification? Pump station identifier? Emergency phone number Is public access limited? Is pump station free of overflow piping? Is the pump station free of signs of overflow? Are run times comparable for multiple pumps? Comment: Pump station appeared to be well maintained with no problems noted. KINGSTOWN - upstream of PS Manhole Is manhole accessible? # Is manhole cover/vent above grade? Is the manhole free of visible signs of overflow? Is the manhole free of sinkholes and depressions? Is manhole cover present? # Is manhole properly seated? # Is manhole in good condition? # Is invert in good condition? Is line free -flowing and unrestricted in manhole? Is manhole free of excessive amounts of grease? Is manhole free of excessive roots? Is manhole free of excessive sand? Is manhole's extended vent screened? Are vents free of submergence? Are manholes free of bypass structures or pipes? Comment: Checked first and third manholes PETTY ROAD - Manhole Is manhole accessible? # Is manhole cover/vent above grade? Is the manhole free of visible signs of overflow? Is the manhole free of sinkholes and depressions? Is manhole cover present? Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ■ ❑❑❑ ■ ❑❑❑ Yes No NA NE RI ❑ ❑ ❑ e❑❑❑ ■ ❑❑❑ • ❑ ❑ ❑ R ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ © ❑❑❑ ▪ ❑ ❑ ❑ 111000 ■ ❑❑❑ • ❑ ❑ ❑ 1110111111 ❑ ❑ ® ❑ ▪ ❑ ❑ ❑ upstream of the pump station. No problems were observed. Yes No NA NE ▪ ❑ ❑ ❑ 11000 11000 11000 11000 Page: 8 Permit: WQCSD0258 Owner - Facility: Town of Kingstown Inspection Date: 04/24/2017 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine PETTY ROAD - Manhole Yes No NA NE . # Is manhole properly seated? • ❑ 0 0 # Is manhole in good condition? MOOD # Is invert in good condition? • 0 ❑ ❑ Is line free -flowing and unrestricted in manhole? • ❑ ❑ ❑ Is manhole free of excessive amounts. of grease? • ❑ 0 0 Is manhole free of excessive roots? IN 0 ❑ ❑ Is manhole free of excessive sand? • 0 ❑ ❑ Is manhole's extended vent screened? ❑ ❑ • 0 Are vents free of submergence? ❑ 0 1 ❑ Are manholes free of bypass structures or pipes? • 0 ❑ ❑ Comment: Checked first and second manholes upstream of pump station. No problems were observed. PETTY ROAD PS - Pump Station Pump station type Are pump station logs available? Is it accessible in all weather conditions? # Is general housekeeping acceptable? Are all pumps present? Are all pumps operable? Are wet wells free of excessive debris? Are upstream manholes free of excessive debris/signs of overflow'? Are floats/controls for pumps/alarms operable? Is "auto polling" feature/SCADA present? Is "auto polling" feature/SCADA operational? Is simple telemetry present? Is simple telemetry operational? Are audio and visual alarms present? Are audio and visual alarms operable? Is the Pump station inspected as required? Are backflow devices in place? Are backflow devices operable? Are air relief valves in place? Are air relief valves operable? # Is an emergency generator available? Yes No NA NE Duplex • ❑ ❑ ❑ • ❑ ❑ ❑ II ❑ ❑ II ❑ ❑ ❑ • ❑ ❑ ❑ 1 ❑ ❑ ❑ II ❑ ❑ ❑ II ❑ ❑ ❑ ❑ ❑ II ❑ ❑ ❑ •❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ▪ ❑ ❑ ❑ ▪ ❑ ❑ ❑ ■ ❑❑❑ ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • • ❑ ❑ ❑ Page: 9 Permit: WQCSD0258 Owner - Facility:Town of Kingstown Inspection Date: 04/24/2017 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine PETTY ROAD PS - Pump Station Yes No NA NE Can the emergency generator run the pumps? IN ❑ ❑ ❑ Is the pump station equipped for quick hook-up? ❑ ❑ ❑ Is the generator operable? • ❑ ❑ ❑ # Is fuel in tank and sufficient? •❑ ❑ ❑ Is the generator inspected according to their schedule? 110111 ❑ Is a 24-hour notification sign posted? ®❑ ❑ ❑ Does it include: Instructions for notification? • ❑ ❑ ❑ Pump station identifier? • ❑ ❑ ❑ Emergency phone number M ❑ ❑ ❑ Is public access limited'? • ❑ ❑ ❑ Is pump station free of overflow piping? • ❑ ❑ ❑ Is the pump station free of signs of overflow? • ❑ ❑ ❑ Are run times comparable for multiple pumps? Comment: Pump station appeared to be well maintained. Page: 10 IA/ QC5aU2,c1/� Jow Qf n s r C 0 f Fes, 1 Is v vt 13dA- 660 re' . it/1,%--/ 13 I' { { pn,Vaci Nctle,A3.65 YN4.14f;li'T„B lea I Is 0 M� NG 'sok-t 2, C Iqr�� ]/ f �, as Gti'` '•�. ,%3 jo :,✓ nJ (ene$ga Ormati0n ,"cf"_6siio �n� i p,n0!G V✓c�L'vi3 1. Number of Pump stations 5 2. SCADA. system PS 2. 3. •TeleUl:etry PS 4. Audible and visual only 5. Generators Permanent a. Frequency tested 1 /w k 3 Generators Portable A. Quick -connect p1ugin PS . Frequency tested Pump stations served by same generator. 6. RC .1 )D 1i ; b ® 70 8 Li'- 6 SLi' o Sewer Use Ordinance c $i1-1Ly P O go,,e 7 51, L NG zS7I31-© -02 spection Check .gt S+4te-¢ ; 10;9c9 �. L ry 1. ; H , S�1 1 L� 3 5. LA/QC- 5 1, tJ 2 5 C G��hllr:sl/�..-.,�f-I� 1CS.-_:. l.�r tc( !j ✓��jj� ,c-- ,'.::`I S�n� c,� e5 yI n �L .'r'a Irb,.VG t r ✓ry11 ]Ennforce, eats Last Year• ; 044:4. ,l�w?P• • =�n FOG Program `s' l e4 1, 'ta Gila 43, +i r3?; «'� . jl 4' "� '� _ jA ro v : Lip.;. Try r ..t d,. , 1, `r i l S )-'^1 ` ,. ri i' zi{� - 5. i L. u Inspecfions - Public ED ': ow . . Annual Report ._ ��.✓ Root Control Pro ram . S °�-^ s1h e / b7 C 11' udget $ Years HAS d DC-4 Q. +1 - ro ,1 •L ''• ,.o •' 1-n 154-4) r'l Pr �3t atio" 41Jt a ✓ lie o £ s✓a Y l! of N ate I� n J3 l �! r- ,�I 0 t-, /-c1 /s v .7 u !7 P e I' v el 6‘2_s /,2 fzs l I 4 o• �f (�O✓L✓ r'1OSu LCrLq j a s stl. /,by Kl Documentationof 1. Line Clearing (1 O %) . --° 2. High priority des (6 s) Tit evc�3 ..i ;1..- !1 ¢�wti 1 � Q ►T °�C7 v 0 cti-e, 3/sg/th - 3. System observation annual 4. ROW mowing r,?opr , Mp ' ye I ♦ 1 >\'��•/.�nit'1 „4,/ Py Review logs for PS O&M -0qe�' P eportable Spills .2A epeat Location/Cause i1 o loom reportable spills n o y� Custo 111 er co `.Ili pti tIt .• vi v::� � F ;r }si Kfvt.0t 7/0 Plaints 0 (40 w c r' Spare parts inventory Map of systelili % complete /'I ers �►;� c► J-.�. ,� d -F wtin psi ;iv9 V, b1 1:,e1 sl;. C 1 T::; r Ci a cL c /�xs'i Q✓�.'t� / 7l u.✓p a. i � V�>" tA'tet p tt 1 �Wd oVaf$ s. y_64, YaA'lo, e' a., e '7 S G+ ' :.