HomeMy WebLinkAboutNC0025542_Compliance Evaluation Inspection_20210119ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
S. DANIEL SMITH NORTH CAROLINA
Director Environmental Quality
January 19, 2021
Shawn Pennell, Public Utilities Director
City of Hickory
Post Office Box 398
Hickory, North Carolina 28603-0398
Subject: Compliance Evaluation Inspection
Hickory -Catawba WWTP
NPDES Permit No. NC0025542
Catawba County
Dear Mr. Pennell:
Enclosed is a copy of the Compliance Evaluation Inspection Report for the inspection conducted at the subject
facility on January 14, 2021, by Mr. Wes Bell of this Office. Please inform the facility's Operator -in -Responsible
Charge (ORC) of our findings by forwarding a copy of the enclosed report.
Should you have any questions concerning this letter, please do not hesitate to contact Mr. Bell at (704) 235-
2192, or via email at wes.bell@ncdenr.gov.
Enclosure:
Inspection Report
D_E
NORTH CAROLINA
Department el EnNrumimbl Qualpy
Sincerely,
-DocuSigned by:
"-A14CC681AF27425...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1610 East Center Avenue, Suite 301 I Mooresville, North Carolina 28115
704.663.1699
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code
1 IN I 2 IL I
21 1 1 1 1 1 1
NPDES yr/mo/day Inspection
3 I NC0025542 111 121 21/01/14 117
Type
1810I
I I 1 1 1
Inspector Fac Type
191 S I 2011
1 1 1 11 1 1 1 I I I 1 1 1 1 1 1 I I I I I
1 11
1 1 1 I 1 P6
Inspection Work Days
67I2.0
Facility Self -Monitoring Evaluation Rating B1 QA Reserved
I 70I4 I 71IN I 72 I N I 73I 1 74 751
I I 1
I I I I I I I80
l
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES Dermit Number)
Catawba WWTP
End Of Sixth Ave Nw
Catawba NC 28609
Entry Time/Date
09:25AM 21/01/14
Permit Effective Date
16/11/01
Exit Time/Date
12:05PM 21/01/14
Permit Expiration Date
20/04/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
David Archambault/ORC/828-234-7419/
Todd Atwell Bumgarner//828-322-5075 /
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Warren Wood,PO Box 398 Hickory NC 286010398/City Manager/828-323-7412/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s)
Wes Bell
of Inspector(s) Agency/Office/Phone and Fax Numbers Date
—Docusigned by: DWR/MRO WQ/704-663-1699 Ext.2192/
144- B 1/19/2021
'-A61696D90CC3437...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger DWR/Division of Water Quality/704-235-2194/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
DocuSigned by:
1/19/2021
A14CC681AF27425...
Page# 1
NPDES yr/mo/day
31 NC0025542 111 121 21/01/14
I17
Inspection Type
18 [j
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page# 2
Permit: NC0025542
Inspection Date: 01/14/2021
Owner - Facility: Catawba WWTP
Inspection Type: Compliance Evaluation
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The Division received the facility's permit renewal application on 1/16/2020.
The City implements a Division -approved Industrial Pretreatment Program.
The last compliance evaluation inspection at this facility was performed by DWR staff on
12/12/2018.
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? • ❑ ❑ ❑
Is all required information readily available, complete and current? • ❑ ❑ ❑
Are all records maintained for 3 years (lab. reg. required 5 years)? • ❑ ❑ ❑
Are analytical results consistent with data reported on DMRs? • ❑ ❑ ❑
Is the chain -of -custody complete? • ❑ ❑ ❑
Dates, times and location of sampling •
Name of individual performing the sampling •
Results of analysis and calibration •
Dates of analysis •
Name of person performing analyses •
Transported COCs •
Are DMRs complete: do they include all permit parameters? • ❑ ❑ ❑
Has the facility submitted its annual compliance report to users and DWQ? • ❑ ❑ ❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operatc ❑ ❑ • ❑
on each shift?
Is the ORC visitation log available and current? • ❑ ❑ ❑
Is the ORC certified at grade equal to or higher than the facility classification? • El El El
Is the backup operator certified at one grade less or greater than the facility classification' • ❑ ❑ ❑
Is a copy of the current NPDES permit available on site? • ❑ ❑ ❑
Facility has copy of previous year's Annual Report on file for review? ❑ ❑ ❑ •
Page# 3
Permit: NC0025542
Inspection Date: 01/14/2021
Owner - Facility: Catawba WWTP
Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Comment: The records reviewed during the inspection were organized and well maintained. Discharge
Monitoring Reports (eDMRs) were reviewed for the period December 2019 through
November 2020. All monitoring frequencies were correct. Weekly average effluent
ammonia violations were reported in March and April 2020. Monthly average effluent
ammonia violations were reported in January, March and April 2000. These violations have
been previously addressed by the Division through the issuances of Notice of Violations
(NOVs) and/or civil penalty assessments.
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? • ❑ ❑ ❑
Are all other parameters(excluding field parameters) performed by a certified lab? • ❑ ❑ ❑
# Is the facility using a contract lab? • ❑ ❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees • ❑ ❑ ❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ • ❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ • ❑
Comment: Influent and effluent analyses are performed under the City of Hickory's municipal laboratory
certification #203. Pace Analytical Services, Blue Ridge Labs and ETT Environmental have
also been contracted to provide analytical support.
