SUBJECT: Compliance Inspection Report
Castle Bay WWTP
Non -discharge Permit No. WQ0018755
Pender County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Castle Bay WWTP on
1/19/2021. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in Non -discharge Permit No. WQ0018755. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled "Compliance Inspection Report". There were no significant issues or findings noted during the
inspection and therefore, a response to this inspection report is not required.
If you should have any questions, please do not hesitate to contact Helen Perez with the Water
Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
helen.perez@ncdenr.gov.
Sincerely,
DocuSigned by:
'Caµ "iln OA, for
7F141E73B6F3456...
Morelia Sanchez -King, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: Upload to Laserfiche
North Carolina Department of Environmental Quality I Division of Water Resources
Wanungton Regonal Dfhoe 1127 Cardinal Dn►le Extension 14hk"gton, North Caroina 28405
�- `•- ^^--� 90796-7215
DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668
Compliance Inspection Report
Permit: WO0018755 Effective: 12/30/19 Expiration: 10/31/25 Owner : Aqua North Carolina Inc
SOC: Effective: Expiration: Facility: Castle Bay WWTP
County: Pender Castle Bay Dr
Region: Wilmington
Hampstead NC 28443
Contact Person: Joel A Mingus Title: Coastal Area Manager Phone: 910-270-1412
Directions to Facility:
System Classifications: SI, WW2,
Primary ORC: Kirklyn Bernard Fields
Secondary ORC(s):
On -Site Representative(s):
On -site representative
Related Permits:
Certification: 998855
Joel A Mingus
Phone: 910-270-1412
910-270-1412
Inspection Date: 01/19/2021 Entry Time 11:20AM Exit Time: 12:30PM
Primary Inspector: Helen I Perez Docu ig 2/3/2021 e Y: Phone: 910-796-7387
Secondary Inspector(s):
1 D645B4A39694BE...
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Reclaimed Water
Facility Status: Compliant Not Compliant
Question Areas:
Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent Miscellaneous Questions
Treatment Flow Measurement -Water Treatment Treatment Barscreen
Use Records
Treatment Filters Record Keeping Treatment Activated Sludge
Treatment Sludge Storage/Treatment Treatment Clarifiers Treatment Disinfection
Treatment Flow Measurement Treatment Return pumps End Use -Reuse
Standby Power
(See attachment summary)
Page 1 of 7
DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668
Permit: WQ0018755 Owner -Facility: Aqua North Carolina Inc
Inspection Date: 01/19/2021 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
A routine compliance inspection of the Castle Bay WWTF was conducted on January 19, 2021. The purpose of the
evaluation was to verify that the facility is operating in compliance with the conditions and limitations specified in Permit
W00018755. Joel Mingus and Kirkland Fields were present during the inspection.
Castle Bay WWTF is a 100,000 GPD extended aeration treatment plant with teriary filters that produces reclaimed quality
effluent. Disposal consists of the dedicated Castle Bay Golf Course site. Currently, the flow averages—25,000 to 35,000
GPD.
The dirt road leading to the plant is in poor condition, especially when it rains. Aqua is planning on repairing the road in the
near future.
The golf course staff maintains records tracking the amount of reclaimed water irrigated on the golf course. Currently, Aqua
does not have a system to confirm these application rates. It was discussed during the last inspection that the addition of a
flowmeter measuring the water taken from the storage pond for irrigation purposes as being a starting point for this
application confirmation. A flowmeter has been added into the 3-year capital improvement budget and Aqua is working
towards installation.
The facility is compliant with non -discharge permit W00018755. Please review the comment sections of the inspection
report for more details.
Page 2 of 7
DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668
Permit: WQ0018755 Owner - Facility:Aqua North Carolina Inc
Inspection Date: 01/19/2021 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Type
Yes No NA NE
Infiltration System
❑
Lagoon Spray, LR
❑
Single Family Spray, LR
❑
Activated Sludge Spray, HR
❑
Activated Sludge Spray, LR
❑
Recycle/Reuse
❑
Activated Sludge Drip, LR
❑
Single Family Drip
❑
Reuse (Quality)
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑
Comment: Many improvements have been made in the last several years to the WWTF that were reported
on the last insaection in February 2019.
Treatment Flow Measurement -Influent
Yes No NA NE
Is flowmeter calibrated annually?
❑
❑ ❑
Is flowmeter operating properly?
❑
❑ ❑
Does flowmeter monitor continuously?
❑
❑ ❑
Does flowmeter record flow?
❑
❑ ❑
Does flowmeter appear to monitor accurately?
