SUBJECT: Compliance Inspection Report
Champion Hills WWTP
Non-discharge Permit No. WQ0004115
Henderson County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Champion Hills WWTP
on 1/29/2021. This inspection was conducted to verify that the facility is operating in compliance with
the conditions and limitations specified in Non-discharge Permit No. WQ0004115. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact me at 828-296-4686 or via email at
mikal.willmer@ncdenr.gov.
Sincerely,
Mikal Willmer, Environmental Specialist II
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Summary
Ec: LF
DocuSign Envelope ID: AFA00D1B-EC9A-4BF6-8EC5-EF673708E952
Compliance Inspection Report
Permit:WQ0004115 Effective:02/01/19 Expiration:03/31/24 Owner :Champion Hills Property Owners Association
Inc
SOC:
Contact Person:
Region:
County:
Directions to Facility:
Henderson
Asheville
Craig Galloway
Effective:Expiration:Facility:Champion Hills WWTP
1000 Indian Cave Rd
Hendersonville NC 28739
Title:Phone:828-696-1662Director of Grounds & Facilities
Secondary ORC(s):
Phone:Certification:Primary ORC:
System Classifications:
On-Site Representative(s):
Related Permits:
NC0087106 Champion Hills Property Owners Association Inc - Champion Hills WWTP
Secondary Inspector(s):
Primary Inspector:
Inspection Date:Exit Time:Entry Time:
Phone:
01/29/2021 07:45AM 08:40AM
Mikal Willmer 828-296-4686
Facility Status:
Permit Inspection Type:
Reason for Inspection:Inspection Type:
Not CompliantCompliant
Routine
Reclaimed Water
Compliance Evaluation
Question Areas:
Treatment Flow Measurement-Effluent Treatment Flow Measurement-Influent Miscellaneous Questions
Treatment Flow Measurement-Water
Use Records
Treatment Treatment Filters
Record Keeping Treatment Activated Sludge Treatment Clarifiers
Treatment Disinfection Treatment Flow Measurement End Use-Reuse
Standby Power
(See attachment summary)
Page 1 of 7
DocuSign Envelope ID: AFA00D1B-EC9A-4BF6-8EC5-EF673708E952
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0004115
01/29/2021 Compliance Evaluation
Champion Hills Property Owners Association Inc
Routine
Inspection Summary:
Mikal Willmer, with the Asheville Regional Office, conducted a compliance evaluation inspection of the Champion Hills
WWTP and irrigation system on January 29, 2021. This inspection was conducted to determine whether the facility was
being operated and maintained in compliance with Non-Discharge Permit WQ0004115. Danielle Hunter and Robert Barr with
RPB systems were present and assisted in the inspection.
Overall, the facility appeared to be compliant with Non-Discharge Permit No. WQ0004115. At the time of the inspection,
several items were in the process of being repaired. The ORC indicated communication has improved between operations
staff and Champion hills staff regarding notification of use of the spray irrigation system. This ensures samples can be
collected as required by the permit.
Pine trees have been cleared immediately surrounding the WWTP to reduce daily maintenance from pine needle debris
entering the facility. Some damage was noted to the safety railing from the tree removal. The turnaround area has been
expanded providing increased access to the facility for equipment and vehicles.
Generator: A new generator was recently installed; however, it is not currently operational. Champion Hills staff are working
with an electrician to determine the cause. ORC indicated the facility does not typically have issues with power reliability.
Facility staff have noted an increased volume of wipes in the facility since the beginning of the pandemic; however, the ORC
reports this has not significantly affected any of the treatment units. Mr. Galloway (Champion Hills Director of Grounds)
indicated biannual FOGS education is distributed to residents. If not already included, it is recommended flushable wipes be
added to the literature.
Flow Meter: The flow meter was in the process of being replaced at the time of the inspection.
Safety Grates/EQ Basin: All safety grates appear to have been replaced and new floats were recently installed within the EQ
basin.
Sludge Holding Tank: ORC reported she was unable to have the holding tank pumped down due to the sump no longer
working (line appeared to be broken during the recent tree removal). The tank floats if this is not operational.
Turbidimeter: The ARO and Central Office received the turbidimeter calibration information on 6/14/19, per section I.2 of the
most recent permit. The permit issued in 2019 now requires annual turbidimeter calibration.
Irrigation Pond: No tears were noted in the pond liner and the berms appeared free of any seeps or erosion. Pond had
adequate freeboard levels and primarily contains rainwater since the irrigation system is not in use during the winter.
O&M Plan: Parts of an O&M plan appeared to be maintained within the blower building at the WWTP. Champion Hills
should review this documentation to ensure all elements required by the permit are included and kept in a central location for
reference by all facility staff. This is to ensure consistency among all staff associated with the WWTP and spray irrigation
system. Refer to section III.2 of the permit for the minimum information.
Irrigation Equipment Calibration: Irrigation equipment was calibrated in 2018. As a reminder, irrigation equipment is required
to be calibrated once per permit cycle. The next calibration will be due before the permit expires in 2024.