Influent Sampling
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is sampling performed according to the permit?
Yes No NA NE
• ❑ ❑ ❑
❑ • ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The subject permit requires influent BOD and TSS composite samples. Sampler aliquot
checks are performed (and documented) multiple times per month.
Filter backwash, plant drainage system and decant (sludge holding tanks) all discharge
upstream of the influent sampling location; however, the ORC and staff do not decant during
influent sampling events. The City is currently investigating a new influent sampling location
above all side streams.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Yes No NA NE
Page# 4
Permit: NC0025542
Inspection Date: 01/14/2021
Owner - Facility: Catawba WWTP
Inspection Type: Compliance Evaluation
Effluent Sampling
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The subject permit requires composite and grab effluent samples. Sampler aliquot checks
are performed (and documented) multiple times per month.
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, anc • ❑ ❑ ❑
sampling location)?
Comment:
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The wastewater treatment facility appeared to be properly operated and well maintained.
The facility staff incorporate a comprehensive process control program with all
measurements being properly documented and maintained on -site. In-depth operation and
maintenance records were also being maintained on -site. The facility is also equipped with
a SCADA System.
Although not required, the facility is visited by certified operators seven days per week.
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment:
Grit Removal
Type of grit removal
a.Manual
Yes No NA NE
Yes No NA NE
Page# 5
Permit: NC0025542
Inspection Date: 01/14/2021
Owner - Facility: Catawba WWTP
Inspection Type: Compliance Evaluation
Grit Removal
b.Mechanical
Is the grit free of excessive organic matter?
Is the grit free of excessive odor?
# Is disposal of grit in compliance?
Comment: Screenings and grit are disposed at the County Landfill.
Oxidation Ditches
Are the aerators operational?
Are the aerators free of excessive solids build up?
# Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Are settleometer results acceptable (> 30 minutes)?
Is the DO level acceptable?(1.0 to 3.0 mg/I)
Are settelometer results acceptable?(400 to 800 ml/I in 30 minutes)
Yes No NA NE
•
IN El El El
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: One of two oxidation ditch trains was in service due to low influent flows. Each oxidation
ditch train is equipped with an anaerobic and anoxic basin. Soda ash is added to maintain
alkalinity/pH levels and a microbial supplement is added to provide an additional carbon
source.
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? • ❑ ❑ El
Is the site free of excessive buildup of solids in center well of circular clarifier? • ❑ ❑ ❑
Are weirs level? • ❑ El El
Is the site free of weir blockage? • ❑ ❑ ❑
Is the site free of evidence of short-circuiting? • ❑ ❑ ❑
Is scum removal adequate? • El El El
Is the site free of excessive floating sludge? • ❑ ❑ ❑
Is the drive unit operational? • ❑ ❑ ❑
Is the return rate acceptable (low turbulence)? • ❑ ❑ ❑
Is the overflow clear of excessive solids/pin floc? • ❑ ❑ ❑
Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth) • ❑ ❑ ❑
Comment: Both secondary clarifiers were operational; however, only one clarifier was in service.
Page# 6
Permit: NC0025542
Inspection Date: 01/14/2021
Owner - Facility: Catawba WWTP
Inspection Type: Compliance Evaluation
Pumps-RAS-WAS
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
Comment:
Filtration (High Rate Tertiary)
Type of operation:
Is the filter media present?
Is the filter surface free of clogging?
Is the filter free of growth?
Is the air scour operational?
Is the scouring acceptable?
Is the clear well free of excessive solids and filter media?
Yes No NA NE
• ❑ ❑ ❑
Yes No NA NE
Down flow
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: All four tertiary filters were operational; however, only one filter was in service.
Disinfection -Liquid
Is there adequate reserve supply of disinfectant?
(Sodium Hypochlorite) Is pump feed system operational?
Is bulk storage tank containment area adequate? (free of leaks/open drains)
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
De -chlorination Yes No NA NE
Type of system ? Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)? • ❑ El El
Is storage appropriate for cylinders? ❑ ❑ • ❑
# Is de -chlorination substance stored away from chlorine containers? • ❑ ❑ ❑
Comment:
Are the tablets the proper size and type? ❑ ❑ • ❑
Are tablet de -chlorinators operational? ❑ ❑ • ❑
Number of tubes in use?
Page# 7
Permit: NC0025542
Inspection Date: 01/14/2021
Owner - Facility: Catawba WWTP
Inspection Type: Compliance Evaluation
De -chlorination Yes No NA NE
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The flow meter is calibrated twice per year and was last calibrated on 1/16/2020 by
Diversified Integration, Inc.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ • ❑
Comment: The effluent appeared clear with no floatable solids or foam. The receiving stream did not
appear to be negatively impacted.
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The facility is equipped with two aerated sludge holding tanks. Sludge is transported by City
personnel to the Regional Compost Facility for continued processing/treatment.
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 8
Permit: NC0025542
Inspection Date: 01/14/2021
Owner - Facility: Catawba WWTP
Inspection Type: Compliance Evaluation
Standby Power Yes No NA NE
Comment: The backup generator is tested twice per month with one of these tests being under a load.
The generator is serviced by City personnel and Cummings has also been contracted to
perform repairs, etc.
Page# 9