SUBJECT: Compliance Inspection Report
Beau Rivage Plantation WWTP
NPDES WW Permit No. NCO065480
New Hanover County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Beau Rivage Plantation
WWTP on 1/28/2021. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in NPDES WW Permit No. NC0065480. The
findings and comments noted during this inspection are provided in the enclosed copy of the inspection
report entitled "Compliance Inspection Report". There were no significant issues or findings noted during the
inspection and therefore, a response to this inspection report is not required.
If you should have any questions, please do not hesitate to contact Helen Perez with the Water
Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
helen.perez@ncdenr.gov.
Sincerely,
DocuSigned by:
OA, for
7F141E73B6F3456...
Morelia Sanchez -King, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: Upload to Laserfiche
�North Carolina Department of Environmental Quality I Division of Water Resouroes
Wanungton Regonal Dfhoe 1127 Cardinal Dn►le Extension 14hk"gton, North Caroina 28405
9079B-7215
DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 IS I 3 I NC0065480 I11 121 21/01/28 I17 18 I,- I 19 I G I 201
21111111111111111111111111111111111111111111 f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 CA ---------------------- Reserved -------------------
67
72 I n, I 73LLI74 71 I I I I I I I80
701LJ � I 71 IN tyI L
J
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
01:OOPM 21/01/28
19/10/01
Beau Rivage Plantation WWTP
6606 River Rd
Exit Time/Date
Permit Expiration Date
Wilmington NC 28412
02:OOPM 21/01/28
22/08/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Gregory Cole Price/ORC/910-408-6413/
Joel A Mingus//910-270-1412 /
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Eric N Youngs,105 Hampstead Village Hampstead NC
28443/ORC/910-270-1412/9102703147 Yes
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispos Facility Site Review Effluent/Receiving Wate
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Helen I Perez oE o^ s'g"eYDWR/WIRO WQ/910-796-7387/ 2/3/2021
i^ex
1 D645B4A39694BE...
Signature of Man ?fi'�!9Aefk'Wiewer Agency/Office/Phone and Fax Numbers Date
Tom Tharring on °n" -TtN"i"3hWR/WIRO WQ/ - - / 2/3/2021
7F141E73B6F3456...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668
NPDES yr/mo/day Inspection Type (Cont.)
31 NCO065480 I11 12I 21/01/28 117 18 ICI
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
A routine compliance inspection of the Beau Rivage WWTP was conducted on January 28, 2021. The
purpose of the evaluation was to verify that the facility is operating in compliance with the conditions
and limitations specified in Permit NC0065480. Joel Mingus, Gregory Price and Eric Young were
present during the inspection.
This facility was upgraded to a 0.2 MGD dual -train Integrated Fixed -Film Activated Sludge treatment
plant in 2018. Flow averages 123,000 GPD. The plant appears to be well maintained and operated.
Extra high level alarms were added to the EQ tanks, the aeration tanks and the digesters for notification
through telemetry. Treated wastewater is discharged through an 80-100 foot pipe outfall, located
underwater, into the Cape Fear River.
Since start-up in 2018, there have been NOVs issued for daily and monthly Ammonia and BOD
exceedances and daily Enterococci exceedances. The last violation was issued in February 2020 for
daily and monthly ammonia exceedances.
The facility is compliant with NPDES permit NC0065480. Please review the comment sections of the
inspection report for more details.
Page#
DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668
Permit: NCO065480 Owner - Facility:
Inspection Date: 01/28/2021 Inspection Type:
Beau Rivage Plantation WVVTP
Compliance Evaluation
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
❑
0
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The sodium hydroxide chemical feed system is currently not beinq used.
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operatc
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification'
❑
❑
❑
Is a copy of the current NPDES permit available on site?
0
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
0
❑
Comment: Records of DMRs, lab results and COCs were organized and complete with no issues.
Bench sheets and calibrations of field parameter testinq performed by operators
were
complete.
Operations & Maintenance
Yes No NA NE
Page# 3
DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668
Permit: NCO065480 Owner - Facility: Beau Rivage Plantation WVVTP
Inspection Date: 01/28/2021 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: DO and ph measurements are taken throughout the treatment process.
Bar Screens Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment: The headworks consists of a Huber mechanical fine screen and grit removal system
installed in the 2018 modification. Once a month, grease is pumped out and the system is
cleaned. The existinq manual bar screen was repurposed as a secondary system.
