Loading...
HomeMy WebLinkAboutWQ0018755_Compliance Evaluation Inspection_20210219DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668 ROY COOPER Governor MICHAEL 5. REGAN Secretary S. DANIEL SMITH 0irecror Joel A Mingus Aqua North Carolina Inc. 251 Merchant's Circle Hampstead, NC 28443 NORTH CAROLINA Environmental Quality February 01, 2021 SUBJECT: Compliance Inspection Report Castle Bay WWTP Non -discharge Permit No. WQ0018755 Pender County Dear Permittee: The North Carolina Division of Water Resources conducted an inspection of the Castle Bay WWTP on 1/19/2021. This inspection was conducted to verify that the facility is operating in compliance with the conditions and limitations specified in Non -discharge Permit No. WQ0018755. The findings and comments noted during this inspection are provided in the enclosed copy of the inspection report entitled "Compliance Inspection Report". There were no significant issues or findings noted during the inspection and therefore, a response to this inspection report is not required. If you should have any questions, please do not hesitate to contact Helen Perez with the Water Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at helen.perez@ncdenr.gov. Sincerely, DocuSigned by: 'Caµ "iln OA, for 7F141E73B6F3456... Morelia Sanchez -King, Regional Supervisor Water Quality Regional Operations Section Wilmington Regional Office Division of Water Resources, NCDEQ ATTACHMENTS Cc: Upload to Laserfiche North Carolina Department of Environmental Quality I Division of Water Resources Wanungton Regonal Dfhoe 1127 Cardinal Dn►le Extension 14hk"gton, North Caroina 28405 �- `•- ^^--� 90796-7215 DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668 Compliance Inspection Report Permit: WO0018755 Effective: 12/30/19 Expiration: 10/31/25 Owner : Aqua North Carolina Inc SOC: Effective: Expiration: Facility: Castle Bay WWTP County: Pender Castle Bay Dr Region: Wilmington Hampstead NC 28443 Contact Person: Joel A Mingus Title: Coastal Area Manager Phone: 910-270-1412 Directions to Facility: System Classifications: SI, WW2, Primary ORC: Kirklyn Bernard Fields Secondary ORC(s): On -Site Representative(s): On -site representative Related Permits: Certification: 998855 Joel A Mingus Phone: 910-270-1412 910-270-1412 Inspection Date: 01/19/2021 Entry Time 11:20AM Exit Time: 12:30PM Primary Inspector: Helen I Perez Docu ig 2/3/2021 e Y: Phone: 910-796-7387 Secondary Inspector(s): 1 D645B4A39694BE... Reason for Inspection: Routine Inspection Type: Compliance Evaluation Permit Inspection Type: Reclaimed Water Facility Status: Compliant Not Compliant Question Areas: Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent Miscellaneous Questions Treatment Flow Measurement -Water Treatment Treatment Barscreen Use Records Treatment Filters Record Keeping Treatment Activated Sludge Treatment Sludge Storage/Treatment Treatment Clarifiers Treatment Disinfection Treatment Flow Measurement Treatment Return pumps End Use -Reuse Standby Power (See attachment summary) Page 1 of 7 DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668 Permit: WQ0018755 Owner -Facility: Aqua North Carolina Inc Inspection Date: 01/19/2021 Inspection Type : Compliance Evaluation Reason for Visit: Routine Inspection Summary: A routine compliance inspection of the Castle Bay WWTF was conducted on January 19, 2021. The purpose of the evaluation was to verify that the facility is operating in compliance with the conditions and limitations specified in Permit