[i L_ Pump Station Inspection Checklist Name Address Housekeeping Secure Accessible Identification Signage Inspection Schedule Daily Weekly Wet Well — Floats Free of debris ✓ ) High water float i (A" - Telemetry ✓ / Audio -Visual ✓ d/ SCADA Alarm system tested for communications No of Pumps 1 2 e✓ Operational 1 2 Capacity of each (gpm) 1 2 Runtime hour meter reading average 1 2 Emergency power Generator Portable Quick -connect _ nsite Fuel tank let 0s / ( Gallons per hour usage rate Testing schedule k i/ Automatic Bypass pumping configurerd Overflow piping Manhole upstream Inspection Logs Collection System Inspection Checklist Manholes- Lines- Right Of Way- Aerials 1. Manhole location or address Cover present - vent and cover above grade - ventscreened Visible signs of overflow Sinkholes and depressions Good condition properly seated Bypass structures or pipes present Invert in good condition Size / 0 inches Pipe capaci Line free flowing and unrestricted I/ Excessive grease, roots, or sand 2. Right of Way - location or name of outfall line Accessible Free of sinkholes or depressions No evidence of leakage Free of non -utility motorized traffic 3. Aerials - High Priority lines Exposed line of ductile material Water crossings and supports in good condition Level of debris on or behind line Free of damage Right of Way mowing records Visual inspection of off street lines General observation of system (annual) diameter. Name Address Pump Station Inspection 'Checklist aol5 24-1y'S0 Housekeeping Secure Accessible t/ Identification Signage Inspection Schedule Daily Wet Well — Floats Free of debris High water float ✓/ Telemetry �,/ Audio -Visual SCADA Alarm _ -system tested for communications Weekly Emergency power Fuel tank Testing schedule Bypass pumping co Overflow piping Manhole upstream Inspection Logs Generator ti of /<ed c v',41a-c/t Portable Gallons per Automatic No of Pumps 1 2 Operational 1 a/ 2i Capacity of each (gpm) 1 2 Runtime hour meter reading' average 1 2 Quick -connect Onsite) hour usage rate Visible signs of overflow Sinkholes and depressions Good condition properly seated Bypass structures or pipes present Invert in good condition Size r Line free flowing and unrestricted Excessive grease, roots, or sand 1. Manhole location or address Collection System Inspection Checklist Manholes- Lines- Right Of Way- Aerials SA, T Cover present - vent and cover above gra le -vest-st a/ t %2 3/4 diameter. inches Pige capaci 2. Right of Way - location or name of outfall line Accessible Free of sinkholes or depressions No evidence of leakage Free of non -utility motorized traffic 3. Aerials - High Priority lines Exposed line of ductile material Water crossings and supports in good condition Level of debris on or behind line Free of damage Right of Way mowing records Visual inspection of off street lines General observation. of system (annual) W°' W �'AC4 C- 510 ° 2`5 E 2.0 I Lf- ojs7 wt rr 2--3I s® s'T 0 YGener lc Information b✓f`i G5i%�Z�� �Na re) 13.x 660 Ne gn1-2- h specfisChecklist /%s40•a )(,6,f©e:.Vt --1. Number of Pump stations 5-, Z. 2. SCADA system P p - 3. Telemetry PS 3 4, Audible and Visual only 5, Generators Permanent 5" 2, a. Frequency tested wv.y..?-k y ram' v .... Generators Portable N o of - A. Quick -connect pink PS B. Frequency tested -Pump stations served by same generator. 7/5o/,s ��s t `i; 3O [J a✓ c 1 1 N K lit })) i+, 13,-ac{ 61v-.e..e. n z -L: -1 S .1s, 1.0 /14K ,4411 Gl✓ K Sy�1 J D cAp / Jr - ORC. it, k; -O s!' cC k -5,44 k cS- H}s_Cbir; 3.^40,41-,, �„z1 G��n..-)-1/1 r4.,•• �}�lh�., s Ewer Use Ordinance • Ennforcemeuntts Last Year FOG IProgra , ; .cA e4 « F ;,, , . III Inspections Public ED How Annual !': eport Date oot Control Program udget $ Years Documentation of 1, Line Deal i inng (1O%) 2. High priority lines (6 m®s) ,ya c 11 ;,, 1 6N �•s�l�_ "4-1" / 1 %1 ss; slq if "L / ,r );4; .5 r rc.�v �o 4°K2o? ShG .2,815) _ 02p, or'�rniions S� «ri„-f ,j .j 7o& 661 25�e J� s r� - l;� , et u5A�•F��'...." a, h' s Gy' 6 u .1 C s.- s� r o I. van M Y a of S p 1 / ei�v:; -et c c /vim � o oar, (49 c t ; f H 6,11 5� c-4-0 ve" -e.-- 3. System observation annual .— 4, ROW mowing ✓ G v d& o Gctrt S B/ c ti gbc,� j W y °L GLke L 0 1 � 6 ct el- A f' /'�et1- ,-..- l'eview logs for PS O&M .... ( e1 64,-- v 1 • ,, 47 t''. SO'C\ ".-e, r• r ; ,;s v%,;.- ,,,_ Reportable Sp 1111 epeat Locatio s /Cause Non reportable spills Customer complaints Spare parts inventory 5 4; 6,..1 Ls ----- Map of system % complete al vn (41 , r G.- r ti -r-- Pump Station Inspection Checklist Name L 3 No of Pumps 1 2 Address 0 Operational 1 2 Capacity of each (gpm) 1 2 Runtime hour meter reading average 1. 2 Housekeeping ✓ Secure ✓ Accessible i✓ / Identification Signage Inspection Schedule Daily Weekly Wet Well — Floats V Free of debris ✓ High water float TelemeA C O Audio- isual SCADA Alarm system tested for communications Emergency power ox_9 Portable Quick -connect Fuel tank Gallons per hour usage rate Testing schedule Automatic Bypass pumping configured Overflow piping 9 et s— Manhole upstream Inspection Logs „lav�, — A cf CI n t Tc,J }1, e.'-iiN��f= / S h y1 ,c,_ 1. Manhole location or address Collection System Inspe Lion Checklist Manholes- Lines- Right Of Way- Aerials Cover present - vent and cover above grade - vent screened Visible signs of overflow ✓l Sinkholes and depressions Good condition properly seated y Bypass structures or pipes preset -62 Invert in good conditionSize inches pe capaci �tfii/2 3/4 diameter. Line free flowing and unfestrictedy Excessive grease, roots, or sand vt 2. Right of Way - location or name of outfall line c'Accessible r' `Tree of sinkholes or depressions 4/ f/No evidence of leakage Free of non -utility motorized traffic 3. Aerials - High Priority lines Exposed line of ductile material Water crossings and supports in good condition Level of debris on or behind line Free of damage Right of Way mowing records Visual inspection of off street lines General observation of system (annual) Pump Station Inspection Checklist Name Address Housekeeping Secure v� Accessible Identification Signage Inspection Schedule Daily �l Weekly (/ No of Pumps 1 2 Operational 1 Capacity of each (gpm) r�� [2- "` l 1 parr 2 Runtime hour meter reading average 1• 2 Wet Well — Floats `!/ :'h 1 k 1)° Lt.i 1-. ,4 Free of debris e^—ao.s.— s % a I I o vct y, od d°,-[r ; ,,, e:1-'_, High water float Teleme �/✓ '` 5 `", a-i e�i��,— N `.5 �`,.s��, `��`�r,, J �, WA- n o �u�%/ tr',s Audio"Visual SCADA Aa.b i.J._..- tP r$ kJ A.f/' u _ I Alarm system tested for communications � �U �i Emergency power Generator !/ Portable Quick -connect Fuel tank Gallons per hour u ge rate Testing schedule ✓✓.