Grit Removal
Type of grit removal
Yes No NA NE
a.Manual
❑
b.Mechanical
Is the grit free of excessive organic matter?
0
❑
❑
❑
Is the grit free of excessive odor?
0
❑
❑
❑
# Is disposal of grit in compliance?
0
❑
❑
❑
Comment: Grit, along with screenings, are conveyed to a roll -out dumpster
for removal.
Equalization Basins
Yes
No
NA
NE
Is the basin aerated?
0
❑
❑
❑
Is the basin free of bypass lines or structures to the natural environment?
0
❑
❑
❑
Is the basin free of excessive grease?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Are audible and visual alarms operable?
0
❑
❑
❑
Page# 4
DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668
Permit: NCO065480
Inspection Date: 01/28/2021
Equalization Basins
# Is basin size/volume adequate?
Owner - Facility: Beau Rivage Plantation WVVTP
Inspection Type: Compliance Evaluation
Yes No NA NE
■ ❑ ❑ ❑
Comment: One of the 35,000 gallon EQ chambers was a repurposed existing
sludge holding
tank.
There are two high-level EQ float alarms which were tested and operable
during inspection.
Operators were notified of alarms by phone.
Aeration Basins
Yes No
NA
NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
0 ❑
❑
❑
Are surface aerators and mixers operational?
❑ ❑
0
❑
Are the diffusers operational?
0 ❑
❑
❑
Is the foam the proper color for the treatment process?
0 ❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0 ❑
❑
❑
Is the DO level acceptable?
❑ ❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/I)
❑ ❑
❑
Comment: There are two 100,000 gal Integrated Fixed -Film Activated Sludge trains, each with a 25,000
gal aerated digester. Each train has three cells filled —30% with honeycomb shaped plastic
media. Wastewater passes throuqh media retention screens between each cell. There are
scare screens on -site.
Pumps-RAS-WAS
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
Comment: No comment.
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Yes
No
NA
NE
■
❑
❑
❑
❑
❑
❑
■
❑
❑
❑
■
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ❑ ■
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 5
DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668
Permit: NCO065480
Inspection Date: 01/28/2021
Secondary Clarifier
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Owner - Facility: Beau Rivage Plantation WVVTP
Inspection Type: Compliance Evaluation
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Comment: The weirs on the dual clarifiers are manually cleaned weekly.
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Yes
No
NA
NE
■
❑
❑
❑
■
❑
❑
❑
❑
❑
❑
■
Yes
No
NA
NE
■
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
■
❑
❑
❑
Comment: Each train has a 25,000 gallon digester. The digesters were in the process of decanting into
the EQ basin during the inspection.
Filtration (High Rate Tertiary)
Yes
No
NA
NE
Type of operation:
Down
flow
Is the filter media present?
❑
❑
❑
Is the filter surface free of clogging?
❑
❑
❑
Is the filter free of growth?
❑
❑
❑
Is the air scour operational?
❑
❑
❑
Is the scouring acceptable?
❑
❑
❑
Is the clear well free of excessive solids and filter media?
0
❑
❑
❑
Comment: The dual Fluidyne cloth media filters are backwashed automatically 10 to 15 times a day.
The filters are cleaned with liquid chlorine every
2 to 3 weeks. Extra cloth media is stored
on -site.
Disinfection - UV
Are extra UV bulbs available on site?
Are UV bulbs clean?
Is UV intensity adequate?
Is transmittance at or above designed level?
Is there a backup system on site?
Is effluent clear and free of solids?
Yes No NA NE
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ ■
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Page# 6
DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668
Permit: NCO065480 Owner - Facility: Beau Rivage Plantation WVVTP
Inspection Date: 01/28/2021 Inspection Type: Compliance Evaluation
Disinfection - UV Yes No NA NE
Comment: The dual UV units are in series. The units are cleaned once a month and Aqua has plans to
replace all UV bulbs in February. The facility has a back-up chlorination/dechlorination
system.
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
MOM ill r•7ill rim ill I:I
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
Comment: The flowmeter was calibrated on 1-23-2020 by Horizon Enqineerinq and Consulti
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ❑ ■
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Comment: The effluent sampler is located at the post aeration well and the temperature was 3 degrees
Celsius.
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
MOM ill r•7ill rim ill I:I
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ❑ ■
■ ❑ ❑ ❑
❑ ❑ ❑ ■
❑ ❑ ❑ ■
Comment: The generator is automatically tested weekly and underload 2 times a year. Major
preventative maintenance is performed annually.
Page# 7