❑
❑ ❑
Comment
Treatment Flow Measurement -Water Use Records Yes No NA NE
Is water use metered? ❑ 1:10 ❑
Are the daily average values properly calculated? 1111011
Comment:
Treatment Flow Measurement -Effluent Yes No NA NE
Is flowmeter calibrated annually? ❑ ❑ ❑
Is flowmeter operating properly? ❑ ❑ ❑
Does flowmeter monitor continuously? ❑ ❑ ❑
Does flowmeter record flow? ❑ ❑ ❑
Does flowmeter appear to monitor accurately? 0 ❑ ❑ ❑
Comment: The effluent flowmeter was calibrated on 10/31/2020 by Horizon Engineering and Consulting, Inc
Standby Power Yes No NA NE
Page 3 of 7
DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668
Permit: WQ0018755 Owner - Facility:Aqua North Carolina Inc
Inspection Date: 01/19/2021 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Is automatically activated standby power available? 0 ❑ ❑ ❑
Is generator tested weekly by interrupting primary power source? 0 ❑ ❑ ❑
Is generator operable? 0 ❑ ❑ ❑
Does generator have adequate fuel? ❑ ❑ ❑
Comment: The generator is automatically tested every Wednesday and major preventative maintenance is
Performed annually.
Treatment Barscreen
Yes No NA NE
Is it free of excessive debris?
❑ ❑ ❑
Is disposal of screenings in compliance?
❑ ❑ ❑
Are the bars spaced properly?
❑
❑ ❑
Is the unit in good condition?
❑ ❑ ❑
Comment: The manual barscreen is cleaned as needed
Treatment Activated Sludge
Yes No NA NE
Is the aeration mechanism operable?
❑ ❑ ❑
Is the aeration basin thoroughly mixed?
❑ ❑ ❑
Is the aeration equipment easily accessed?
❑ ❑ ❑
Is Dissolved Oxygen adequate?
❑
❑ ❑
Are Settleometer results acceptable?
❑
❑ ❑
Is activated sludge an acceptable color?
0
❑ ❑ ❑
Comment: Process control includes a settleometer test once a week and
PH and DO monitoring.
Treatment Clarifiers Yes No NA NE
Are the weirs level? ❑ ❑ ❑
Are the weirs free of solids and algae? ❑ ❑ ❑
Is the scum removal system operational? ❑ ❑ ❑
Is the scum removal system accessible? ❑ ❑ ❑
Is the sludge blanket at an acceptable level? ❑ ❑ ❑
Is the effluent from the clarifier free of excessive solids? 0 ❑ ❑ ❑
Comment: Clarifier weirs are cleaned once a week. Surface scimmers appear to be operational.
Treatment Return pumps Yes No NA NE
Are they in place? 011011
Are they operational? 011011
Comment: No comment.
Treatment Filters Yes No NA NE
Is the filter media present? ❑ ❑ ❑
Is the filter media the correct size and type? ❑ ❑ ❑
Page 4 of 7
DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668
Permit: WQ0018755 Owner - Facility:Aqua North Carolina Inc
Inspection Date: 01/19/2021 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Is the air scour operational? 0 ❑ ❑ ❑
Is the scouring acceptable? ❑ ❑ ❑
Is the clear well free of excessive solids? 0 ❑ ❑ ❑
Is the mud well free of excessive solids and filter media? 0 ❑ ❑ ❑
Does backwashing frequency appear adequate? 0 ❑ ❑ ❑
Comment: The tertiary filters beds have two floats to activate backwashing, which usually takes place 2-3
times a day.
Treatment Sludge Storage/Treatment Yes No NA NE
Is the aeration operational? ❑ ❑ ❑
Is the aeration pattern even? ❑ ❑ ❑
If required, are Sanitary "Ts" present in tankage? 0 ❑ ❑ ❑
Comment: Residuals are removed by Lewis Farms and disposed of on their permitted application sites.
Dates of removal and amounts are recorded and tracked by Agua's Hampstead office.
Treatment Disinfection
Yes No NA NE
Is the system working?
❑ ❑ ❑
Do the fecal coliform results indicate proper disinfection?
❑ ❑ ❑
Is there adequate detention time (-30 minutes)?
❑
❑ ❑
Is the system properly maintained?
❑ ❑ ❑
If gas, does the cylinder storage appear safe?
❑
❑ ❑
Is the fan in the chlorine feed room and storage area operable?
❑
❑ ❑
Is the chlorinator accessible?
❑
❑ ❑
If tablets, are tablets present?
❑
❑ ❑
Are the tablets the proper size and type?
❑
❑ ❑
Is contact chamber free of sludge, solids, and growth?
❑ ❑ ❑
If UV, are extra UV bulbs available?
❑ ❑ ❑
If UV, is the UV intensity adequate?
❑ ❑ ❑
# Is it a dual feed system?
❑
❑ ❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
❑
❑ ❑
If yes, then is there a Risk Management Plan on site?
❑
❑ ❑
If yes, then what is the EPA twelve digit ID Number? (1000-
If yes, then when was the RMP last updated?
Comment: No comment.