- .4337 Automatic Bypass pumping configured Overflow piping Manhole upstream Inspection Logs Collection S stem Inspecti n Chec:, ist �L, ght Of Way- Aerials Manholes- Lines- 1. Manhole location or address r � Cover present - vent and cover above grade - vent screened Visible signs of overflow Sinkholes and depressions vi Good condition properly seated Bypass structures or pipes present vi Invert in good condition Size inches Pipe capacity 1/4 %2 3/4 diameter. Line free flowing and unrestricted Excessive grease, roots, or sand 2. Right of Way - location or name of outfall line Accessible Free of sinkholes or depressions No evidence of leakage Free of non -utility motorized traffic . Aerials - High Priority lines Exposed line of ductile material Water crossings and supports in good condition Level of debris on or behind line Free of damage Right of Way mowing records Visual inspection of off street lines General observation of system (annual) Pat McCrory Governor ATA NCDE R North Carolina Department of Environment and Natural Resources August 4, 2015 Mr. David Hux, Assistant Utilities Director City of Shelby Post Office Box 207 Shelby, North Carolina 28151-0207 Dear Mr. Hux: Donald R. van der Vaart Secretary Subject: Compliance Evaluation Inspection Town of Kingstown Collection System Permit No. WQCSD0258 Kingstown, Cleveland County Enclosed is a copy of the Compliance Evaluation Inspection Report for the inspection conducted at the subject facility on July 30, 2015 by Mr. Barry Love and Mr. Ori Tuvia of this Office. The assistance and cooperation of the staff there was greatly appreciated. The inspection revealed that the system is being properly operated and well maintained. The inspection report should be self-explanatory; however, should you have any questions concerning this report, please do not hesitate to contact Mr. Love at (704) 235-2143. Michael L. Parker, Regional Supervisor Mooresville Regional Office. Water Quality Regional Operations Section Division of Water Resources, NCDENR Attachment: Inspection Report —July 2015 cc: Town of Kingstown MRO file PERCS Mooresville Regional office, 610 East Center Avenue, Mooresville, North Carolina 28155 Phone: 704-663-1699\ Internet: www,ncdenr.gov An Equal Opportunity 1 Affirmative Action Employer — Made in part by recycled paper 4 Compliance Inspection Report Permit: WQCSD0258 Effective: 07/06/07 Expiration: SOC: Effective: Expiration: County: Cleveland Region: Mooresville Contact Person: Clarence Withrow Title: Mayor Directions to Facility: System Classifications: Primary ORC: Secondary ORC(s): On -Site Representative(s): Related Permits: Certification: NC0024538 City of Shelby - First Broad River WWTP Inspection Date: 07/30/2015 Owner : Town of Kingstown Facility: Kingstown Collection System Phone: 704-484-9776 Phone: Entry Time: 09:30AM Exit Time: 01:30PM Primary Inspector: Barry F Love Phone: 704-663-1699 Ext.263 Secondary Inspector(s): Ori A Tuvia Reason for Inspection: Routine Inspection Type: Collection System Inspect Non Sampling Permit Inspection Type: Deemed permitted collection system management and operation Facility Status: jj Compliant El Not Compliant Question Areas: LJ Miscellaneous Questions ® Records Pump Station (See attachment summary) pri Performance Standards ® Operation & Maint Reqmts Monitoring & Rpting Reqmts 11 Inspections Manhole Lines Page: 1 Permit: WQCSD0258 Owner - Facility: Town of Kingstown Inspection Date: 07/30/2015 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Inspection Summary: Page: 2 Owner - Facility: Town of Kingstown Permit: WQCSD0258 z z 0 z Performance Standards ❑ ❑❑❑® ❑❑❑❑❑❑❑❑❑ M. NM 000000000 r• a) a) E U O 0 •o a) to a) a) co 0) o) O E o) O O w U co What educational tools are used? Flyers at various events and festivals in the area. Is Sewer Use Ordinance/Legal Authority available? Does it appear that the Sewer Use Ordinance is enforced? Is Grease Trap Ordinance available? Is Septic Tank Ordinance available (as applicable, i.e. annexation) List enforcement actions by permittee, if any, in the last 12 months Has an acceptable Capital Improvement Plan (CIP) been implemented? o- an 0. 8 c 0 U C CO CI a) 4) as E € r. cn a) a) m r• c (0 'U r• o (0CD r• as co O U c • r• a) m a) .N m c .O O- w. O •X .0 p2 a) ' c a a) c c • a) • a) 4- • � • a) 7 a) co O • O • ON> ci=' CD O CO • c O _) • O8 Oa) • (.0 N co 2 a) L 0 'O -O Y 4� co a) a) a) a) a) a) 7 = '? = 7 > 0 U 0 U 0 co U • c C C C c O 0 0 0 0 0 0 na)aaaa) am a • a 00 0 0• 0 0 0 Is CIP designated only for wastewater collection and treatment? Approximate capital improvement budget for collection system? Total annual revenue for wastewater collection and treatment? CIP Comments ❑ 0 ❑❑❑ ❑ O 0 000 0 ❑ 0 000 1 Is system free of known points of bypass? If no, describe type of bypass and location Is a 24-hour notification sign posted at ALL pump stations? # Does the sign include: Instructions for notification? Pump station identifier? 24-hour contact numbers If no, list deficient pump stations # Do ALL pump stations have an "auto polling" feature/SCADA? 0 N 0 0 a) a) a) CO a) O a) (n (0 E E E E E € 7 7 7 7 7 a) a a a a a n• O 4- 0 0 0 s .0 .0 .0 .0 a) E E E E E 0 7 7 7 7 0 Z Z Z Z Z* 9 Is a Spill Response Action Plan available? What areas are scheduled for cleaning in the next 12 months? Has at least 10% of system been cleaned annually? Are system cleaning records available? Are right-of-ways currently accessible in the event of an emergency? Are maintenance records for right-of-ways available? Inspecting alarms, telemetry and auxiliary equipment? Inspecting and lubricating pumps and other equipment? Inspecting and exercising all valves? Inside and outside cleaning and debris removal? :epnloul s6o1 uoge}s dwnd oa What is the schedule for testing emergency/standby equipment? Is a schedule maintained for testing emergency/standby equipment? Are maintenance records for equipment available? What is the schedule for reviewing inspection, maintenance, & operations logs and problem areas? Does the supervisor have plans to address documented short-term problem areas? Does supervisor review all log books on a regular basis? ,elgellene sroq 601 lie aav tag DO EADPE `° ❑ DO Cy ❑❑❑❑ El El El El El EIDDELOODDO OD DOD abuie f =g uogeJeao n cp 3 (D c 3N VN oN seA 0 0 3 3 cD Has there been visual inspections of high -priority lines in last six months? Are records available that document inspections of high -priority lines? # Has there been an observation of remote areas in the last year? # Do you have a system to conduct an annual observation of entire system? Are records available that document citizen complaints? Are non-SCADA/telemetry equipped pump stations inspected every day? Are SCADA or telemetry equipped pump stations inspected at least once a week? Are records available that document pump station inspections? [4❑❑DEIDEIDEIDOEI OODIDEIVEDEID ID El El El El I� Are maintenance records for sewer lines available? i 3N VN oN saA eJ Se UMO;S UN JO UMOj 81.11 se;eJ8 uol;OelloO uMo;s 0 0 3 q 3 m m rt noJLl; euop sl uol;eonpe pod I};o esn ay; u ers at local events/festivals. It was not clear if Inspection Date: 07/30/2015 Inspection Type : Collection System Inspect Non Sampling Jo} uosee 59Zo0SOOM :}nwed Owner - Facility: Town of Kingstown A Permit: WQCSD0258 Owner - Facility: Town of Kingstown Inspection Date: 07/30/2015 