HomeMy WebLinkAboutWQ0019868_Permit (Issuance)_20010503State of North Carolina
•Department of Environment
and Natural Resources
Division of Water Quality
Michael F. Easley, Governor
William G. Ross, Jr., Secretary
Kerr T. Stevens, Director
May 3, 2001
WILLIAM A. WATSON, OWNER
CAROLYN'S COURT
POST OFFICE BOX 7096
WHITE LAKE. NC 28337
AVA
NCDENR
NORTH CAROLINA DEPARTMENT OF
ENVIRONMENT AND NATUEAL..RESCDURCES
DENR-F� .
NAY 7 2001
DWQ
Subject: Permit No. WQ0019868
Carolyn's Court
Wastewater Collection System Extension
Bladen County
Dear Mr. Watson:
In accordance with your application received April 5, 2001, we are forwarding herewith Permit No.
WQ0019868, dated May 3, 2001, to Carolyn's Court for the construction and operation of the subject wastewater
collection system extension. This permit shall be effective from the date of issuance until rescinded and shall be
subject to the conditions and limitations as specified therein. This cover letter shall be considered a part of this
permit and is therefore incorporated therein by reference.
Please pay particular attention to Permit Condition 3 which requires that the wastewater collection
facilities be properly operated and maintained in accordance with 15A NCAC 2H .0227 or any individual
system -wide collection system permit issued to the Permittee.
Permitting of this project does not constitute an acceptance of any part of the project that does not meet
15A NCAC 2H .0200; the Division of Water Quality's (Division) Gravity Sewer Minimum Design Criteria
adopted February 12, 1996 as applicable; and the Division's Minimum Design Criteria for the Fast -Track
Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable, unless specifically mentioned
herein. Division approval is based on acceptance of the certification provided by a North Carolina -licensed
Professional Engineer in the application. It shall be the Permittee's responsibility to ensure that the as -
constructed project meets the appropriate design criteria and rules. Failure to comply may result in penalties in
accordance with North Carolina General Statute § 143-215.6A through § 143-215.6C, construction of additional or
replacement wastewater collection facilities, and/or referral of the North Carolina -licensed Professional Engineer
to the licensing board.
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as
amended, and other applicable Laws, Rules, and Regulations, permission is hereby granted to Carolyn's Court for
the construction and operation of approximately 405 linear feet of 6-inch gravity sewer to serve five (5) two -
bedroom units as part of the Carolyn's Court project, and the discharge of 1,200 gallons per day of collected
domestic wastewater into the Town of White Lake's existing sewerage system, pursuant to the application
received April 5, 2001, and in conformity with 15A NCAC 2H .0200; the Division's Gravity Sewer Minimum
Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -
Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting
data subsequently filed and approved by the Department of Environment and Natural Resources and considered a
part of this permit.
1617 Mail Service Center, Raleigh, North Carolina 27699-1617 Telephone (919) 733-5083 FAX (919) 715-6048
An Equal Opportunity Affirmative Action Employer 50% recycled/ 10% post -consumer paper
The sewage and wastewater collected by this system shall be treated in the Town of White Lae
Wastewater Treatment Facility (NPDES Permit No. NC0023353) prior to being discharged into the receiving
stream.
This permit shall become voidable unless the agreement between Carolyn's Court and the Town of White
Lake for the collection and final treatment of wastewater is in full force and effect.
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the right to
request an adjudicatory hearing upon written request within 30 days following receipt of this permit. This
request must be in the form of a written petition, conforming to Chapter 150B of North Carolina General
Statutes, and filed with the Office of Administrative Hearings, 6714 Mail Service Center, Raleigh, NC 27699-
6714. Unless such demands are made, this permit shall be final and binding.
If you need additional information concerning this matter, please contact Kristin E. Miguez at
(919) 733-5083 extension 524.