Record Keeping Yes No NA NE
Is a copy of current permit available? ❑ ❑ ❑
Are monitoring reports present: NDMR? ❑ ❑ ❑
NDAR? ❑ ❑ ❑
Page 5 of 7
DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668
Permit: WQ0018755 Owner -Facility: Aqua North Carolina Inc
Inspection Date: 01/19/2021 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Are flow rates less than of permitted flow?
0
❑ ❑ ❑
Are flow rates less than of permitted flow?
0
❑ ❑ ❑
Are application rates adhered to?
0
❑ ❑ ❑
Is GW monitoring being conducted, if required (GW-59s submitted)?
❑ ❑ ❑
Are all samples analyzed for all required parameters?
❑ ❑ ❑
Are there any 2L GW quality violations?
❑ ❑ ❑
Is GW-59A certification form completed for facility?
❑
❑ ❑
Is effluent sampled for same parameters as GW?
0
❑ ❑ ❑
Do effluent concentrations exceed GW standards?
❑
0 ❑ ❑
Are annual soil reports available?
❑
❑ 0 ❑
# Are PAN records required?
❑
❑ ❑
# Did last soil report indicate a need for lime?
❑
❑ ❑
If so, has it been applied?
❑
❑ ❑
Are operational logs present?
0
❑ ❑ ❑
Are lab sheets available for review?
0
❑ ❑ ❑
Do lab sheets support data reported on NDMR?
❑ ❑ ❑
Do lab sheets support data reported on GW-59s?
❑
❑ ❑
Are Operational and Maintenance records present?
❑ ❑ ❑
Were Operational and Maintenance records complete?
0
❑ ❑ ❑
Has permittee been free of public complaints in last 12 months?
❑
❑ ❑
Is a copy of the SOC readily available?
❑
❑ 0 ❑
No treatment units bypassed since last inspection?
0
❑ ❑ ❑
Comment: Monitoring reports, lab results and COCs were organized and complete
with no issues.
Operation and maintenance records were complete. Aqua is field lab certified and Envirochem
analyzes the remaining parameters. Monitoring Wells #2 and #3 have had ammonia hits for the
past several years. The wells are located near a managed timber forest which is likely
Contributing to the ammonia exceedances.
End Use -Reuse
Yes No NA NE
Is the acreage in the permit being utilized?
❑ ❑ ❑
Does the acreage specified in the permit correspond to the measured acreage at the site?
❑
❑ ❑
Are all essential units provided in duplicate?
❑ ❑ ❑
Is an automatically activated standby power source available?
❑ ❑ ❑
Is the equalization capacity adequate?
❑ ❑ ❑
Is aerated flow equalization present?
❑ ❑ ❑
Has the turbidity meter been calibrated in the last 12 months?
❑ ❑ ❑
Does the turbidity meter have recording capabilities?
❑
❑ ❑
Is all flow diverted at the appropriate times?
❑ ❑ ❑
Page 6 of 7
DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668
Permit: WQ0018755 Owner - Facility:Aqua North Carolina Inc
Inspection Date: 01/19/2021 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Is all upset wastewater diverted from reuse storage unit?
0
❑ ❑ ❑
Is all upset wastewater treated, retreated, or disposed of acceptably?
0
❑ ❑ ❑
Is upset wastewater treated prior to discharge to irrigation storage?
0
❑ ❑ ❑
Is public access restricted from irrigation area during active site use?
❑ ❑ ❑
If golf course, is a sign posted in plain sight on the club house?
❑ ❑ ❑
Is the cover crop acceptable?
❑ ❑ ❑
Are buffers adequate?
❑
❑ ❑
Is the site free of ponding/runoff?
0
❑ ❑ ❑
Is the acreage in the permit being utilized?
0
❑ ❑ ❑
Is the application equipment acceptable?
0
❑ ❑ ❑
Is the application area free of limiting slopes?
❑ ❑ ❑
How close is the closest water supply well?
❑
❑ ❑
Are any supply wells within the CB?
❑
❑ ❑
Are any supply wells within 250' of the CB?
❑
❑ ❑
Is municipal water available in the area?
❑
❑ ❑
Are GW monitoring wells required?
❑ ❑ ❑
Are GW monitoring wells located properly w/ respect to RB and CB?
❑ ❑ ❑
Are GW monitoring wells properly constructed, including screened interval?
❑
❑ ❑
Comment: The turbidity meter was calibrated on 9/24/2020 by Delta Systems
Environmental. The EQ tank
high level visual and audio alarms were tested and operational. Upset wastewater is
automatically diverted to the 5-day upset pond and freeboard was —3 feet. The 5.4 MG storage
pond, located across the second entrance to the Castle Bay
subdivision, had a freeboard of —6
feet. Signs of reclaim water use are posted at the golf course hole #1, the storage pond
gate and
at the WWTF gate.
Page 7 of 7