Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 1 3 I NCO032867 I11 121 21/01/19 I17 18 I,- I 19 I G I 201
21111111111111111111111111111111111111111111 f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating 131 CA ---------------------- Reserved -------------------
67
72 I n, I 73LLI74 71
1.0 701LJ � I 711 ty, L
J 1 1 1 1 L L j80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
11:30AM 21/01/19
18/09/01
Kings Mountain Travel Plaza
400 Dixon School Rd
Exit Time/Date
Permit Expiration Date
Kings Mountain NC 28086
12:30PM 21/01/19
23/08/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Daniel James Dougherty/ORC/704-477-5514/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Dan Dougherty, /ORC/704-477-5514/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispos Facility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
Ori ATuvia DWR/MRO WQ/704-663-1699/ 1/27/2021
CF- Qr7A-)nr:n17AQA
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger DWR/Division of Water Quality/704-235-2194/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
DocuSigned by:
_ 1/27/2021
n�accsa�nFz�azs... Page#
NPDES yr/mo/day Inspection Type (Cont.)
31 NCO032867 I11 12I 21/01/19 117 18 ICI
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
New permit effective June 22, 2018 lists the following treatment components: Two septic tanks with
piping and valves, two aeration basins each equipped with two positive displacement blowers, an
aerobic digester, a holding tank, and One flow measuring system comprised of a 22-1/2-degree
V-notch weir and Flow Meter with totalizer and chart recorder. At the time of the inspection: Two septic
tanks were non -operational, leaking, not piped, nor valved. The two septic tanks must be properly
sealed to avoid leaching wastewater to the ground, and piped so they can be used as indicated in the
permit. The facility has two (2) permitted aeration basins: Only one of the aeration basins was
operational, the second basin had no blowers and was used as a storage tank to store sludge.
Additionally, the aeration basin grating was insufficient, floor grating should be properly installed to
ensure the safety of the ORC/operators and DWR staff. The ORC indicated that the aerobic digester
and a holding tank may be leaking. The tanks should be tested for leaking and if found to be leaking
they should be fixed and properly maintained. At the time of the inspection the flow meter was not
operational. flow meter censor was underwater. Properly operating flow meter is needed to determine
the discharge from the treatment plant. All issues were listed during the previous inspection on January
28, 2020, that resulted in NOV-2020-PC-0073, and are ongoing.
Page#
Permit: NCO032867 Owner - Facility:
Inspection Date: 01/19/2021 Inspection Type:
Kings Mountain Travel Plaza
Compliance Evaluation
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑
❑
0
❑
application?
Is the facility as described in the permit?
❑
0
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: See Summary.
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operatc
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification'
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
0
❑
Comment: Records reviewed for September 2020 - December 2020 were complete and well
maintained. As was discussed in a previous meeting, it is the responsibility of the permitee,
not the ORC, to maintain all permit related documents.
Effluent Sampling
Yes No NA NE
Page# 3
Permit: NCO032867 Owner - Facility: Kings Mountain Travel Plaza
Inspection Date: 01/19/2021 Inspection Type: Compliance Evaluation
Effluent Sam piinq
Yes
No
NA
NE
Is composite sampling flow proportional?
❑
❑
0
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
❑
❑
0
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment: The subject permit requires effluent grab samplin
Laboratory
Yes
No
NA
NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
0
❑
Comment: Water Tech Labs has been contracted to perform lab sampling.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ❑ 0 ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The facility must have all treatment units listed in the permit maintained and operational.
Septic Tank
(If pumps are used) Is an audible and visual alarm operational?
Is septic tank pumped on a schedule?
Are pumps or syphons operating properly?
Are high and low water alarms operating properly?
Comment: Two septic tanks were non -operational, leaking, not piped, nor valved.
Aeration Basins
Mode of operation
Yes No NA NE
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ■ ❑ ❑
❑ ❑ ■ ❑
Yes No NA NE
Ext. Air
Page# 4
Permit: NCO032867
Inspection Date: 01/19/2021
Aeration Basins
Type of aeration system
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/I)
Owner - Facility: Kings Mountain Travel Plaza
Inspection Type: Compliance Evaluation
Yes No NA NE
Fixed
■ ❑ ❑ ❑
❑ ■ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
Comment: Only one of the two permitted aeration basins was operational. The second aeration basin is
used for storing sludge, and has no operational blowers (two permitted). At the time of the
inspection one of the two blowers used in the first basin was out of service.
Disinfection -Tablet
Yes
No
NA
NE
Are tablet chlorinators operational?
0
❑
❑
❑
Are the tablets the proper size and type?
0
❑
❑
❑
Number of tubes in use?
2
Is the level of chlorine residual acceptable?
0
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
0
❑
❑
❑
Comment:
De -chlorination
Yes
No
NA
NE
Type of system ?
Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
0
❑
❑
❑
Is storage appropriate for cylinders?
0
❑
❑
❑
# Is de -chlorination substance stored away from chlorine containers?
0
❑
❑
❑
Comment:
Are the tablets the proper size and type? 0 ❑ ❑ ❑
Are tablet de -chlorinators operational? 0 ❑ ❑ ❑
Number of tubes in use? 2
Comment:
Flow Measurement - Effluent Yes No NA NE
Page# 5
Permit: NCO032867 Owner - Facility:
Inspection Date: 01/19/2021 Inspection Type:
Kings Mountain Travel Plaza
Compliance Evaluation
Flow Measurement - Effluent
Yes
No
NA
NE
# Is flow meter used for reporting?
❑
0
❑
❑
Is flow meter calibrated annually?
❑
0
❑
❑
Is the flow meter operational?
❑
0
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
0
❑
❑
Comment: At the time of the inspection the flow meter was not operational. Flow meter censor was
underwater and not operational. In addition, the flow meter chart recorder was not
operational (as indicated in previous inspection), the flow meter has not been in operation
since the previous inspection on January 28, 2020, that resulted in NOV-2020-PC-0073.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Yes No NA NE
❑ ❑ ❑ ■
❑ ❑ ❑ ■
❑ ❑ ❑ ■
Yes No NA NE
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
Comment: Facility staff indicated that power outlets do not work properly and light is needed for night
operation
Solids Handling Equipment
Is the equipment operational?
Is the chemical feed equipment operational?
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
Yes No NA NE
❑ ■ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ❑ ■
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
Page# 6
Permit: NC0032867
Inspection Date: 01/19/2021
Solids Handling Equipment
Owner - Facility: Kings Mountain Travel Plaza
Inspection Type: Compliance Evaluation
Yes No NA NE
Comment: Sludge holding tanks were not being used at the time of the inspection. Facility staff
indicated that additional study of the sludge holding tank is needed as it may be leaking.
Page#