HomeMy WebLinkAboutNC0023736_Compliance Evaluation Inspection_20180614 United States Environmental Protection Agency
Form Approved.
EPA Washington,D.C.20460 OMB No.2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A: National Data System Coding(i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 15 I 3 I NC0023736 111 12 I 18/06/14 I17 18 L Q j 19 L G j 201
211111 1 1 I I I I II I I I I I I I I I I I I 1 I I I I I I I I I I II I I I I I f6
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 CA ----------------------Reserved-------------------
671 70 IJ 71 [ ] 72 LIJ
N I 73 L_LJ74 751
I I I I I I I80
Section B: Facility Data
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES oermit Number) 09:OOAM 18/06/14 14/07/01
Gunpowder Creek WWTP
450 Pine Mtn Rd Exit Time/Date Permit Expiration Date
Hudson NC 28638 10:OOAM 18/06/14 19/03/31
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
Ronnie E H end rix/ORC/828-757-21 98/
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
Monte L Wall,PO Box 958 Lenoir NC 2 8 64 50 9 58//8 28-757-2 1 98/
No
Section C:Areas Evaluated During Inspection(Check only those areas evaluated)
Effluent/Receiving Waters
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Timothy H Heim DocuSigned by: ARO WQ//828-296-4665/
lwtb fkUwt 8/20/2018
082B1105A3CA418...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3(Rev 9-94)Previous editions are obsolete.
Page# 1
NPDES yr/mo/day Inspection Type (Cont.) 1
31 NCO023736 111 121 18/06/14 117 18 JBI
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
Tim Heim of the Asheville Regional Office performed a Bioassay Compliance Inspection on June 12 &
June 14th, 2018. Matthew Mackie (City of Lenoir Lab Analyst)was present at the time of the inspection
and assisted with the sampling. Composite effluent samples were collected for use in a chronic
ceriodaphnia dubia pass-fail toxicity test. The toxicity tests performed by both the Division's Aquatic
Toxicity Branch and ETT Environmental resulted in a pass.
Toxicity test information follows:
Test Type: 3-Brood Ceriodaphnia dubia chronic pass-fail
Test Result: Pass
Test Concentrations: 52%
Control Survival: 81.8%
Control Mean Reproduction: 16.7 neonates
Test Treatment Survival: 91.7%
Treatment Mean Reproduction: 22.7 neonates
First Sample pH: 6.57 SU
First Sample Conductivity: 249 micromhos/cm
First Sample Total Residual Chlorine: <0.1 mg/L
Second Sample pH: 6.56 SU
Second Sample Conductivity: 234 micromhos/cm
Second Sample Total Residual Chlorine: <0.1 mg/L
Page# 2
Permit: NC0023736 Owner-Facility: Gunpowder Creek WWTP
Inspection Date: 06/14/2018 Inspection Type: Bioassay Compliance
Yes No NA NE