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Does the plan include: 24-hour contact numbers Response time Equipment list and spare parts inventory Access to cleaning equipment Access to construction crews, contractors, and/or engineers Source of emergency funds Site sanitation and cleanup materials Post-overflow/spill assessment Is a Spill Response Action Plan available for all personnel? Is the spare parts inventory adequate? Comment: Records Are adequate records of all SSOs, spills and complaints available? Are records of SSOs that are under the reportable threshold available? Do spill records indicate repeated overflows (2 or more in 12 months) at same location? If yes, is there a corrective action plan? Is a map of the system available? Does the map include: Pipe sizes Pipe materials Pipe location Flow direction Approximate pipe age Number of service taps Pump stations and capacity If no, what percent is complete? List any modifications and extensions that need to be added to the map # Does the permittee have a copy of their permit? Comment: Monitoring and Reporting Requirements Are copies of required press releases and distribution lists available? Are public notices and proof of publication available? # Is an annual report being prepared in accordance with G.S. 143-215.1C? # Is permittee compliant with all compliance schedules in the permits? If no, which one(s)? ®❑ ❑ ❑ ® ❑ ❑ ❑ • ❑ ❑ ❑ ®❑❑❑ ®❑ Cl ❑ ❑ ❑ ❑ II NI El ❑ ❑ ®❑ ❑ ❑ BE El ❑ ❑ ®ODE: Yes No NA NE ® ❑ ❑ ❑ ®❑❑❑ ❑ ❑❑$ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ®❑❑❑ ®❑ ❑ ❑ ®❑ ❑ ❑ ®❑ ❑ ❑ ❑ ❑ ❑ ® ❑ ❑ ❑ ® ❑❑❑ ❑ ❑ ❑ III Yes No NA NE ❑ ❑ ❑ ❑❑❑® O 011110 ❑ ❑ ® ❑ Page: 5 Owner - Facility: Town of Kingstown Permit: WQCSD0258 c 0 Reason for Visit: Inspection Type : Collection System Inspect Non Sampling Inspection Date: 07/30/2015 E E O 0 KINGSTOWN - 1st upstrean Yes No NA NE ❑❑❑❑❑❑❑❑❑❑❑❑❑❑❑ ❑ ❑❑❑❑❑❑❑❑❑❑❑®❑❑ ❑ ❑❑❑❑❑❑❑❑❑❑❑❑❑❑ Is the manhole free of visible signs of overflow? Is the manhole free of sinkholes and depressions? Is manhole cover present? # Is manhole properly seated? # Is manhole in good condition? # Is invert in good condition? s line free -flowing and unrestricted in manhole? s manhole free of excessive amounts of grease? s manhole free of excessive roots? s manhole free of excessive sand? s manhole's extended vent screened? Are vents free of submergence? Are manholes free of bypass structures or pipes? Yes No NA NE ❑ ❑❑❑❑❑❑❑❑❑❑❑❑❑❑ ❑❑❑❑❑❑❑❑❑❑❑❑U00 ❑ ❑❑❑❑❑❑❑❑❑❑❑❑❑❑ Is manhole accessible? # Is manhole cover/vent above grade? Is the manhole free of visible signs of overflow? Is the manhole free of sinkholes and depressions? Is manhole cover present? # Is manhole properly seated? # Is manhole in good condition? # Is invert in good condition? s line free -flowing and unrestricted in manhole? s manhole free of excessive amounts of grease? s manhole free of excessive roots? s manhole free of excessive sand? s manhole's extended vent screened? Are vents free of submergence? Are manholes free of bypass structures or pipes? Permit: WQCSD0258 Owner - Facility: Town of Kingstown Inspection Date: 07/30/2015 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Comment: KINGSTOWN - Lines/Right-of-Ways/Aerie) Lines Is right-of-way accessible for emergency? Is right-of-way free of sinkholes or depressions? Is line/right-of-way free of evidence of leakage? # Are there areas of exposed line? # Is any exposed line constructed of ductile iron or other approved material? Are water crossing and supports in good condition? # Is right-of,way free of non -utility motorized traffic? Is line free of visible damage? # Are there siphons in this system? If yes, are they maintained and documented? ROW had been recently mowed. Comment: KINGSTOWN LS - 1623 W. - Pump Station Pump station type Are pump station logs available? Is it accessible in all weather conditions? # Is general housekeeping acceptable? Are all pumps present? Are all pumps operable? Are wet wells free of excessive debris? Are upstream manholes free of excessive debris/signs of overflow? Are floats/controls for pumps/alarms operable? Is "auto polling" feature/SCADA present? Is "auto polling" feature/SCADA operational? Is simple telemetry present? Is simple telemetry operational? Are audio and visual alarms present? Are audio and visual alarms operable? Is the Pump station inspected as required? Are backflow devices in place? Are backflow devices operable? Are air relief valves in place? Yes No NA NE ❑ ❑ ❑ El ❑ ❑ ❑ 511 ❑ ❑ ❑ ❑ ❑ ® ❑ ❑❑®❑ ❑ ❑ ® D NE ❑ ❑ CI I'� ❑ ❑ ❑ ❑ ❑ ❑ in Yes No NA NE Duplex El El ❑❑ 1 ❑ ❑ .❑ ❑ ® ❑ ❑ ❑ MOOD ® ❑ ❑ ❑ ®:.❑ ❑❑ ®❑ ❑ ❑ ❑ ❑ AN ❑ ❑ . ❑ ® ❑ ® ❑ ❑ ❑ OM ❑ ❑ ❑ ® ❑ ❑ ❑ ❑ ❑ ❑ IN ❑ ❑ ❑ El El ❑L El ❑ ❑ 11 ❑ ❑ ENE Page: 7 Permit: WQCSD0258 Owner - Facility: Town of Kingstown Inspection Date: 07/30/2015 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Are air relief valves operable? # Is an emergency generator available? Can the emergency generator run the pumps? Is the pump station equipped for quick hook-up? Is the generator operable? # Is fuel in tank and sufficient? Is the generator inspected according to their schedule? Is a 24-hour notification sign posted? Does it include: Instructions for notification? Pump station identifier? Emergency phone number Is public access limited? Is pump station free of overflow piping? Is the pump station free of signs of overflow? Are run times comparable for multiple pumps? Comment: Generator would not crank onthe day of the inspection. Records showed that it had been operating recently through its weekly self test. PETTY ROAD - 2015 Petty I Pump Station Pump station type. Arepump station logs available? Is it accessible in all weather conditions? # Is general housekeeping acceptable? Are all pumps present? Are all pumps operable? Are wet wells free of excessive debris? Are upstream manholes free of excessive debris/signs of overflow? Are floats/controls for pumps/alarms operable? Is "auto polling" feature/SCADA present? Is "auto polling" feature/SCADA operational? Is simple telemetry present? Is simple telemetry operational? Are audio and visual alarms present? Are audio and visual alarms operable? Is the Pump station inspected as required? ❑ ❑ ❑ 1 ❑ ❑ ❑ ❑ ❑ ❑ U DD ❑ NI ❑ ❑ • ❑ ❑ ❑ IN ❑ ❑ ❑ • ❑ ❑ ❑ • ❑❑❑ FI ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ E ❑ ❑ ❑ • ❑ ❑ ❑ Yes Yes No NA NE Duplex LS ❑ ❑ ❑ i ❑ ❑ ❑ ❑ ❑ ❑ El ❑ ❑ ❑ ❑ ❑❑ ❑ ❑ ❑ MOOD ❑ ❑❑ ❑ ❑ E ❑ ❑ ❑ ❑ MOOD W OOD • ❑ ❑ ❑ ❑ ❑ ❑ N ❑ ❑ ❑ Page: 8 ❑ ❑ ❑ 111 DOOM ❑ ❑ ❑ II ❑ ❑ ❑ ❑ ❑ ❑ 5M ❑ ❑ ❑ ❑ ❑ i`-$ ❑ `:d ▪ El CI ❑ ❑❑® L ❑ ❑ ❑ ❑ ❑❑ s.' ❑ ❑ ❑ II ❑ ❑ ❑ MOOD MI ❑ ❑ ❑ MOOD 61 ❑ ❑ ❑ no Permit: WQCSD0258 Owner - Facility: Town of Kingstown Inspection Date: 07/30/2015 