Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN i 2 IS I 3 I NCO021181 I11 121 21/02/08 I17 18 i,. i 19 i G i 201
211111111111III11IIIIIII111111III IIIIIIIIIII f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 CA ---------------------- Reserved -------------------
67
72 i n, i 73 LLI74 71
1.0 70 Lis J i 71 1ty, L
J 1 1 1 1 L L j80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
11:00AM 21/02/08
19/12/01
Belmont WWTP
298 Parkdale Rd
Exit Time/Date
Permit Expiration Date
Belmont NC 28012
12:15PM 21/02/08
24/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Tanya S Carter/ORC/704-825-3791/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Adrian T Miller,PO Box 431 Belmont NC 280120431/City Manager/704-825-5586/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispos Facility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ori ATuvia DWR/MRO WQ/704-663-1699/
Pocusigned by:Date
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Nu 7�F161FB69A2DMA3
Andrew Pitner DWR/MRO WQ/704-663-1699 Ext.2180/ 2.11.21
...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
31 NCO021181 I11 12I 21/02/08 117 18IC
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO021181 Owner - Facility: Belmont WWTP
Inspection Date: 02/08/2021 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The subject permit expires on 6/30/2024. The City implements an approved industrial
pretreatment program.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operatc
on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility classification'
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
■
❑
1111
❑
❑
❑
■
❑
❑
❑
■
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
❑
❑
■
❑
■
❑
❑
❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ❑ ■
■ ❑ ❑ ❑
Comment: The records reviewed during the inspection were organized and well maintained. DMRs,
COC, ORC logs and process control data were reviewed for October 2020. At the time of
the inspection the inspector instructed the ORC to log the time the ORC/BORC arrives and
leaves the WWTP.
Page# 3
Permit: NCO021181
Inspection Date: 02/08/2021
Owner - Facility: Belmont VVVVTP
Inspection Type: Compliance Evaluation
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Yes
No
NA
NE
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
❑
❑
■
❑
❑
❑
■
❑
Comment: Influent and effluent analyses (includinq field) are performed by Shealy
Environmental
Services, Inc. (Certification #329). ETT Environmental, Inc. (toxicity) has also been
contracted to provide analytical support.
Influent Sampling
Yes
No
NA
NE
# Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected above side streams?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Is sampling performed according to the permit?
0
❑
❑
❑
Comment: The subject permit requires composite BOD and TSS influent samples. Facility staff
conducts bi-monthly aliquot verifications.
Effluent Sampling
Yes
No
NA
NE
Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment: The subject permit requires composite and grab effluent samples.
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, an( 0 ❑ ❑ ❑
sampling location)?
Page# 4
Permit: NCO021181 Owner - Facility: Belmont WWTP
Inspection Date: 02/08/2021 Inspection Type: Compliance Evaluation
Upstream / Downstream Sampling Yes No NA NE
Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: Overall the facility appeared to be properly operated and well maintained. Maintenance is
needed to clear woody vegetation in the solids holding tank, and the secondary clarifier that
has excessive algae buildup. The ORC and staff incorporate a comprehensive process
control program with all measurements being properly documented and maintained on -site.
Bar Screens
Yes
No
NA
NE
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment:
Grit Removal
Yes
No
NA
NE
Type of grit removal
a.Manual
❑
b.Mechanical
Is the grit free of excessive organic matter?
❑
❑
❑
Is the grit free of excessive odor?
❑
❑
❑
# Is disposal of grit in compliance?
❑
❑
❑
Comment: System was out for repairs at the time of the inspection. Screenings and grit are disposed
at the County Landfill.
Flow Measurement - Influent
Yes
No
NA
NE
# Is flow meter used for reporting?
❑
0
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
Page# 5
Permit: NCO021181 Owner - Facility: Belmont WWTP
Inspection Date: 02/08/2021 Inspection Type: Compliance Evaluation
Flow Measurement - Influent Yes No NA NE
(If units are separated) Does the chart recorder match the flow meter? 0 ❑ ❑ ❑
Comment:
Aeration Basins
Yes
No
NA
NE
Mode of operation
Ext. Air
Type of aeration system
Surface
Is the basin free of dead spots?
0
❑
❑
❑
Are surface aerators and mixers operational?
0
❑
❑
❑
Are the diffusers operational?
❑
❑
0
❑
Is the foam the proper color for the treatment process?
0
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
0
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/I)
❑
❑
❑
Comment: The facility is equipped with two aeration basins (inactive aertion basin has been out of
service for more then 10 years and would require maintenance); however, only one aeration
basin is used due to low influent flows. Sodium hydroxide is added to the influent prior to the
aeration basin to maintain appropriate alkalinity/pH levels
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Comment: Both secondaries were operational and in service.
Pumps-RAS-WAS
Are pumps in place?
Yes No NA NE
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
Yes No NA NE
■ ❑ ❑ ❑
Page# 6
Permit: NCO021181
Inspection Date: 02/08/2021
Pumps-RAS-WAS
Are pumps operational?
Are there adequate spare parts and supplies on site?
Comment:
Disinfection -Gas
Are cylinders secured adequately?
Are cylinders protected from direct sunlight?
Is there adequate reserve supply of disinfectant?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Owner - Facility: Belmont VVVVTP
Inspection Type: Compliance Evaluation
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1000- - )
If yes, then when was the RMP last updated?
Comment: The chlorination and dechlorination systems are serviced annually
De -chlorination
Type of system ?
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Yes
No
NA
NE
■
❑
❑
❑
■
❑
❑
❑
Yes
No
NA
NE
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
Yes No NA NE
Gas
❑ ❑ ❑ ■
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
Yes No NA NE
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ■ ❑
Page# 7
Permit: NC0021181
Inspection Date: 02/08/2021
Flow Measurement - Effluent
Comment: Flow meter is calibrated quarterly
Owner - Facility: Belmont VVVVTP
Inspection Type: Compliance Evaluation
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Comment:
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Comment: Standby generator is tested weekly.
Yes No NA NE
Yes
No
NA
NE
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
Yes
No
NA
NE
❑
❑
❑
Yes
No
NA
NE
❑
❑
❑
❑
❑
❑
■
❑
❑
❑
❑
❑
110
■
❑
❑
❑
❑
❑
❑
❑
❑
❑