Loading...
HomeMy WebLinkAboutWQ0002284_Compliance Evaluation Inspection_20210215ROY COOPER Governor MICHAEL S. REGAN Seartary S. DANIEL SMITH Director NORTH CAROLINA Environmental Quality February 15, 2021 Ray E Hollowell Outer Banks/Kinnakeet Associates LLC PO Box 34 Connelly Spring, NC 28612 SUBJECT: Compliance Inspection Report Kinnakeet Shores WWTP Non -discharge Permit No. WQ0002284 Dare County Dear Mr. Hollowell: The North Carolina Division of Water Resources conducted an inspection of the Kinnakeet Shores WWTP on 12/18/2020. This inspection was conducted to verify that the facility is operating in compliance with the conditions and limitations specified in Non -discharge Permit No. WQ0002284. The findings and comments noted during this inspection are provided in the enclosed copy of the inspection report entitled "Compliance Inspection Report". Please respond in writing to this office within 15 days of your receipt of this letter regarding your plans or measures to be taken to address the issues noted in the Inspection report and the Notice of Violation/Notice of Intent to Enforce. North Caro no Deportment of Env ron menus Qua-ty D %son, of Water Resources Wah njton Rai ma Off ce 1943 Wah-njton Sooxt s?a: I Wan r'gton, North Coro 27889 25244S-64S1 If you should have any questions, please do not hesitate to contact Sarah Toppen with the Water Quality Regional Operations Section in the Washington Regional Office at 252-946-6481 or via email at Sarah.Toppen@ncdenr.gov. ATTACHMENTS Cc: Laserfiche Sincerely, Sarah Toppen, Environmental Specialist II Water Quality Regional Operations Section Washington Regional Office Division of Water Resources, NCDEQ h.+R :arz *e 0epertmeatof Eavroameata QUA n I ONsoa of Water Fes -....ryes Was., rgton Regal* Offve 1943 West -Aston Squint Meal I WWi-a3taa, horns Caro ae 27889 252 4-8481 Compliance Inspection Report Permit: WO0002284 Effective: 08/17/18 SOC: Effective: County: Dare Region: Washington Contact Person: Ray E Hollowell Expiration: 02/28/23 Expiration: Owner : Outer Banks/Kinnakeet Associates LLC Facility: Kinnakeet Shores WWfP 41105 Big Kinnakeet Dr Avon NC 27915 Title: Manager Phone: Directions to Facility: On the outer banks, take NC Hwy 12 south of Rodanthe to Avon and take a right onto Big Kinnakeet Drive and follow to the gated end of drive System Classifications: SI, WW2, Primary ORC: David Pharr Certification: 21101 Phone: 252-473-3461 Secondary ORC(s): On -Site Representative(s): Related Permits: Inspection Date: 12/18/2020 Primary Inspector: Sarah A Toppen Secondary Inspector(s): Entry Time 10:OOAM Reason for Inspection: Routine Permit Inspection Type: Reclaimed Water Facility Status: ❑ Compliant iii Not Compliant Question Areas: ▪ Treatment Flow Measurement -Effluent • Treatment Flow Measurement -Water Use Records II Treatment Filters ▪ Treatment Clarifiers ▪ Treatment Flow Measurement ▪ Wells (See attachment summary) Exit Time: 11:30AM Phone: 252-946-6481 Inspection Type: Compliance Evaluation ▪ Treatment Flow Measurement -Influent II Treatment I. Treatment Activated Sludge ▪ Treatment Disinfection ▪ End Use -Reuse MI Miscellaneous Questions • Treatment Barscreen • Treatment Sludge Storage/Treatment III End Use -Infiltration ▪ Standby Power Page 1 of 8 Permit: W00002284 Owner - Facility:Outer Banks/Kinnakeet Associates LLC Inspection Date: 12/18/2020 Inspection Type : Compliance Evaluation Reason for Visit: Routine Inspection Summary: On December 18, 2020, Sarah Toppen and Robert Tankard with NCDWR conducted a Compliance Inspection with David Pharr, ORC, and Michelle Pharr present. A walk through of the facility was conducted. Both clarifiers,the traveling bridge filter, and the generator were not working the day of inspection. Also, the last date that sludge has been removed from the plant is unknown. In the facilities current permit dated August 17, 2018 the schedule has several dates that have expired and our Division has not recieved the information to show that it has been completed. The list is below: 1. Within 90 days of permit issuance, the Permittee shall submit a permit