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Are backflow devices in place? Are backflow devices operable? Are air relief valves in place? Are air relief valves operable? # Is an emergency generator available? Can the emergency generator run the pumps? Is the pump station equipped for quick hook-up? Is the generator operable? # Is fuel in tank and sufficient? Is the generator inspected according to their schedule?, Is a 24-hour notification sign posted? Does it include: Instructions for notification? Pump station identifier? Emergency phone number Is public access limited? Is pump station free of overflow piping? Is the pump station free of signs of overflow? Are run times comparable for multiple pumps? Comment: Pump one had been out for repair recently. It had not been reset to auto rotate, so didn't show a change in run time. Page: 9 Beverly Eaves Perdue Governor NCDEHR North Carolina Department of Environment and Natural Resources FILE„- Division of Water Quality Coleen H. Sullins Dee Freeman Director Secretary August 22, 2011 Mr. Brad Cornwell, Public Utilities Director City of Shelby P. O. Box 207 Shelby, NC 28151 Subject: Notice of Violation Tracking No. NOV-2011-DV-0210 Collection System Permit Number WQCSD0258 Town of Kingstown Cleveland County Dear Mr. Cornwell: A review has been conducted of the Town of Kingstown's self reported Sanitary Sewer Overflows (SSOs) 5-Day Report(s) for July 2011. This review has shown Kingstown to be in violation of the requirements found in Collection System Permit WQCSD0258 and/or G.S. 143- 215.1(a)(1). The violations that occurred during July 2011 are summarized in Attachment A. Remedial and corrective actions, if not already implemented, should be taken to prevent further SSOs. As of December 1, 2007, any reportable SSO may be issued a Notice of Violation (NOV) and some may be assessed a civil penalty. Civil penalties will be issued for SSOs based on volume, volume reaching surface waters, duration and gravity, impacts to public health, fish kills, and recreational area closures. Other factors considered in determining the amount of the civil penalty are the violator's history of spills, the cost of rectifying the damage, whether the spill was intentional, and whether money was saved by non-compliance. Mooresville Regional Office Location: 610 East Center Ave., Suite 301 Mooresville, NC 28115 Phone: (704) 663-1699 \ Fax: (704) 663-6040 \ Customer Service: 1-877-623-6748 Internet: www.ncwaterquality.org An Equal Opportunity \ Affirmative Action Employer — 50% Recycled/10% Post Consumer paper One NorthCarolina A atffralll/ Mr. Brad Cornwell NOV-201 1-DV-0210 Page 2 Be advised that G.S. 143-215.6A provides for a civil penalty assessment of not more than twenty-five thousand dollars ($25,000), or twenty-five thousand dollars ($25,000) per day when the violation is of a continuing nature, against any person who is required but fails to apply for or to secure a permit required by G.S. 143-215.1. Penalties may also be assessed for any damage to the surface waters of the State that may result from the unpermitted discharge. The SSOs noted in Attachment A under violation action as "Proceed to Enforcement" are the overflows that the regional office has determined, after review of the CS-SSO 5-day report, that may result in a civil penalty assessment. You have 20 days from receiving this Notice of Violation letter to provide any additional justification for the identified SSOs as to why these spills do not meet the criteria listed in this letter for civil penalty assessment. If you have any questions regarding this policy please do not hesitate to contact Mr. Lon Snider or myself at 704-663-1699. Sincerely, Robert B. Krebs Surface Water Protection Section Supervisor Division of Water Quality Mooresville Regional Office Attachment — A Cc: PERCS Files Attachment A Town of Kingstown Collection System July 2011 24 Hour 5 Day Vol. Cause: Pemlit # Location Incident # Start Date Gallons Reaching Surface NOV Case Violation Action Cause: Grease Water Debris in line WQCSD0258 Quail Run Dr ROW 20110/339 07/01/11 1270 318 NOV-2011-DV-0210 Proceed to NOV Yes Yes • FiLEks NCDENR North Carolina Department of Environment and Natural Resources Division of Water Quality Beverly Eaves Perdue Ccieen H. Sullins Dee Freeman Governor Director Secretary December 15, 2010 Mr. David Hux, Assistant Public Works Director City of Shelby P. O. Box 207 Shelby, NC 28151 Subject: Compliance Evaluation Inspection Town of Kingstown Collection System Deemed Permit No. WQCSD0258 Cleveland County, N.C. Dear Mr. Hux: Enclosed is a copy of the Compliance Evaluation Inspection Report for the inspection conducted at the subject facility on December 1, 2010 by Mr. Lon Snider of this Office. The operation and maintenance activities initiated by the facility staff are commendable. The report should be self-explanatory; however, should you have any questions concerning this report, please do not hesitate to contact Mr. Snider at (704) 663-1699. Sincerely, Robert B. Krebs Surface Water Protection Regional Supervisor Enclosure cc: Town of Kingstown Mooresville Regional Office Location: 610 East Center Ave., Suite 301 Mooresville, NC 28115 Phone: (704) 663-1699 \ Fax: (704) 663-6040 1 Customer Service: 1-877-623-6748 Internet: www.ncwaterquality.org An Equal Opportunity \ Affirmative Action Employer — 50% Recycled/10% Post Consumer paper NorthCarolina Naturally f Compliance Inspection Report Permit: WQCSD0258 Effective: 07/06/07 Expiration: SOC: Effective: Expiration: County: Cleveland Region: Mooresville Contact Person: Clarence Withrcw Directions to Facility: Owner: Town of Kingstown Facility: Kingstown Collection System Title: Mayor Phone: 704-484-9776 System Classifications: Primary ORC: Certification: Phone: Secondary ORC(s): On -Site Representative(s): Related Permits: NC0024538 City of Shelby - First Broad River WNTP Inspection Date: 12/01/2010Entry Time: 09:00 AM Exit Time: 03:00 PM Primary Inspector: Lon Snider Secondary Inspector(s): Phone: 704-663-1699 Reason for Inspection: Routine Inspection Type: Collection System Inspect Non Sampling Permit Inspection Type: Deemed permitted collection system management and operation Facility Status: El Compliant ❑ Not Compliant Question Areas: El Miscellaneous Questions Monitoring & Rpting Reqmts Lines Performance Standards Inspections (See attachment summary) rai Operation & Maint Regmts Records Ei Pump Station Manhole Page: 1 Inspection Date: 12/01/2010 Permit: VVQCSD0258 Owner - Facility: Town of Kingstown Inspection Type: Collection System Inspect Non Sampling Reason for Visit: Routine Inspection Summary: Page: 2 Permit: WQCSCO258 Owner - Facility: Town of Kingstown Inspection Date: 12/01/2010 Inspection Type: Collection System Inspect Non Sampling Reason for Visit: Routine Performance Standards Is Public Education Program for grease established and documented? 