HomeMy WebLinkAboutNC0041866_Compliance Evaluation Inspection_20210304ROY COOPER
Governor
MICHAEL 5. REGAN
Secretary
S. DANIEL SMITH
Director
Robert K Draughn
Surry County Schools
PO Box 364
Dobson, NC 27017-0364
NORTH CAROLINA
Environmental Qualiay
March 04, 2021
SUBJECT: Compliance Inspection Report
Mountain Park Elementary
NPDES WW Permit No. NC0041866
Surry County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Mountain Park
Elementary on 2/24/2021. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in NPDES WW Permit No. NC0041866. The
findings and comments noted during this inspection are provided in the enclosed copy of the inspection
report entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required. ORC Larry Riggans demonstrated good maintenance and operations
practices, all within the purview of the permit requirements.
North Caro;i au Department of Euv.rournenta' Quality I Divisor of Water Resources
WinstouSaiem Regans! Office 1450 West ffsaes Mill Road, Suite 300 I WiustouSECem. North Carob 27105
336-776-9500
If you should have any questions, please do not hesitate to contact Alex Lowe with the Water Quality
Regional Operations Section in the Winston-Salem Regional Office at 336-776-9800 or via email at
alex.lowe@ncdenr.gov.
Sincerely,
,-0ocuSigned by:
L-o1.. 1. <JMl1ft
145B49E225C94EA...
Lon T. Snider, Regional Supervisor
Water Quality Regional Operations Section
Winston-Salem Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: WQS Winston-Salem Regional Office - Enforcement File
NPDES Compliance/Enforcement Unit - Enforcement File
Laserfiche — Digital Enforcement File
North Csro;i au Department of Euv.rournental Quality I Divisor of Water Resources
WinstouS81em Regans! Office 1450 West ffsaes Mill Road, Suite 300 I Wius-SECe111. North Carob 27105
336-776-9500
United States Environmental Protection Agency
E PA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction
1 IN I
21I I
Code NPDES yr/mo/day Inspection
2 LI 3 I NC0041866 111 121 21/02/24 I17
Type
1810I
I I I I I
Inspector Fac Type
19I S I 2011
I 1 1 1 I I I I II I I I I I I I I I I I I I I I I I
I II
I I I I I P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
671 I 7° I I 711 172 I N I 73I 1 74 71
I I 1
I I I I I I 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Mountain Park Elementary
197 Mtn Park Rd
State Road NC 28676
Entry Time/Date
08:50AM 21/02/24
Permit Effective Date
19/01/01
Exit Time/Date
09:50AM 21/02/24
Permit Expiration Date
23/12/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Larry Odell Riggans/ORC/336-386-8381/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Robert K Draughn,PO Box 364 Dobson NC
270170364/Director/336-386-8381/3363864279 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Facility Site Review Effluent/Receiving Wate Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Alex Lowe DWR/WSRO WQ/336-776-9689/
Signature
of Manaaement Q A Reviewer Agency/Office/Phone and Fax Numbers Date
�DocuSigned by:
L- A, 'T.Sti41cs- 3/4/21
145B49E225C94EA...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
sI
NPDES yr/mo/day
NC0041866 111 121 21/02/24
117
Inspection Type
18 [j
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On February 4th, Environmental Specialist Alex Lowe of the North Carolina Division of Water
Resources conducted an inspection of Mountain Park Elementary School wastewater treatment
system. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NC0041866. ORC Larry Riggans was
present.
ORC was unable to provide copy of permit or past reporting data at the site, as it was filed in the
administrative building. Due to ongoing COVID-19 precautions, Lowe opted not to travel to the office,
but instead requested that photocopies be sent for review. These copies were provided promptly the
same morning. All records appear well organized and maintained.
No signs of permit violation were observed in the treatment process. The site was well maintained, and
backup parts were present for all necessary systems (e.g. the UV bulbs and plastic sprinkler heads.
Page# 2
Permit: NC0041866
Inspection Date: 02/24/2021
Owner - Facility: Mountain Park Elementary
Inspection Type: Compliance Evaluation
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Yes No NA NE
• ❑ ❑ ❑
Comment: Plant areas are well maintained and organized. ORC indicated upcoming replacement of
septic holding tank (current tank is original to 1950s era school buildings) and replacing sari(
on filter bed.
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Yes No NA NE
❑ ❑ • ❑
Comment: Permit is kept off -site at administrative building, which I decided to avoid due to ongoing
COVID-19 precautions. Follow-up email from office provided a photocopy of the permit as
requested.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment: Effluent sampling collected weekly by ORC with manual grab.
Yes No NA NE
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
❑ ❑ • ❑
• ❑ ❑ ❑
Disinfection -Tablet Yes No NA NE
Are tablet chlorinators operational? • ❑ ❑ ❑
Are the tablets the proper size and type? • ❑ ❑ ❑
Number of tubes in use? 0
Is the level of chlorine residual acceptable? ❑ ❑ • ❑
Is the contact chamber free of growth, or sludge buildup? • ❑ ❑ ❑
Is there chlorine residual prior to de -chlorination? ❑ ❑ • ❑
Page# 3
Permit: NC0041866
Inspection Date: 02/24/2021
Owner - Facility: Mountain Park Elementary
Inspection Type: Compliance Evaluation
Disinfection -Tablet Yes No NA NE
Comment: Chlorination contact chambers are not used regularly, but are in place as a backup in case
of UV system failure.
Disinfection - UV
Are extra UV bulbs available on site?
Are UV bulbs clean?
Is UV intensity adequate?
Is transmittance at or above designed level?
Is there a backup system on site?
Is effluent clear and free of solids?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: ORC stated that he always orders four bulbs whenever he replaces existing two bulbs, so
he always has at least two extras on site. They are cleaned weekly, and replaced annually,
or more frequently if fecal becomes an issue.
Septic Tank
(If pumps are used) Is an audible and visual alarm operational?
Is septic tank pumped on a schedule?
Are pumps or syphons operating properly?
Are high and low water alarms operating properly?
Yes No NA NE
❑ ❑ • ❑
• ❑ ❑ ❑
Comment: Septic tank is entirely gravity fed. Sludge is pumped at the end of the school year every five
years, or as needed.
Sand Filters (Low rate)
(If pumps are used) Is an audible and visible alarm Present and operational?
Is the distribution box level and watertight?
Is sand filter free of ponding?
Is the sand filter effluent re -circulated at a valid ratio?
# Is the sand filter surface free of algae or excessive vegetation?
# Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1)
Comment: Recirculation pump is operable and alarm is present and functioning.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Yes No NA NE
• ❑ ❑ ❑
❑ ❑ ❑ •
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
❑ ❑ • ❑
Page# 4
Permit: NC0041866
Inspection Date: 02/24/2021
Owner - Facility: Mountain Park Elementary
Inspection Type: Compliance Evaluation
Effluent Pipe Yes No NA NE
Comment: Drains to dry/rainwater drainage ditch which runs through several hundred feet of meadow
before contact with surface waters.
Flow Measurement - Influent Yes No NA NE
# Is flow meter used for reporting? • El El El
Is flow meter calibrated annually? • ❑ ❑ ❑
Is the flow meter operational? • ❑ ❑ ❑
(If units are separated) Does the chart recorder match the flow meter? ❑ ❑ • ❑
Comment: Flow into treatment plant is measured with meter on school building.
Pump Station - Effluent
Is the pump wet well free of bypass lines or structures?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry available and operational?
Is audible and visual alarm available and operational?
Yes No NA NE
• ❑ ❑ ❑
Comment: ORC demonstrated effectiveness of both effluent and recirculation pump wells.
Page# 5