HomeMy WebLinkAbout20120432 Ver 1_Staff Comments_20120524Leucas, Annette From Lucas Annette Sent Thursday May 24 2012 3 21 PM To Witherspoon Lauren Cc Lucas Annette Subject 12 X412 SGWSA WWTP Imprnvement,, Attachments 12 0432 SGWSA WWTP Improvements docx Lauren A hold bullet is attached It looks like they need a stormwater plan Thanks Annette Annette M Lucas PE Environmental Engineer NCDENR I DWQ I Wetlands and Stormwater Branch 1650 Mail Service Center Raleigh NC 27699 1650 (Mail) 512 N Salisbury St Raleigh NC 27604 1 9u' Floor (Location & Parcels) Phone (919) 807 6381 1 Fax (919) 807 6494 1 Email Annette Lucas6�),ncdenr gov Website http / /portal ncdenrorg/web/wq/swp/ws/401 A Before printing this email please consider your budget and the environment E mail correspondence to and from this address may be subject to the North Carolina Public Records Law and may be disclosed to third parties 12 0432 SGWSA WWTP Improvements AML comments May 24 2012 1 It appears that this site may be over 24% impervious and that a piped storm drainage system has been used Please either a Provide evidence showing that this protect meets all of the requirements for low density development found in Appendix A of General Condition 3890 available at http //portal ncdenr org/c /document librar /get file'?uuid= 9e7c74e6 1036 44dd b70f 8e93e7ef6fbe &groupId =38364 b Provide a Stormwater Management Plan that removes a minimum of 85 percent TSS and 30 percent TN and TP from the stormwater generated by this project For each proposed BMP please provide a completed BMP Supplement Form with all the required items The BMP Supplement Forms are available at the following web site http //portal ncdenr org/web/wq/ws/su/bmp manual