'Nrat educational tools are used? Mailers. Is Sewer Use Ordinance/Legal Authority available? Does it appear that the Sewer Use Ordinance is enforced? Is Grease Trap Ordinance available? Is Septic Tank Ordinance available (as applicable, i.e. annexation) List enforcement actions by permittee, if any, in the last 12 months None Has an acceptable Capital Improvement Plan (CIP) been implemented? Does CIP address short term needs and long term \"master plan\" concepts? Does CIP cover three to five year period? Dees CIP include Goal Statement? Does CIP include description of project area? Does CIP include description of existing facilities? Does CIP include known deficiencies? Does CIP include forecasted future needs? Is CIP designated only for wastewater collection and treatment? Approximate capital improvement budget for collection system? Total annual revenue for wastewater collection and treatment? CIP Comments Is system free of known points of bypass? If no, describe type of bypass and location Is a 24-hour notification sign posted at ALL pump stations? # Does the sign include: Instructions for notification? Pump station identifier? 24-hour contact numbers If no, list deficient pump stations Yes No NA NE • nnn • nnn g nnn nnn n nna? nn;n n n n nnn n nn n nrjn n n®n n n ❑ ❑ n nn nnn ®nnn n n n nnn nnn Page: 3 Permit: WQCSD0258 Owner - Facility: Town of Kingstown Inspection Date: 12/01/2010 Inspection Type: Collection System Inspect Non Sampling Reason for Visit: Routine # Do ALL pump stations have an "auto polling" feature/SCADA? Number of pump stations Number of pump stations that have SCADA Number of pump stations that have simple telemetry Number of pump stations that have only audible and visual alarms Number of pump stations that do not meet permit requirements # Does the permittee have a root control program? # If yes, date implemented? Describe: Pump Stations have simple telemetry. Comment: Inspections Are maintenance records for sewer lines available? Are records available that document pump station inspections? Are SCADA or telemetry equipped pump stations inspected at least once a week? Are non-SCADA/telemetry equipped pump stations inspected every day? Are records available that document citizen complaints? # Do you have a system to conduct an annual observation of entire system? .# Has there been an observation of remote areas in the last year? Are records available that document inspections of high -priority lines? Has there been visual inspections of high -priority lines in last six months? Comment: Operation & Maintenance Requirements Are all log books available? Does supervisor review all log books on a regular basis? Does the supervisor have plans to address documented short-term problem areas? What is the schedule for reviewing inspection, maintenance, & operations logs and problem areas? Weekly. Are maintenance records for equipment available? Is a schedule maintained for testing emergency/standby equipment? What is the schedule for testing emergency/standby equipment'? nunn 3 0 3 0 0 nnn Yes No NA NE ®nnn •.nnn n nn nn_'®n n nn Einnn n nn nnn ®nnn Yes No NA NE ®nnn n nn n nn nnn nnn Weekly Page: 4 Permit: WCCSD0258 Owner - Facility: Town of Kingstown Inspection Date: 12/01/2010 Inspection Type: Collection System Inspect Non Sampling Reason for Visit: Routine Do pump station logs include: Inside and outside cleaning and debris removal? Inspecting and exercising all valves? Inspecting and lubricating pumps and other equipment? Inspecting alarms, telemetry and auxiliary equipment? Is there at least one spare pump for each pump station w/o pump reliability? Are maintenance records for right-of-ways available? Are right-of-ways currently accessible in the event of an emergency? • Are system cleaning records available? Has at least 10% of system been cleaned annually? What areas are scheduled for cleaning in the next 12 months? N/A Is a Spill Response Action Plan available? Does the plan include: 24-hour contact numbers Response time Equipment list and spare parts inventory Access to cleaning equipment Access to construction crews, contractors, and/or engineers Source of emergency funds Site sanitation and cleanup materials Post-overflow/spill assessment Is a Spill Response Action Plan available for all personnel? Is the spare parts inventory adequate? Comment: Records Are adequate records of all SSOs, spills and complaints available? Are records of SSOs that are under the reportable threshold available? Do spill records indicate repeated overflows (2 or more in 12 months) at same location? If yes, is there a corrective action plan? Is a map of the system available? nnn nnn • nnn ggnnn • nEln nnn nnn n n:,n n nn nnn tg nnn • nnn Fannn Iinnn nnn nnn nnn annn nnn Yes No NA NE • nnn nnn nn;an nnn nnn Page: 5 t Permit: WQCSD0258 Owner - Facility: Town of Kingstown Inspection Date: 12/01/2010 Inspection Type: Collection System Inspect Non Sampling Reason for Visit: Routine Does the map include: Pipe sizes Pipe materials Pipe Iccaticn Flow direction Approximate pipe age Number of service taps Pump stations and capacity If no, what percent is complete? List any modifications and extensions that need to be added to the map # Does the permittee have a copy of their permit? Comment: Monitoring and Reporting Requirements Are copies of required press releases and distribution lists available? Are public notices and proof of publication available? # Is an annual report being prepared in accordance with G.S. 143-215.1C? # Is permittee compliant with all compliance schedules in the permits? If no, which one(s)? Comment: Kingston Deemed Collection System is operated by the City of Shelby. KINGSTOWN - 1623 Zion Church Road Pump Station Pump station type Are pump station logs available? Is it accessible in all weather conditions? # Is general housekeeping acceptable? Are all pumps present? Are all pumps operable? Are wet wells free of excessive debris? Are upstream manholes free of excessive debris/signs of overflow? ❑❑nE n ❑❑E ❑ ❑ ❑s ❑ ❑❑rg • El 11 ❑❑❑® nn Yes No NA NE ❑❑®❑ ❑❑❑ ❑ ❑E❑ ❑ ❑®❑ Yes No NA NE Duplex • ❑❑❑ 11❑❑❑. ❑❑❑ ® ❑❑❑ Ell ❑❑❑ n❑❑ ❑❑❑ Page: 6 Permit: WGCSCO258 Owner - Facility: Town of Kingstown Inspection Date: 12/01/2010 Inspection Type: Collection System Inspect Non Sampling Are floats/controls for pumps/alarms operable'? Is "auto polling" feature/SCADA present? Is "auto polling" feature/SCADA operational? Is simple telemetry present? Is simple telemetry operational? Are audio and visual