HomeMy WebLinkAboutNC0066788_Inspection_20200212United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 2 u 3 I NCO066788 111 121 20/02/12 I17 18 L e j 19 I s I 201
211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I n, I 73 � I 74 79 I I I I I I I80
70 I I 71 I LL -1 I I
LJ
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
10:55AM 20/02/12
16/01/01
Fairview Elementary School
1355 Charlotte Hwy
Exit Time/Date
Permit Expiration Date
Fairview NC 28730
12:30PM 20/02/12
20/12/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Clark Wyatt,175 Bingham Rd Asheville NC 28806/Maintenance
Director/828-232-4244/ Yes
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Operations & Maintenar 0 Facility Site Review 0 Effluent/Receiving Wate
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Linda S Wiggs Docusigned by: DWR/ARO WQ/828-296-4500 Ext.4653/
�.tin.o�c WlAga'
6C38CDE295CF449...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO066788 I11 12I 20/02/12 117 18 I s
(Cont.)
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Linda Wiggs, Inspector, met with Kevin Bryan ORC.
Facility has 5 months in 2019 with BOD violations. The inspection was conducted to discuss
compliance issues, conduct follow up with sampling and process control evaluations.
Process Control:
Pumper Truck Dates: 3/19/19, 3/22/19, 4/24/19, 7/3/19, 8/26/19 (3600 gallons each)
Settleability:
700 ml @ 10 min.
550 ml @ 30 min.
Supernatant clear.
Sludge Judge:
Clarifier - 1 st hopper — 7.5' blanket/9.5' liquid, 2nd hopper — 7.5' blanket/9.5' liquid.
Chlorine Contact Chamber — 1' blanket
ORC stated:
Air On 45 min./Off 15 min. Daytime
Air On 30 min./Off 30 min. Nighttime
RAS every other month
WAS monthly
Chlorination 1 tube, De -Chlorination 1.5 tube. ORC has adjusted these chemical levels to such
anticipating this correct the BOD issue.
MLSS Results: 4140 mg/1
Influent Sample Results:
BOD: 160 mg/I
Effluent Sample Results:
BOD: 23 mg/I
Corrosion of the WWTP remains a concern. Safety issue remains.
The culvert under the driveway is blocked, because of the blockage and recent rains the small stream
flooded overland and cause moderate erosion alongside the driveway. This culvert needs to be
cleaned out, otherwise this erosion will become severe.
While onsite an electrical component in the control box for the EQ caught fire. Note: Follow up
repair/replacement of these components took place.
Page#
Permit: NCO066788
Inspection Date: 02/12/2020
Owner -Facility: Fairview Elementary School
Inspection Type: Compliance Sampling
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: See summary.
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