W00018755. Joel Mingus and Kirkland Fields were present during the inspection. Castle Bay WWTF is a 100,000 GPD extended aeration treatment plant with teriary filters that produces reclaimed quality effluent. Disposal consists of the dedicated Castle Bay Golf Course site. Currently, the flow averages—25,000 to 35,000 GPD. The dirt road leading to the plant is in poor condition, especially when it rains. Aqua is planning on repairing the road in the near future. The golf course staff maintains records tracking the amount of reclaimed water irrigated on the golf course. Currently, Aqua does not have a system to confirm these application rates. It was discussed during the last inspection that the addition of a flowmeter measuring the water taken from the storage pond for irrigation purposes as being a starting point for this application confirmation. A flowmeter has been added into the 3-year capital improvement budget and Aqua is working towards installation. The facility is compliant with non -discharge permit W00018755. Please review the comment sections of the inspection report for more details. Page 2 of 7 DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668 Permit: WQ0018755 Owner - Facility:Aqua North Carolina Inc Inspection Date: 01/19/2021 Inspection Type : Compliance Evaluation Reason for Visit: Routine Type Yes No NA NE Infiltration System ❑ Lagoon Spray, LR ❑ Single Family Spray, LR ❑ Activated Sludge Spray, HR ❑ Activated Sludge Spray, LR ❑ Recycle/Reuse ❑ Activated Sludge Drip, LR ❑ Single Family Drip ❑ Reuse (Quality) Treatment Yes No NA NE Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑ Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑ Comment: Many improvements have been made in the last several years to the WWTF that were reported on the last insaection in February 2019. Treatment Flow Measurement -Influent Yes No NA NE Is flowmeter calibrated annually? ❑ ❑ ❑ Is flowmeter operating properly? ❑ ❑ ❑ Does flowmeter monitor continuously? ❑ ❑ ❑ Does flowmeter record flow? ❑ ❑ ❑ Does flowmeter appear to monitor accurately? ❑ ❑ ❑ Comment Treatment Flow Measurement -Water Use Records Yes No NA NE Is water use metered? ❑ 1:10 ❑ Are the daily average values properly calculated? 1111011 Comment: Treatment Flow Measurement -Effluent Yes No NA NE Is flowmeter calibrated annually? ❑ ❑ ❑ Is flowmeter operating properly? ❑ ❑ ❑ Does flowmeter monitor continuously? ❑ ❑ ❑ Does flowmeter record flow? ❑ ❑ ❑ Does flowmeter appear to monitor accurately? 0 ❑ ❑ ❑ Comment: The effluent flowmeter was calibrated on 10/31/2020 by Horizon Engineering and Consulting, Inc Standby Power Yes No NA NE Page 3 of 7 DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668 Permit: WQ0018755 Owner - Facility:Aqua North Carolina Inc Inspection Date: 01/19/2021 Inspection Type : Compliance Evaluation Reason for Visit: Routine Is automatically activated standby power available? 0 ❑ ❑ ❑ Is generator tested weekly by interrupting primary power source? 0 ❑ ❑ ❑ Is generator operable? 0 ❑ ❑ ❑ Does generator have adequate fuel? ❑ ❑ ❑ Comment: The generator is automatically tested every Wednesday and major preventative maintenance is Performed annually. Treatment Barscreen Yes No NA NE Is it free of excessive debris? ❑ ❑ ❑ Is disposal of screenings in compliance? ❑ ❑ ❑ Are the bars spaced properly? ❑ ❑ ❑ Is the unit in good condition? ❑ ❑ ❑ Comment: The manual barscreen is cleaned as needed Treatment Activated Sludge Yes No NA NE Is the aeration mechanism operable? ❑ ❑ ❑ Is the aeration basin thoroughly mixed? ❑ ❑ ❑ Is the aeration equipment easily accessed? ❑ ❑ ❑ Is Dissolved Oxygen adequate? ❑ ❑ ❑ Are Settleometer results acceptable? ❑ ❑ ❑ Is activated sludge an acceptable color? 