Sincerely,
Kerr T. Stevens
7/7
el)-14Ptc
cc: Bladen County Health Department
Fayetteville Regional Office, Water Quality Section (WWTF Permit No. NC0023353)
Anderson Engineering & Associates, PA
Town of White Lake —PO Box 7250, White Lake, NC 28337-7250
NORTH CAROLINA
ENVIRONMENTAL' MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
RALEIGH
WASTEWATER COLLECTION SYSTEM EXTENSION PERMIT
This permit shall be effective from the date of issuance until rescinded and shall be subject to the following
specified conditions and limitations:
1. This permit shall become voidable unless the wastewater collection facilities are constructed in accordance
with the conditions of this permit; 15A NCAC 2H .0200; the Division of Water Quality's (Division) Gravity
Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design
Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as
applicable; and other supporting materials unless specifically mentioned herein.
2. This permit shall be effective only with respect to the nature and volume of wastes described in the
application and other supporting data.
3. The wastewater collection facilities shall be properly maintained and operated at all times. The Permittee
shall maintain compliance with an individual system -wide collection system permit for the operation and
maintenance of these facilities as required by 15A NCAC 2H .0227. If an individual permit is not required,
the following performance criteria shall be met as provided in 15A NCAC 2H .0227:
a. The sewer system shall be effectively maintained and operated at all times to prevent discharge to land
or surface waters, and any contravention of the groundwater standards in 15A NCAC 2L .0200 or the
surface water standards in 15A NCAC 2B .0200.
b. A map of the sewer system shall be developed prior to January 1, 2004 and shall be actively
maintained.
c. An operation and maintenance plan shall be developed and implemented.
d. Pump stations that are not connected to a telemetry system shall be inspected at least three times per
week until July 1, 2000; thereafter, pump stations shall be inspected at least daily, as defined in 15A
NCAC 2B .0503(5), until July 1, 2001; and thereafter, pump stations shall be inspected every day.
Pump stations that are connected to a telemetry system shall be inspected at least once per week.
e. High -priority sewer lines shall be inspected at least once per every six-month period of time.
f. A general observation of the entire sewer system shall be conducted at least once per year.
g. Inspection and maintenance records shall be maintained for a period of at least three years.
h. Overflows and bypasses shall be reported to the appropriate Division regional office in accordance
with 15A NCAC 2B .0506(a), and public notice shall be provided as required by North Carolina
General Statute §143-215.1C.
1
4. This permit shall not be transferable. In the event there is a desire for the wastewater collection facilities
to change ownership, or there is a name change of the Permittee, a formal permit request shall be submitted
to the Division accompanied by documentation from the parties involved, and other supporting materials as
may be appropriate. The approval of this request shall be considered on its merits and may or may not be
approved.
5. Construction of the gravity sewers shall be scheduled so as not to interrupt service by the existing utilities
nor result in an overflow or bypass discharge of wastewater to the surface waters of the State.
6. Upon completion of construction and prior to operation of these permitted facilities, a certification, a copy
of the construction record drawings, as well as supporting design calculations for any pump stations
permitted as part of this project shall be received from a North Carolina -licensed Professional Engineer
certifying that the facilities have been installed in accordance with this permit; 15A NCAC 2H .0200; the
Division's Gravity Sewer Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum
Design Criteria for the Fast -Track Permitting of Pump Station and Force Main adopted June 1, 2000 as
applicable; and other supporting materials. If this project is to be completed in phases and partially
certified, you shall retain the responsibility to track further construction approved under the same permit,
and shall provide a final certificate of completion once the entire project has been completed. A copy of the
construction record drawings, indicating the facilities constructed in the phase being certified, shall be
submitted with each partial certification. Mail the Engineer's Certification, one copy of the "Construction
Record Drawings", and one copy of the supporting design calculations to the Non -Discharge Permitting
Unit, 1617 Mail Service Center, Raleigh, NC 27699-1617.
7. A copy of the construction record drawings shall be maintained on file by the Permittee for the life of the
wastewater collection facilities.