modification addressing the following: a. Several residences appear to be within 100 feet of the 5-day upset pond. Any residences that are within 100 feet and were there prior to the permitting of the pond, must have a setback waiver. [15A NCAC 02T .0506(d)] b.Easements for all parcels not owned by the applicant specifically indicating the intended use of the property and meeting the condition of 15A NCAC 02L .0107(f). [15A NCAC 02U .0202(f)(3)] c. Provide a table listing each irrigation field, property owner(s), and easement book and page. d. A site map with a scale no greater than 1-inch equals 100 feet; however, special provisions may be granted upon prior approval for large properties. At a minimum, the map shall include the following information: i. The location and identity of each monitoring well. ii. The location and major components of the waste disposal system. iii. The wetted perimeter of all irrigation fields. iv. The location and ownership of property boundaries within 500 feet of the disposal areas. v. The location of all wells, streams (ephemeral, intermittent, and perennial), wetlands, springs, lakes, ponds, ditches, and other surface drainage features within 500 feet of all facilities. vi. The elevation of the top of the well casing (i.e., measuring point) relative to a common datum. vii. The depth of water below the measuring point at the time the measuring point is established. viii.The delineation of compliance and reivew boundaries. ix. The minimum distance for approved setback waivers. x. The date the map is prepared and/or revised. [15A NCAC 02T .0108(b)(2)] 3. The permit dated March 14, 2018 required that the Permittee provide a functioning flow meter for the reclaimed irrigation system and have the reclaimed water spray irrigation system operational no later than August 1, 2018. Per Notice of Violation NOV-2018-PC-0311, the Permittee failed to have the flow meter and reclaim irrigation system operational by August 1, 2018. The Permittee remains in noncompliance with this permit condition and is subject to daily civil penalty assessment until such time as compliance with this condition has been met. The Washington Regional Office, telephone number (252)946-6481, shall be notified whe the flow meter and irrigation system is functioning such that an in -place inspection can be made. [15A NCAC 02T .0108(b)(2) 4. The permit dated March 14, 2018 requried that the Permittee install monitoring wells MW-10, MW-11, and MW-12 prior to June 12, 2018. Per Notice of Violation NOV-2018-PC-0311, the Permittee failed to install the wells prior to June 12, 2018. The Permittee shall install the wells and sample the monitoring wells per permit conditions. The Permittee remains in noncompliance with this condition and is subect to daily civil penalty assessments until such time as compliance with this condition has been met. Washington Regional Office, telephone number (252)946-6481, shall be notified when the system has been installed and certified such that an in -place inspection can be made. [15A NCAC 02T .0108(b)(2)] 5. Prior to April 1, 2019, the Permittee shall replace the tertiary filter media. Compliance with this condition shall be verified with an inspection by the Washington Regional Office. [15A NCAC 02T .0108(b)(2)] 6. Prior to March 14, 2020, the Permittee shall repair the damaged roof above the wastewater treatment facility. Compliance with this condition shall be verified with an inspection by the Washington Regional Office [15A NCAC 02T .0108 (b)(2)] Page 2 of 8 Permit: WO0002284 Owner - Facility:Outer Banks/Kinnakeet Associates LLC Inspection Date: 12/18/2020 Inspection Type : Compliance Evaluation Reason for Visit: Routine The facility is in noncompliance. Please refer to the summary above and the rest of the inspection report for more details of what needs repairs/replacements. Page 3 of 8 Permit: WQ0002284 Owner - Facility:Outer Banks/Kinnakeet Associates LLC Inspection Date: 12/18/2020 Inspection Type : Compliance Evaluation Reason for Visit: Routine Type Yes No NA NE Activated Sludge Spray, LR ❑ Activated Sludge Spray, HR ❑ Single Family Spray, LR ❑ Infiltration System ❑ Lagoon Spray, LR ❑ Activated Sludge Drip, LR ❑ Recycle/Reuse ❑ Single Family Drip ❑ Reuse (Quality) Treatment Are Treatment facilities consistent with those outlined in the current permit? Do all treatment units appear to be operational? (if no, note below.) Comment: There are several treatment units not working the day of both clarifiers and the traveling bridge filter. Treatment Flow Measurement -Influent Is flowmeter calibrated annually? Is flowmeter operating properly? Does flowmeter monitor continuously? Does flowmeter record flow? Does flowmeter appear to monitor accurately? Comment: Treatment Flow Measurement -Water Use Records Is water use metered? Are the daily average values properly calculated? Comment: Treatment Flow Measurement -Effluent Is flowmeter calibrated annually? Is flowmeter operating properly? Does flowmeter monitor continuously? Does flowmeter record flow? Does flowmeter appear to monitor accurately? Yes No NA NE • ❑ ❑ ❑ ❑ • ❑ ❑ the inspection. the units not working an Yes No NA NE ❑❑■❑ O 0110 ❑ ❑■❑ ❑ ❑•❑ ❑ ❑•❑ Yes No NA NE ❑ ❑ • ❑ ❑ ❑■❑ Yes No NA NE ▪ ❑ ❑ ❑ O 1E00 O 1E00 01100 011100 Page 4 of 8 Permit: W00002284 Owner - Facility:Outer Banks/Kinnakeet Associates LLC Inspection Date: 12/18/2020 Inspection Type : Compliance Evaluation Reason for Visit: Routine Comment: The effluent flow meter appeared to not be working. At the bottom of the display screen it showed a code RS485 timed out. A picture of this is attached to the back of the inspection report. The flow meter had a sticker that listed Albemarle Environmental as the company that completed a calibration on 5-16-2020. Standby Power Is automatically activated standby power available? Is generator tested weekly by interrupting primary power source? Is generator operable? Does generator have adequate fuel? Comment: the ORC stated that the generator wasn't currently working. Treatment Barscreen Is it free of excessive debris? Is disposal of screenings in compliance? Are the bars spaced properly? Is the unit in good condition? Comment: Treatment Activated Sludge Is the aeration mechanism operable? Is the aeration basin thoroughly mixed? Is the aeration equipment easily accessed? Is Dissolved Oxygen adequate? Are Settleometer results acceptable? Is activated sludge an acceptable color? Comment: The wastewater in the aeration basin looked septic the day of inspcetion. Treatment Clarifiers Are the weirs level? Are the weirs free of solids and algae? Is the scum removal system operational? Is the scum removal system accessible? Is the sludge blanket at an acceptable level? Is the effluent from the clarifier free of excessive solids? Yes No NA NE ▪ ❑ ❑ ❑ ❑ ❑ ❑• ❑•❑ ❑ O 00MI Yes No NA NE ▪ ❑ ❑ ❑ ❑ ❑ ❑• • ❑ ❑ ❑ • ❑ ❑ ❑ Yes No NA NE II ❑ ❑ ❑ • ❑ ❑ ❑ ❑ U ❑ ❑ ❑ ❑ ❑ U ❑ ❑❑■ ❑•❑ ❑ Yes No NA NE ❑ ❑ ❑• • ❑ ❑ ❑ O 1100 ❑■❑❑ ❑ ❑ ❑• ❑ ❑❑■ Comment: Both clarifiers were observed druinq the inspection and not working. Pictures are attached at the end of the inspection report. Treatment Filters Is the filter media present? Yes No NA NE ❑ ❑ ❑• Page 5 of 8 680 ayl ulyl!M spats Aiddns /ue ei e,paulelulew siaj nq eiv # Is the application High Rate or Low Rate? uo!;eJ;lIJul-esn pu3 .uo!;oajuis!p 0 0 3 3 0 ✓ oe: ay; }e pasn sl auuolgO pin goealq asnoH 0 0 1 Joj goealq sap!noJ If yes, then when was the RMP last updated? If yes, then what is the EPA twelve digit ID Number? (1000- - ) If yes, then is there a Risk Management Plan on site? Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)? i.,walsiSs peal lenp ell sl # f UV, is the UV intensity adequate? f UV, are extra UV bulbs available? s contact chamber free of sludge, solids, and growth? Are the tablets the proper size and type? f tablets, are tablets present? s the chlorinator accessible? s the fan in the chlorine feed room and storage area operable? f gas, does the cylinder storage appear safe? s the system properly maintained? s there adequate detention time (>=30 minutes)? Do the fecal coliform results indicate proper disinfection? 