alarms present'? Are audio.and visual alarms operable? Is the Pump station inspected as required? Are backflow devices in place? Are backflow devices operable? Are air relief valves in place? Are air relief valves operable? # Is an emergency generator available? Can the emergency generator run the pumps? Is the pump station equipped for quick hook-up? Is.the generator operable? # Is fuel in tank and sufficient? Is the generator inspected according to their schedule? Is a 24-hour notification sign posted? Does it include: Instructions for notification? Pump station identifier? Emergency phone number Is public access limited? Is pump station free of overflow piping? Is the pump station free of signs of overflow? Are run times comparable for multiple pumps'? Reason for Visit: Routine fannn n npn nn n • nnn nnn nnn • nnn n nnn n nno n nnEm nnnE3 nnnft • nnn • nnn n nn nnn • nnn El El nn.n Comment: This is Kingston's main pump station that sends all of its flow to the City of Shelby. • nnn Ninnn annn B-Annn nnn ionnn 5-10 hours per week Page: 7 Collection System SSO 24-Hour Notification Collection System: Number and Name VVQCV OZS S Incident Number from BIIVIS CD(IDI �c( Incident Reviewed (Date): Incident Action Taken: J NOV-2011-DV CORAO 1 d C C A R 6 72L O H@ S■ a e 222 626•®■ C C 6@ ®E ®® F 9■ H 8 Y 6 C O B® A O E H 6 6 m C 9 1•2 H 0 9 Y 6 9 G E R! 0 e e u c s a (1.cam Spill Date ( Time calm/ pm Reported Date 7i( Time tAc am/isao Reported To SWP Staff or EM Staff (—ors SN► ref Reported By -(9 Phone 70Lt Address of Spill a_, A gr- 2 c - County City (/_,,sss(--evz Cause of Spill C,,e, }- Total Estimated Gallons 14270 Est. Gal to Stream 3 I Strearn r;(2 kusL3 CI Fish Kill: Yes No Number Species Non Required Information and other comments relating to SSO incident: Response time minutes Zone Map Quad 07/06/2011 09:04 704-484-6808 CITY OF SHELBY UDC PAGE 02 Form CS-SSO Collection System Sanitary Sewer Overflow Reporting Form PART 1 This form shall be submitted to the appropriate DWQ Regional Office within five days of the first knowledge of the sanitary sewer overflow (SSO). Permit Nurriber : WQCSD0258 To'mi of Kingstown Facility: Town of Kingetown Owner. City: Kingaton, NC (WQCS# if active, otherwise use treatment plant NC/W 01 \ 3 rC\ Incident # Source of S50 (check applicable) : ❑✓ Sanitary Sewer © Pump Station Region: County Mooresville clevelend SPECIFIC location of the SSO (be consistent in description from past reports or documentation - i,e. Pump Station 6, Manhole 10060803 Manhole at Westall & Bragg Street, etc.) : Latitude (degrees/minute/second): Incident Started Dt: 07 01 2011 (mm-dd-yyyy) 1,270 Estimated volume of the SSO: Time. 10:00 am hh:mm AM/PM Describe how the volume was determined: Weather conditions during SSO event: Hotenddry Did SSO reach surface waters? 0 Yes❑NoE1 Unknown Surface water name; Unnamed tributary of Brushy Creek Did the SSO result in a fish kill? ❑ Yes SPECIFIC cause(s) of the SSO; TD Severe Natural Condition El inflow and Infiltration ❑ Vandalism gallons Longitude(degrees/minute/second): 07-01 2011 11:00 am Incident End Dt Time: (mm-dd-yyyy) hh:mm AM/PM Estimated Duration (Round to nearest hour): 8" pipe=1/10=(400)^1/5(1670)=1270X1hr.1270x25%=318 gals Volume reaching surface waters (gallons): 318 �✓ No ❑ Unknown If Yes, what is the estimated number of fish killed? Immediate 24-hour verbal notification reported to: r` ❑� Grease ❑ Pump Station Equipment Failure E✓ Debris in line Lon Snider ❑ Roots C Power outage ❑ Other (Please explain in Part II) DWQ Emergency Mgmt. Date (mm-dd-yyyy): 07-01-2011 Time (hh:mm AM/PM): 1:45 pm If an SSO is ongoing, please notify Regional Office on a daily basis until SSO can be stopped. Per G.S. 143-215.1 C(b), the responsible party of a discharge of 1,000 gallons or more of untreated wastewater to surface waters shall issue a press release within 48-hours of first knowledge to all print and electronic news media providing general coverage in the county where the discharge occurred, When 15,000 gallons or more of untreated wastewater enters surface waters, a public notice shall be published within 1 D days and proof of publication shall be provided to the Division within 30 days. Refer to the referenced statute for further detail. The Director, Division of Water Quality, may take enforcement action for SSOs that are re uired to be reported to Division unless it is demonstrated that: 1) the discharge was caused by severe natural conditions and there were no feasible alternatives to the discharge; or 2) the discharge was exceptional, unintentional, temporary and caused by factors beyond the reasonable control of the Permittee and/or owner, and the discharge could not have been prevented by the exercise of reasonable control, Part II must be completed to provide a justification claim for either of the above situations. This information will be the basis for the determination of any enforcement action. Therefore, it is important to be as complete as possible. WHETHER OR NOT PART II IS COMPLETED, A SIGNATURE IS REQUIRED AT THE END OF THIS FORM. CS-SSO Form October 9, 2003 Page 1 07/06/2011 09:04 70d-484-6808 CITY OF SHELBY UOC PAGE 01 Shel. -,..„- NORTH CAR.Ot,tNA Post Office 13ax 207 Shelby, NC 20151-0Z07 Fax Transmission Cove- Sheet To: Lon Snider From: Karen Wilkins Company: NC DWQ Date: 7/6/2011 Fax: 704.663.6040 Dept: Utilities Phone: 704.663.1699 Re: Spill Report - Quail Run Dr Message: Following is our report for the Quail Run Dr spill reported on July 1, 2011. .Number- of pees transmitted (including cover sheet) 9 If you do not receive all the pages, please call 704,484.6840 Revfsed 3/2008 www_cityofshelby.com 07/06/2011 09:04 704-484-6808 CITY OF SHELBY UOC PAGE 03 Farm CS-SSO Collection System Sanitary Sewer Overflow Reporting Form PART 1 I ANSWER THE FOLLOWING QUESTIONS FOR EACH RELATED CAUSE CHECKED IN PART I OF THIS FORM AND INCLUDE THE APPROPRIATE DOCUMENTATION AS REQUIRED OR DESIRED COMPLETE ONLY THOSE SECTIONS PERTAINING TO THE CAUSE OF THE SSO AS CHECKED IN PART I In the check boxes below, NA = Not Applicable and NE = Not Evaluated A HARDCOPY OF THIS FORM SHOULD BE SUBMITTED TO THE APPROPRIATE DWQ REGIONAL OFFICE UNLESS IT HAS BEEN SUBMITTED ELECTRONICALLY THROUGH THE ONLINE REPORTING SYSTEM Severe Natural Condition (hurricane, tornado, etc.) Describe the "severe natural condition" in detail. How much advance warning did you have and what actions were taken in preparation for the event? Comments' Grease (Documentation such as cleaning, inspections, enforcem ent actions, past overflow reports, educational material and distribution date etc. should be available upon request.) When was the last time this specific line (or wet well) was cleaned? Do you have an enforceable grease ordinance that requires new or retrofit of grease traps/interceptors? Have there been recent inspections and/or enforcement actions taken on nearby restaurants or other. nonresidential grease contributors? Explain. No restaurants EJYesLJ No❑NAONE Yes❑ No E NA ❑ NE Have there been other SSOs or blockages in this area that were also caused by grease? ❑YesErNo El NA ❑NE When? If yes, describe them: Have cleaning and inspections ever been increased at this location? Explain_ ❑Yes No❑NA❑NE CS-SSO Form October 9. 