0 ❑ ❑ ❑ Comment: Process control includes a settleometer test once a week and PH and DO monitoring. Treatment Clarifiers Yes No NA NE Are the weirs level? ❑ ❑ ❑ Are the weirs free of solids and algae? ❑ ❑ ❑ Is the scum removal system operational? ❑ ❑ ❑ Is the scum removal system accessible? ❑ ❑ ❑ Is the sludge blanket at an acceptable level? ❑ ❑ ❑ Is the effluent from the clarifier free of excessive solids? 0 ❑ ❑ ❑ Comment: Clarifier weirs are cleaned once a week. Surface scimmers appear to be operational. Treatment Return pumps Yes No NA NE Are they in place? 011011 Are they operational? 011011 Comment: No comment. Treatment Filters Yes No NA NE Is the filter media present? ❑ ❑ ❑ Is the filter media the correct size and type? ❑ ❑ ❑ Page 4 of 7 DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668 Permit: WQ0018755 Owner - Facility:Aqua North Carolina Inc Inspection Date: 01/19/2021 Inspection Type : Compliance Evaluation Reason for Visit: Routine Is the air scour operational? 0 ❑ ❑ ❑ Is the scouring acceptable? ❑ ❑ ❑ Is the clear well free of excessive solids? 0 ❑ ❑ ❑ Is the mud well free of excessive solids and filter media? 0 ❑ ❑ ❑ Does backwashing frequency appear adequate? 0 ❑ ❑ ❑ Comment: The tertiary filters beds have two floats to activate backwashing, which usually takes place 2-3 times a day. Treatment Sludge Storage/Treatment Yes No NA NE Is the aeration operational? ❑ ❑ ❑ Is the aeration pattern even? ❑ ❑ ❑ If required, are Sanitary "Ts" present in tankage? 0 ❑ ❑ ❑ Comment: Residuals are removed by Lewis Farms and disposed of on their permitted application sites. Dates of removal and amounts are recorded and tracked by Agua's Hampstead office. Treatment Disinfection Yes No NA NE Is the system working? ❑ ❑ ❑ Do the fecal coliform results indicate proper disinfection? ❑ ❑ ❑ Is there adequate detention time (-30 minutes)? ❑ ❑ ❑ Is the system properly maintained? ❑ ❑ ❑ If gas, does the cylinder storage appear safe? ❑ ❑ ❑ Is the fan in the chlorine feed room and storage area operable? ❑ ❑ ❑ Is the chlorinator accessible? ❑ ❑ ❑ If tablets, are tablets present? ❑ ❑ ❑ Are the tablets the proper size and type? ❑ ❑ ❑ Is contact chamber free of sludge, solids, and growth? ❑ ❑ ❑ If UV, are extra UV bulbs available? ❑ ❑ ❑ If UV, is the UV intensity adequate? ❑ ❑ ❑ # Is it a dual feed system? ❑ ❑ ❑ Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)? ❑ ❑ ❑ If yes, then is there a Risk Management Plan on site? ❑ ❑ ❑ If yes, then what is the EPA twelve digit ID Number? (1000- If yes, then when was the RMP last updated? Comment: No comment. Record Keeping Yes No NA NE Is a copy of current permit available? ❑ ❑ ❑ Are monitoring reports present: NDMR? ❑ ❑ ❑ NDAR? ❑ ❑ ❑ Page 5 of 7 DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668 Permit: WQ0018755 Owner -Facility: Aqua North Carolina Inc Inspection Date: 01/19/2021 Inspection Type : Compliance Evaluation Reason for Visit: Routine Are flow rates less than of permitted flow? 0 ❑ ❑ ❑ Are flow rates less than of permitted flow? 0 ❑ ❑ ❑ Are application rates adhered to? 0 ❑ ❑ ❑ Is GW monitoring being conducted, if required (GW-59s submitted)? ❑ ❑ ❑ Are all samples analyzed for all required parameters? ❑ ❑ ❑ Are there any 2L GW quality violations? ❑ ❑ ❑ Is GW-59A certification form completed for facility? ❑ ❑ ❑ Is effluent sampled for same parameters as GW? 0 ❑ ❑ ❑ Do effluent concentrations exceed GW standards? ❑ 0 ❑ ❑ Are annual soil reports available? ❑ ❑ 0 ❑ # Are PAN records required? ❑ ❑ ❑ # Did last soil report indicate a need for lime? ❑ ❑ ❑ If so, has it been applied? ❑ ❑ ❑ Are operational logs present? 