66uwoM walsi(s ay; s ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ■ ■ ■ ■ O 00000000000000 • ❑ ❑ ••❑ ❑ ❑ ❑ uo!;oajulsla ;uaua;ea!1 coo N z O z z m 0 0 3 3 CD pnls penowaJ ;,useq 0 0 Q ou ueo OHO a 3 co 3 0 (D 1 If required, are Sanitary "Ts" present in tankage? Is the aeration pattern even? CD ❑❑■ Pl ❑ ❑ ❑ DDD N • • ❑ pnls ;uaua;eaul Comment: The ORC stated that the travel! 0 0 0 Does backwashing frequency appear adequate? he mud well free of excessive solids and filter media? he clear well free of excessive solids? 4,algeldaooe 6uunoos ay Cleuolleaado Jnoos Jle ay he filter media the correct size and type? N 000000 ❑ ❑ ❑ ■ ■ ❑ 000000 ❑ ❑ u OZOZ/8 L/Z!. :eled uo!;oadsul Inspection Type : Compliance Evaluation aullnoei :3!s!n Jo; uoseaa b8ZZ00OOM :;1WJed Owner - Facility:Outer Banks/Kinnakeet Associates LLC s the application equipment acceptable? s the acreage in the permit being utilized? s the site free of ponding/runoff? ,atenbape siajjnq eiy s the cover crop acceptable'? f golf course, is a sign posted in plain sight on the club house? s public access restricted from irrigation area during active site use? s upset wastewater treated prior to discharge to irrigation storage? v • v c c CD CD Q 03 N Cn CD CD n) 0 CO 0) (D CD N (0 a CD m m 3 Fri a c O rn • O -0 El;0(0 U)) (0 (D 7 O. O 0) 0 n (D 0▪ ) s all flow diverted at the appropriate times? Does the turbidity meter have recording capabilities? Has the turbidity meter been calibrated in the last 12 months? Is aerated flow equalization present? Is the equalization capacity adequate? Is an automatically activated standby power source available? Are all essential units provided in duplicate? Does the acreage specified in the permit correspond to the measured acreage at the site? Is the acreage in the permit being utilized? ❑ ❑ ■ ■ ■ ❑ ■ ❑ ❑ ❑ ❑ ❑ ■ ■ ■ ❑ ❑ ❑ ❑ N ■ ■ ❑ ❑ ❑ ❑ ❑ ■ ■ ■ ■ . ❑ ❑ ❑ ■ ■ ❑ ■ fD ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ O ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ■ ❑ asnaa-esn pu3 eoxa uogeie O 1 O No chemicals or rototiller used to eliminate vegetation, solids, algae, etc.? Do any surface water features appear to be adversely impacted by GW discharge? Are the disposal sites free of vegetation? Do the records show that the fields are properly maintained? Are the disposal sites free of solids, algae, etc.? s the disposal site free of breakout? s the disposal site free of ponding? s the distribution equipment acceptable? ,algetdaooe ails iesodslp ayt s s a usable green area maintained? Are GW monitoring wells properly constructed, including screened interval? Are GW monitoring wells located properly w/ respect to RB and CB? Are GW monitoring wells required? Is municipal water available in the area? Are any supply wells within 250' of the CB? M ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ■ . ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ■ ❑ ❑ ■ ■ ❑ ❑ ■ ■ ❑ ■ ■ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ m ❑ ❑ ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ OZOZ/8I./ZI. :ales uo!loadsul Inspection Type : Compliance Evaluation augnoei :l!s!n Jo; uoseaa 48ZZ000OM :l!wJed Owner - Facility:Outer Banks/Kinnakeet Associates LLC Permit: WQ0002284 Owner - Facility:Outer Banks/Kinnakeet Associates LLC Inspection Date: 12/18/2020 Inspection Type : Compliance Evaluation Reason for Visit: Routine Is the application area free of limiting slopes? How close is the closest water supply well? Are any supply wells within the CB? Are any supply wells within 250' of the CB? Is municipal water available in the area? Are GW monitoring wells required? Are GW monitoring wells located properly w/ respect to RB and CB? Are GW monitoring wells properly constructed, including screened interval? ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ • ❑ ❑ ❑ ❑• ▪ ❑ ❑ ❑ ❑•❑ ❑ ❑•❑ ❑ ❑•❑ ❑ Comment: The spray irrigation equipment does not work. Operator has more issues to resolve than the irrigation system. All wastewater goes to the infiltration pond. Last two visits, the turbidity meter has been malfunctioning. Do not know if wastewater is diverted when ww does not meet reclaimed standards. Page 8 of 8