2003 Page 2 07/06/2011 09:04 704-484-6808 CITY OF SHELBY UOC PAGE 04 Have educational materials about grease been distributed in the past? ❑Yesl--U No ❑ NA u NE When? and to whom? Explain? If the SSO occurred at a pump station, when was the wet well and pumps last checked for grease accumulation? Were the floats clean? Comments: OYEZ) No❑NAQNE Roots Do you have an active root control program? Describe ❑ YesD No ❑ NA ❑ NE Have cleaning and inspections ever been increased at this location because of roots? Explain_ L1YeJIIl NoLNALJNE What corrective actions have been accomplished at the SSO location (and surrounding system if associated with the SSO)? What corrective actions are planned at the SSO location to reduce root intrusion'? Has the line been smoke tested or videoed within the past year? ilYe If Yes, when? Comments: NoNA❑NE Inflow and Infiltration ��yy T 1 d�I Are you under an SOC (Special Order by Consent) or do you have a schedule in any permit that &--1 Ye.� l No DNA UNE addresses UI? CS-SSO form October 9, 2003 Page 3 07/06/2011 09:04 704-484-6808 CITY OF SHELBY UOC PAGE 05 Explain if Yes: What corrective actions have been taken to reduce or eliminate I & I related overflows at this spill location within the last year? 1--c Has there been any flow studies to determine I/1 problems in the collection system at the SSO location? YeE No DNAONE ONE If Yes, when was the study completed and what actions did it recommend? Has the line been smoke tested orvideoed within the past year? ❑YesO No CNA ENE If Yes, when and indicate what actions are necessary and the status of such actions: Are there I/I related projects in your Capital Improvement Plan? If Yes, explain: Yes0 No NA Have there been any grant or loan applications for 1/1 reduction projects? flYasin No IJNA DNE If Yes, explain: Do you suspect any major sources of inflow or cross connections with storm sewers? ❑Yes — No ENA ®NE If Yes, explain: -� �l Have all lutes contacting surface waters in the SSO location and upstream been inspected recently? ElYen NoCNA ENE If Yes, explain: What other corrective action9 are planned to prevent future I/1 related SSOe et this location? Comments: Pump Station Equipment Failure (Documentation of testing, records etc., shoul be provided upon request.) What kind of notification/alarm systems are present? Auto-dialer/telemetry (one-way communication) ❑Yee CS-SSO Fonn October 9, 2003 Page 4 07/06/2011 09:04 704-484-6808 CITY OF SHELBY UOC PAGE 06 Audible 1JYes ❑Yes Visual SCADA (two-way communication) l_lYes Emergency Contact Signage Yes ❑Yes Other Describe the equipment that failed? What kind Of situations trigger an alarm condition at this station (i.e. pump failure, power failure, high water, etc.)? Ware notification/alarm systems operable? If no, explain: ❑YesEll No UNA TINE If a pump failed, when was the last maintenance and/or inspection performed? What specifically was checked/maintained? If a valve failed, when was it last exercised'? Were all pumps set to alternate? Did any pump show above normal run times prior to and during the SSO event? Were adequate spare parts on hand to fix the equipment (switch, fuse, valve, seal, etc.)? Was a spare or portable pump immediately available? If a float ptoblern, when were the floats last tested? Haw? ❑Yes No ❑NA❑NE CI Yes® NoGNAEINE ❑YeFV I No NA CI NE EllYesO No❑NADNE If an auto=dialer or SCADA, when was the system last tested? How'? Comments: CS-SSO Form October 9, 2003 Page 5 mit 07/06/2011 09:04 704-484-6808 CITY OF SHELBY UOC PAGE 07 Power outage (Documentation of testing records, etc., should be provided of alternative power source upon request.) What is your alternate power or pumping source? Or-`.Slito :GeberatorifidAT Did it function properly? Describe? When was the alternate power or pumping source last tested under load? ❑YesIL I No CNA ONE If caused by a weather event, how much advance warning did you have and what actions were taken to prepare for the event? Comments: Vandalism Provide police report number: Was the site secured?" if YP4 hr.nr7 Padlocked Control Panel CDYesu NOENADNE Have there been previous problems with vandalism at the SSO location? If Yes, explain: NA NE What security measures have been put in place to prevent similar occurrences in the future? ]Yesd No NA UNE Comments: Debris in line (Rocks, sticks, rags and other items not allowed in the collection system, etc,) What type of debris has been found in the litre? Sticks How could it have gotten there? Had to be placed into system through vent holes in lid. Are manholes in the area secure and intact? UyesLJ NoL NA ®NE CS-SSO Form October 9, 2003 Page 6 07/06/2011 09:04 704-484-6808 CITY OF SHELBY UOC PAGE 08 When was the area last checked/cleaned? Have cleaning and inspections ever been increased at this location due to previous problems with debris? °YesEl No LNAClNE Explain: • Are appropriate educational materials being developed and distributed to prevent future similar occurrences? Comments: YesNoDNA UNE Other (Pictures and a police report should be available upon request.) Describe: Were adequate equipment and resources available to fix the problem? DYe If Yes, explain: No _ NA ©NE If the problem could not be immediately repaired, What actions were taken to lessen the impact of the SSO? Comments: For DWQ Use Only: DWQ Requested an Additional Written Report: If Yes, What Additional Information Is Needed: DyesL No DNA u NE Comments: CS-SSO Form October 9, 2003 Page 7 07/06/2011 09:04 704-484-6808 CITY OF SHELBY UDC PAGE 09 Asa representative for the responsible party, I certify that the information contained in this report is true and accurate to the best of my knowledge. Person submitting claim: Mark Swink Signature: Date: 7/6/11 Field Operations Superintendent Title: Telephone Number: 704-484-6840 Any additional information desired to be submitted should be sent to the appropriate Division Regional Office within five days of first knowledge of the SSO with reference to the incident number (the incident number is only generated when electronic entry of this form is completed, if used). CS-SSO Form October 9, 200 Page 8