8. Failure to abide by the conditions and limitations contained in this permit; 15A NCAC 2H .0200; the
Division's Gravity Sewer Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum
Design Criteria for the Fast -Track Permitting of Pump Station and Force Mains adopted June 1, 2000 as
applicable; and other supporting materials may subject the Permittee to an enforcement action by the
Division, in accordance with North Carolina General Statutes § 143-215.6A through § 143-215.6C.
9. In the event that the wastewater collection facilities fail to perform satisfactorily, including the creation of
nuisance conditions, the Permittee shall take immediate corrective action, including those as may be
required by this Division, such as the construction of additional or replacement facilities.
10. The issuance of this permit shall not exempt the Permittee from complying with any and all statutes, rules,
regulations, or ordinances that may be imposed by other government agencies (local, state and federal)
which have jurisdiction, including but not limited to applicable river buffer rules in 15A NCAC 2B .0200,
erosion and sedimentation control requirements in 15A NCAC Ch. 4 and under the Division's General
Permit NCG0100000, and any requirements pertaining to wetlands under 15A NCAC 2B .0200 and 15A
NCAC 2H .0500.
11. Noncompliance Notification:
The Permittee shall report by telephone to the Fayetteville Regional Office, telephone number (910) 486-
1541, as soon as possible, but in no case more than 24 hours or on the next working day, following the
occurrence or first knowledge of the occurrence of either of the following:
a. Any process unit failure, due to known or unknown reasons, that renders the facility incapable of
adequate wastewater transport, such as mechanical or electrical failures of pumps, line blockage or
breakage, etc.; or
b. Any failure of a pumping station or sewer line resulting in a by-pass directly to receiving waters without
treatment of all or any portion of the influent to such station or facility.
2
Persons reporting such occurrences by telephone shall also file a written report in letter form within five
days following first knowledge of the occurrence. This report must outline the actions taken or proposed to
be taken to ensure that the problem does not recur.
Permit issued this the third day of May, 2001
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
/(.4
6, Kerb T. Stevens, Director U
Division of Water Quality
By Authority of the Environmental Management Commission
Permit Number WQ0019868
3
Permit No. WQ0019868
May 3, 2001
ENGINEER'S CERTIFICATION
Partial Final
I, , as a duly registered Professional Engineer in the State of North Carolina,
having been authorized to observe (periodically, weekly, full time) the construction of the
project, for the
Project Name Location and County
Permittee hereby state that, to the best of my abilities, due care and diligence was used in the observation of the
construction such that the construction was observed to be built within substantial compliance of this permit;
15A NCAC 2H .0200; the Division of Water Quality's (Division) Gravity Sewer Minimum Design Criteria
adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting
of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting materials.
North Carolina Professional Engineer's seal, signature, and date:
The above Engineer's Certification shall be completed and submitted to the address below with one copy of the
"Construction Record Drawings" of the wastewater collection system extension as well as supporting design
calculations for any pump stations permitted as part of this project. This project shall not be considered complete
nor allowed to operate until this Engineer's Certification and all required supporting documentation have been
received by the Division. Any wastewater flow made tributary to the wastewater collection system extension
prior to completion of this Engineer's Certification shall be considered a violation of the permit and shall subject
the Permittee to appropriate enforcement actions.
NORTH CAROLINA DIVISION OF WATER QUALITY
WATER QUALITY SECTION
NON -DISCHARGE PERMITTING UNIT
1617 MAIL SERVICE CENTER
RALEIGH, NORTH CAROLINA 27699-1617
4
04/17/2001111 12:46
919-715-6048
DWQ NON DISCHARGE BR PAGE 01/01
PROCEDURE 4 REQUEST FORM
DATE: /7 d/
TO FROM: Paul Rawls, Water Quality Supervisor
Fayetteville Regional Office, Water Quality Section
TO FROM: Kristin Miguez
Non -Discharge Permitting Unit
State Engineering Review Group
(919) 733-5083 x524
Fax (919) 715-6048
Application Number:
Applicant: C'a �l tins
Receiving
Flow. Volu
Engineer:
6 /9g log County: £%a.ie'1
Name: ease �y r► s eou
Facility: i G� f
d.
