SUBJECT: Compliance Inspection Report
Connestee Falls WWTP #1
NPDES WW Permit No. NCO024295
Transylvania County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Connestee Falls WWTP
#1 on 1/20/2021. This inspection was conducted to verify that the facility is operating in compliance
with the conditions and limitations specified in NPDES WW Permit No. NC0024295. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled "Compliance Inspection Report".
Please respond in writing to this office within 30 days of your receipt of this letter regarding your plans
or measures to be taken to address the following issues:
The effluent pipe has separated at the concrete step aerator where it discharges to the receiving stream.
This may result in undermining the structure. Repair the effluent pipe and stabilize the discharge structure.
If you should have any questions, please do not hesitate to contact Timothy Heim with the Water
Quality Regional Operations Section in the Asheville Regional Office at 828-296-4500 or via email at
tim.heim@ncdenr.gov.
ATTACHMENTS
Ec: LF
Sincerely,
CDocuSigned by:
1—r(OA A� tkUwt
082B1105A3CA418
Tim Heim, P.E., Environmental Engineer
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
North Carofina Depsftment of Emnronmental Quairty I Dsvwon of Water Resources
AsheW* Ragronal Moe 12090 U.S. 70 Htlrway I Swannsnos, North Camino 28778
DocuSign Envelope ID: E824D320-A0F4-4E1 C-994F-5FD5387BF7F8
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 I 3 I NC0024295 I11 121 21/01/20 I17 18 n 19 L G j 201
21111111111111111111111111111111111111111111 f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 CA ---------------------- Reserved -------------------
67
I 71 I I 72 L n, � 73 LLI74 71 I I I I I I I80
70 Iu ty LJ
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
10:OOAM 21/01/20
17/12/01
Connestee Falls WWTP #1
5999 Greenville Hwy
Exit Time/Date
Permit Expiration Date
Brevard NC 28712
12:OOPM 21/01/20
20/09/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Douglas McArthur Corn/ORC/800-222-5291/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Tony Konsul,PO Box 240908 Charlotte NC 282240908/Operations
Director/704-319-0523/7045258174 Yes
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar 0 Records/Reports
Facility Site Review 0 Effluent/Receiving Wate
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Timothy H Heim DWR/ARO WQ/828-296-4665/
[DocuSigndby: 1/25/2021
lwtb{ (�Uwt
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
i 1/25/2021
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
DocuSign Envelope ID: E824D320-A0F4-4E1 C-994F-5FD5387BF7F8
NPDES yr/mo/day Inspection Type (Cont.)
31 NCO024295 I11 12I 21/01/20 117 18 ICI
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Tim Heim of the Asheville Regional Office performed a Compliance Evaluation Inspection of the facility
on January 21, 2021. Douglas Corn (ORC) was present and assisted with the inspection.
No violations of the permit conditions or deleterious impacts to the receiving stream were observed at
the time of the inspection, and the facility appeared compliant with NC0024295. This is a relatively new
and state -of -the art facility.
The following items were noted at the time of the inspection:
The effluent pipe has separated at the concrete step aerator where it discharges to the receiving
stream. This may result in undermining the structure. Repair the effluent pipe and stabilize the
discharge structure.
Page#
DocuSign Envelope ID: E824D320-A0F4-4E1 C-994F-5FD5387BF7F8
Permit: NCO024295 Owner -Facility: Connestee Falls WWTP #1
Inspection Date: 01/20/2021 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment:
Operations & Maintenance
Yes
No
NA
NE
Is the plant generally clean with acceptable housekeeping?
0
❑
❑
❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
0
❑
❑
❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Pump Station - Influent
Yes
No
NA
NE
Is the pump wet well free of bypass lines or structures?
0
❑
❑
❑
Is the wet well free of excessive grease?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Is SCADA telemetry available and operational?
0
❑
❑
❑
Is audible and visual alarm available and operational?
0
❑
❑
❑
Comment:
Bar Screens
Yes
No
NA
NE
Type of bar screen
a.Manual
❑
b.Mechanical
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment:
Page# 3
DocuSign Envelope ID: E824D320-A0F4-4E1 C-994F-5FD5387BF7F8
Permit: NC0024295 Owner - Facility:
Inspection Date: 01/20/2021 Inspection Type:
Connestee Falls WWTP #1
Compliance Evaluation
Sequencing Batch Reactors
Yes
No
NA
NE
Type of operation:
Duplex
Is the reactor effluent free of solids?
❑
❑
❑
Does minimum fill time correspond to the peak hour flow rate of the facility?
❑
❑
❑
Is aeration and mixing cycled on and off during fill?
❑
❑
❑
The operator understands and can explain the process?
❑
❑
❑
Comment:
Filtration (High Rate Tertiary)
Yes
No
NA
NE
Type of operation:
Cross
flow
Is the filter media present?
0
❑
❑
❑
Is the filter surface free of clogging?
0
❑
❑
❑
Is the filter free of growth?
0
❑
❑
❑
Is the air scour operational?
❑
❑
0
❑
Is the scouring acceptable?
❑
❑
0
❑
Is the clear well free of excessive solids and filter media?
0
❑
❑
❑
Comment:
Disinfection - UV
Yes
No
NA
NE
Are extra UV bulbs available on site?
0
❑
❑
❑
Are UV bulbs clean?
0
❑
❑
❑
Is UV intensity adequate?
0
❑
❑
❑
Is transmittance at or above designed level?
0
❑
❑
❑
Is there a backup system on site?
0
❑
❑
❑
Is effluent clear and free of solids?
0
❑
❑
❑
Comment:
Flow Measurement - Effluent
Yes
No
NA
NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
❑
Comment:
Page# 4
DocuSign Envelope ID: E824D320-A0F4-4E1 C-994F-5FD5387BF7F8
Permit: NC0024295 Owner -Facility: Connestee Falls WWTP #1
Inspection Date: 01/20/2021 Inspection Type: Compliance Evaluation
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑
Are the receiving water free of foam other than trace amounts and other debris? 0 ❑ ❑ ❑
If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ 0 ❑
Comment: The effluent pipe has separated at the concrete step aerator where it discharges to the
receiving stream. This may result in undermining the structure. Repair the effluent pipe and
stabilize the discharae structure.
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Comment:
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ❑ ■
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Page# 5