0 ❑ ❑ ❑ Are lab sheets available for review? 0 ❑ ❑ ❑ Do lab sheets support data reported on NDMR? ❑ ❑ ❑ Do lab sheets support data reported on GW-59s? ❑ ❑ ❑ Are Operational and Maintenance records present? ❑ ❑ ❑ Were Operational and Maintenance records complete? 0 ❑ ❑ ❑ Has permittee been free of public complaints in last 12 months? ❑ ❑ ❑ Is a copy of the SOC readily available? ❑ ❑ 0 ❑ No treatment units bypassed since last inspection? 0 ❑ ❑ ❑ Comment: Monitoring reports, lab results and COCs were organized and complete with no issues. Operation and maintenance records were complete. Aqua is field lab certified and Envirochem analyzes the remaining parameters. Monitoring Wells #2 and #3 have had ammonia hits for the past several years. The wells are located near a managed timber forest which is likely Contributing to the ammonia exceedances. End Use -Reuse Yes No NA NE Is the acreage in the permit being utilized? ❑ ❑ ❑ Does the acreage specified in the permit correspond to the measured acreage at the site? ❑ ❑ ❑ Are all essential units provided in duplicate? ❑ ❑ ❑ Is an automatically activated standby power source available? ❑ ❑ ❑ Is the equalization capacity adequate? ❑ ❑ ❑ Is aerated flow equalization present? ❑ ❑ ❑ Has the turbidity meter been calibrated in the last 12 months? ❑ ❑ ❑ Does the turbidity meter have recording capabilities? ❑ ❑ ❑ Is all flow diverted at the appropriate times? ❑ ❑ ❑ Page 6 of 7 DocuSign Envelope ID: 8853A46D-5A69-4E51-B26B-B7F6A4D64668 Permit: WQ0018755 Owner - Facility:Aqua North Carolina Inc Inspection Date: 01/19/2021 Inspection Type : Compliance Evaluation Reason for Visit: Routine Is all upset wastewater diverted from reuse storage unit? 0 ❑ ❑ ❑ Is all upset wastewater treated, retreated, or disposed of acceptably? 0 ❑ ❑ ❑ Is upset wastewater treated prior to discharge to irrigation storage? 0 ❑ ❑ ❑ Is public access restricted from irrigation area during active site use? ❑ ❑ ❑ If golf course, is a sign posted in plain sight on the club house? ❑ ❑ ❑ Is the cover crop acceptable? ❑ ❑ ❑ Are buffers adequate? ❑ ❑ ❑ Is the site free of ponding/runoff? 0 ❑ ❑ ❑ Is the acreage in the permit being utilized? 0 ❑ ❑ ❑ Is the application equipment acceptable? 0 ❑ ❑ ❑ Is the application area free of limiting slopes? ❑ ❑ ❑ How close is the closest water supply well? ❑ ❑ ❑ Are any supply wells within the CB? ❑ ❑ ❑ Are any supply wells within 250' of the CB? ❑ ❑ ❑ Is municipal water available in the area? ❑ ❑ ❑ Are GW monitoring wells required? ❑ ❑ ❑ Are GW monitoring wells located properly w/ respect to RB and CB? ❑ ❑ ❑ Are GW monitoring wells properly constructed, including screened interval? ❑ ❑ ❑ Comment: The turbidity meter was calibrated on 9/24/2020 by Delta Systems Environmental. The EQ tank high level visual and audio alarms were tested and operational. Upset wastewater is automatically diverted to the 5-day upset pond and freeboard was —3 feet. The 5.4 MG storage pond, located across the second entrance to the Castle Bay subdivision, had a freeboard of —6 feet. Signs of reclaim water use are posted at the golf course hole #1, the storage pond gate and at the WWTF gate. Page 7 of 7