Modification: Should Champion Hills wish to increase the irrigation area and/or add acreage to the permit, a major
modification would be required. Additionally, please keep the Asheville Regional Office and Non-Discharge Permitting Branch
apprised of any planned changes to the system.
Page 2 of 7
DocuSign Envelope ID: AFA00D1B-EC9A-4BF6-8EC5-EF673708E952
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0004115
01/29/2021 Compliance Evaluation
Champion Hills Property Owners Association Inc
Routine
Type Yes No NA NE
Infiltration System
Single Family Spray, LR
Lagoon Spray, LR
Activated Sludge Spray, LR
Activated Sludge Spray, HR
Activated Sludge Drip, LR
Single Family Drip
Recycle/Reuse
Reuse (Quality)
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit?
Do all treatment units appear to be operational? (if no, note below.)
All treatment units appeared to be operational; however, a few pieces of accessory equipment
were in the process of being fixed/replaced.
Comment:
Treatment Flow Measurement-Influent Yes No NA NE
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Does flowmeter appear to monitor accurately?
An influent flow meter is no longer in use.Comment:
Treatment Flow Measurement-Water Use Records Yes No NA NE
Is water use metered?
Are the daily average values properly calculated?
Comment:
Treatment Flow Measurement-Effluent Yes No NA NE
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Does flowmeter appear to monitor accurately?
Flow meter was in the process of being replaced at the time of the inspection. Chart recorder is
also still used onsite.
Comment:
Page 3 of 7
DocuSign Envelope ID: AFA00D1B-EC9A-4BF6-8EC5-EF673708E952
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0004115
01/29/2021 Compliance Evaluation
Champion Hills Property Owners Association Inc
Routine
Standby Power Yes No NA NE
Is automatically activated standby power available?
Is generator tested weekly by interrupting primary power source?
Is generator operable?
Does generator have adequate fuel?
New Kohler natural gas generator. Champion Hills maintains the generator. Currently new
generator will not operate, and permittee is working with electrician to find a solution. When in
operation the generator self-tests every Monday. ORC reports the facility rarely loses power
Comment:
Treatment Activated Sludge Yes No NA NE
Is the aeration mechanism operable?
Is the aeration basin thoroughly mixed?
Is the aeration equipment easily accessed?
Is Dissolved Oxygen adequate?
Are Settleometer results acceptable?
Is activated sludge an acceptable color?
Blowers and diffusers appeared to be working at the time of the inspection. No dead spots or
excessive foam noted within the basin.
Comment:
Treatment Clarifiers Yes No NA NE
Are the weirs level?
Are the weirs free of solids and algae?
Is the scum removal system operational?
Is the scum removal system accessible?
Is the sludge blanket at an acceptable level?
Is the effluent from the clarifier free of excessive solids?
Appeared to be a few pop ups on the clarifier during the inspection; however, the effluent exiting
the facility appeared free of visible solids.
Comment:
Treatment Filters Yes No NA NE
Is the filter media present?
Is the filter media the correct size and type?
Is the air scour operational?
Is the scouring acceptable?
Is the clear well free of excessive solids?
Is the mud well free of excessive solids and filter media?
Does backwashing frequency appear adequate?
Facility effluent data indicates the tertiary filters are working adequately and ORC reports no
issues maintaining filters since they have been repaired and put back into use.
Comment:
Treatment Disinfection Yes No NA NE
Page 4 of 7
DocuSign Envelope ID: AFA00D1B-EC9A-4BF6-8EC5-EF673708E952
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0004115
01/29/2021 Compliance Evaluation
Champion Hills Property Owners Association Inc
Routine
Is the system working?
Do the fecal coliform results indicate proper disinfection?
Is there adequate detention time (>=30 minutes)?
Is the system properly maintained?
If gas, does the cylinder storage appear safe?
Is the fan in the chlorine feed room and storage area operable?
Is the chlorinator accessible?
If tablets, are tablets present?
Are the tablets the proper size and type?
Is contact chamber free of sludge, solids, and growth?
If UV, are extra UV bulbs available?
If UV, is the UV intensity adequate?
# Is it a dual feed system?
Does the Stationary Source have more than 2500 lbs of Chlorine (CAS No. 7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1000-____-____)
If yes, then when was the RMP last updated?
Chlorine tablets are used.Comment:
Record Keeping Yes No NA NE
Is a copy of current permit available?
Are monitoring reports present: NDMR?
NDAR?
Are flow rates less than of permitted flow?
Are flow rates less than of permitted flow?
Are application rates adhered to?
Is GW monitoring being conducted, if required (GW-59s submitted)?
Are all samples analyzed for all required parameters?
Are there any 2L GW quality violations?
Is GW-59A certification form completed for facility?
Is effluent sampled for same parameters as GW?
Do effluent concentrations exceed GW standards?
Are annual soil reports available?
# Are PAN records required?
# Did last soil report indicate a need for lime?
If so, has it been applied?
