HomeMy WebLinkAboutNCG030055_DMR_20200723 Stormwater Discharge Monitoring Report
for North Carolina Division of Energy, Mineral and Land Resources General Permit No. NCG030000
Date submitted 07/23/2020
CERTIFICATE OF COVERAGE NO. NCGO3 0 0 5 5 SAMPLE COLLECTION YEAR 2020
FACILITY NAME Mentor Heavy Vehicle Systems LLc SAMPLE PERIOD 0 Jan-June 0 July-Dec
COUNTY Henderson or ❑Monthly1 (month)
PERSON COLLECTING SAMPLES Claude Laughter/Jack Anders PPS r-(� DISCHARGING TO CLASS DORW ❑HQW ❑■Trout ❑PNA
LABORATORY Pace Analytical,Asheville NC Lab Cert.# 92481731001 PD ❑Zero-flow ❑Water Supply ESA
Comments on sample collection or analysis: AUG 4 4 2020 Other
CAN/ i -*
PLEASE REMEMBER TO SIGN ON PAGES 2 AND/OR 3
Ot'" 0ECr(i. r ja
pr
Part A:Stormwater Benchmarks and Monitoring Results
No discharge this period?2
Date Sample 24-hour rainfall pH, Non-Polar O&G/ Total Toxic
Outfall No. Collected) amount, Total Suspended Solids Standard units Total Copper Total Lead Total Zinc Total Petroleum Organicss
(mo/dd/yr) Inches; Hydrocarbons
Benchmarks - - 100 mg/L or 50 mg/L` 6.0—9.0 0.010 mg/L 0.075 mg/L 0.126 mg/L 15 mg/L 1 mg/L
Parameter Code - 46529 C0530 00400 01119 01051 01094 00552 78141
Outfall 1,pond flume 06/10/2020 .29 <2.5 6.3 .0103 < .005 .0138 <5.0 < .0005
Outfall 2,North ditch 06/10/2020 .29 52.5 7.1 < .005 <.005 .0142 <5.0 <.0005
1 Monthly sampling(instead of semi-annual)must begin with the second consecutive benchmark exceedance for the same parameter at the same outfall.
2 For sampling periods with no discharge at any single outfall,you must still submit this discharge monitoring report with a checkmark here.
;The total precipitation must be recorded using data from an on-site rain gauge. Unattended sites may be eligible for a waiver of the rain gauge requirement.
°See General Permit,Section B,Table 1 to identify the especially sensitive receiving water classifications where the more protective benchmark applies.
5 Total Toxic Organics sampling is applicable only for those facilities which perform metal finishing operations, manufacture semiconductors,manufacture
electronic crystals,or manufacture cathode ray tubes. For purposes of this permit the definition of Total Toxic Organics is that definition contained in the EPA
Effluent Guidelines for the facility subject to the requirement to sample(for metal finishing use the definition as found in 40 CFR 433.11;for semiconductor
manufacture use the definition as found in 40 CFR 469.12;for electronic crystal manufacture use the definition as found in 40 CFR 469.22;and for cathode ray
tube manufacture use the definition found in 40 CFR 469.31).
Permit Date:11/1/2018-05/31/2021 SWU-245,last revised 11/1/2018
Page 1 of 3
Facilities that incorporate a solvent management plan into the Stormwater Pollution Prevention Plan may so certify, and the requirement for TTO monitoring
may be waived. The solvent management plan shall include a list of the total toxic organic compounds used and the other elements listed in the General
Permit. For those facilities electing to employ the TTO monitoring waiver,the discharger shall sign the following certification statement:
"Based upon my inquiry of the person or persons directly responsible for managing compliance with the permit monitoring requirement for total toxic organics
(TTO),I certify that to the best of my knowledge and belief,no dumping of concentrated toxic organics into the stormwater or areas which are exposed to rainfall or
stormwater runoff has occurred since filing the last discharge monitoring report. I further certify that this facility is implementing the all the provisions of the
solvent management plan included in the Stormwater Pollution Prevention Plan."
Claude F. Laughter
Name(Print name)
Maint. planner
Title rint title)
ig ur Da e
Note: Results must be reported in numerical format. Do not report Below Detection Limit, BDL,<PQL, Non-detect, ND,or other similar non-numerical
format. When results are below the applicable limits,they must be reported in the format,"<XX mg/L",where XX is the numerical value of the detection
limit, reporting limit,etc. in mg/L.
Note: If you report a sample value in excess of the benchmark,you must implement Tier 1, Tier 2,or Tier 3 responses. See General Permit text.
Part B: Vehicle Maintenance Area Monitoring Results:only for facilities averaging> 55 gal of new oil per month.
❑ No discharge this period?2
Outfall No. Date Sample Collected) 24-hour rainfall amount, New Motor Oil or Non-Polar O&G/Total Total Suspended
(mo/dd/yr) Inches3 Hydraulic Oil Usage Petroleum Hydrocarbons Solids
Benchmarks - - - 15 mg/L 100 mg/L or 50 mg/L4
Parameter Code - 46529 NCOIL 00552 CO530
Footnotes from Part A also apply to Part B
Note: If you report a sample value in excess of the benchmark,you must implement Tier 1, Tier 2,or Tier 3 responses. See General Permit text.
Permit Date: 11/1/2018-05/31/2021 SWU-245,last revised 11/1/2018