Project N
o Permit# CdD433S3
• a GPD Flow Type: _)C Dom. Com. In
-awe--SOC project? yes no
Approval: V
Denial:
Comments:
Regional Signature:
Application Number: County:
Applicant:
Project Name:
Receiving Facility: Permit #
Flow Volume: GPD Flow Type: Dom. Com. Ind.
Engineer: SOC project? yes no
Approval:
Comments:
Denial:
Regional Signature:
GKEX88/MP
COMPLIANCE EVALUATION ANALYSIS REPORT
04/19/2001
PAGE 1
PERMIT--NC0023353 PIPE--001
FACILITY --WHITE LAKE WWTP, TOWN OF
LOCATION --WHITE LAKE
REPORT PERIOD: 0001-0012 LOC---E
DESIGN FLOW-- .8000 CLASS--2
REGION/COUNTY--06 BLADEN
50050 00310 00530 00610 31616 50060 00300 00010
MONTH Q/MGD BOD RES/TSS NH3+NH4- FEC COLI CHLORINE DO TEMP
LIMIT F .8000 F 30.00 F 90.0 NOL F 200.0 NOL NOL NOL
00/01 .4161 7.05 17.7 2.51 .0 .536 11.75 7.80
00/02 .4362 8.97 20.0 1.61 .0 .542 11.60 9.77
00/03 .4209 6.38 5.2 3.06 .0 .540 8.94 15.80
00/04 .4106 5.97 7.5 4.24 .0 .537 9.05 17.55
00/05 .3506 12.27 23.2 2.97 .0 .511 7.80 23.95
00/06 .4617 20.80 30.6 4.56 5.9 .427 6.86 25.98
00/07 .4914 25.75 29.5 6.40 1.0 .477 6.65 27.12
00/08 .5287 6.06 5.8 3.55 .0 .420 5.78 26.60
00/09 .6480 4.77 4.7 2.86 .0 .362 6.82 22.95
00/10 .3613 4.60 6.8 1.85 .0 .388 9.85 17.30
00/11 .3396 4.00 7.7 2.27 .0 .388 9.42 12.40
00/12 .3797 3.82 16.4 1.63 1.0 .350 10.75 6.47
AVERAGE .4370 9.20 14.5 3.12 .6 .456 8.77 17.80
MAXIMUM 1.1000 35.00 48.0 8.25 39.0 1.100 14.90 28.50
MINIMUM .1560 2.50 2.0 .06 LESSTHAN .000 5.00 2.90
UNIT MGD MG/L MG/L MG/L #/100ML MG/L MG/L DEG.0
GKEX88/•MP •
COMPLIANCE EVALUATION ANALYSIS REPORT
04/19/2001
PAGE 2
PERMIT--NC0023353 PIPE--001
FACILITY --WHITE LAKE WWTP, TOWN OF
LOCATION --WHITE LAKE
00400 00600 00665
MONTH PH TOTAL N PHOS-TOT
LIMIT 9.0 6.0 NOL NOL
00/01 7.3-7.1 6.620 .9600
00/02 7.2-7.0
00/03 7.3-7.2
00/04 7.4-7.4 7.370 1.0700
00/05 7.6-7.4
00/06 7.5-7.2
00/07 7.4-7.3 24.060 2.9900
00/08 7.3-6.0
00/09 7.2-7.0
00/10 7.2-7.0 4.500 .9400
00/11 7.1-6.6
00/12 6.8-6.6
AVERAGE 10.637 1.4900
MAXIMUM 7.600 24.060 2.9900
MINIMUM 6.000 4.500 .9400
UNIT SU MG/L MG/L
REPORT PERIOD: 0001-0012 LOC---E
DESIGN FLOW-- .8000 CLASS--2
REGION/COUNTY--06 BLADEN