Are operational logs present?
Page 5 of 7
DocuSign Envelope ID: AFA00D1B-EC9A-4BF6-8EC5-EF673708E952
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0004115
01/29/2021 Compliance Evaluation
Champion Hills Property Owners Association Inc
Routine
Are lab sheets available for review?
Do lab sheets support data reported on NDMR?
Do lab sheets support data reported on GW-59s?
Are Operational and Maintenance records present?
Were Operational and Maintenance records complete?
Has permittee been free of public complaints in last 12 months?
Is a copy of the SOC readily available?
No treatment units bypassed since last inspection?
Facility no longer has groundwater monitoring. Operator logs were thorough. Parts of an O&M
plan appear to be maintained within the building onsite. See summary for details.
Comment:
End Use-Reuse Yes No NA NE
Is the acreage in the permit being utilized?
Does the acreage specified in the permit correspond to the measured acreage at the site?
Are all essential units provided in duplicate?
Is an automatically activated standby power source available?
Is the equalization capacity adequate?
Is aerated flow equalization present?
Has the turbidity meter been calibrated in the last 12 months?
Does the turbidity meter have recording capabilities?
Is all flow diverted at the appropriate times?
Is all upset wastewater diverted from reuse storage unit?
Is all upset wastewater treated, retreated, or disposed of acceptably?
Is upset wastewater treated prior to discharge to irrigation storage?
Is public access restricted from irrigation area during active site use?
If golf course, is a sign posted in plain sight on the club house?
Is the cover crop acceptable?
Are buffers adequate?
Is the site free of ponding/runoff?
Is the acreage in the permit being utilized?
Is the application equipment acceptable?
Is the application area free of limiting slopes?
How close is the closest water supply well?
Are any supply wells within the CB?
Are any supply wells within 250' of the CB?
Is municipal water available in the area?
Are GW monitoring wells required?
Page 6 of 7
DocuSign Envelope ID: AFA00D1B-EC9A-4BF6-8EC5-EF673708E952
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0004115
01/29/2021 Compliance Evaluation
Champion Hills Property Owners Association Inc
Routine
Are GW monitoring wells located properly w/ respect to RB and CB?
Are GW monitoring wells properly constructed, including screened interval?
The system is currently switched to the NPDES discharge for the winter so irrigation patterns
were not assessed. Irrigation occurs when the golf course is not in use. The facility does not
have an upset pond. All upset wastewater manually diverted to the stream discharge. Champion
Hills hopes to inspect the irrigation pond liner this year. The permittee may pursue additional
acreage for the reuse permit. Reuse water not meeting fecal limits cannot be immediately
diverted due to time required for analysis.
Comment:
Page 7 of 7
DocuSign Envelope ID: AFA00D1B-EC9A-4BF6-8EC5-EF673708E952
Certificate Of Completion
Envelope Id: AFA00D1BEC9A4BF68EC5EF673708E952 Status: Completed
Subject: Please DocuSign: WQ0004115_CEI ltr.docx, WQ0004115_CEI insp.pdf
Source Envelope:
Document Pages: 8 Signatures: 1 Envelope Originator:
Certificate Pages: 1 Initials: 1 Mikal Willmer
AutoNav: Enabled
EnvelopeId Stamping: Enabled
Time Zone: (UTC-05:00) Eastern Time (US & Canada)
217 W. Jones Street
Raleigh, NC 27699
Mikal.willmer@ncdenr.gov
IP Address: 149.168.204.10
Record Tracking
Status: Original
Feb 22, 2021 | 08:07
Holder: Mikal Willmer
Mikal.willmer@ncdenr.gov
Location: DocuSign
Security Appliance Status: Connected Pool: StateLocal
Storage Appliance Status: Connected Pool: North Carolina Department of Environmental
Quality
Location: DocuSign
Signer Events Signature Timestamp
Mikal Willmer
mikal.willmer@ncdenr.gov
Environmental Specialist
North Carolina Department of Environmental Quality
Security Level: Email, Account Authentication
(None)
Signature Adoption: Pre-selected Style
Using IP Address: 149.168.204.10
Sent: Feb 22, 2021 | 08:23
Viewed: Feb 22, 2021 | 08:23
Signed: Feb 22, 2021 | 08:23
Electronic Record and Signature Disclosure:
Not Offered via DocuSign
In Person Signer Events Signature Timestamp
Editor Delivery Events Status Timestamp
Agent Delivery Events Status Timestamp
Intermediary Delivery Events Status Timestamp
Certified Delivery Events Status Timestamp
Carbon Copy Events Status Timestamp
Witness Events Signature Timestamp
Notary Events Signature Timestamp
Envelope Summary Events Status Timestamps
Envelope Sent Hashed/Encrypted Feb 22, 2021 | 08:23
Certified Delivered Security Checked Feb 22, 2021 | 08:23
Signing Complete Security Checked Feb 22, 2021 | 08:23
Completed Security Checked Feb 22, 2021 | 08:23
Payment Events Status Timestamps