NORTH CAROLINA
Environmental Quality
December 21, 2020
CERTIFIED MAIL #: 7019 1120 0000 8361 1725
RETURN RECEIPT REQUESTED
Robert Hoyle, Director of Construction & Maintenance
Catawba County Schools
PO Box 1010
Newton, North Carolina 28658
Subject:
Dear Mr. Hoyle:
Notice of Violation/Notice of Recommendation
for Enforcement
Compliance Evaluation Inspection
Fred T. Foard High School WWTP
NPDES Permit No. NCO029297
Catawba County
Tracking #: NOV-2020-PC-0533
Enclosed is a copy of the Compliance Evaluation Inspection Report for the inspection conducted at the subject
facility on December 2, 2020, by Mr. Wes Bell of this Office. Please inform the facility's Operator -in -Responsible
Charge (ORC) of our findings by forwarding a copy of the enclosed report.
This report is being issued as a Notice of Violation (NOV)/Notice of Recommendation for Enforcement (NRE)
due to the following:
- High water alarm (audible and visual) did not properly operate (third consecutive inspection with this
violation);
- Flow measurements are not being performed properly (third consecutive inspection with this
violation);
- Inadequate disinfection during low flows (second consecutive inspection with this violation);
- Filter bed sand was bound with solids and clay/dirt (second consecutive inspection with this violation);
- Several lateral distribution sections were warped (second consecutive inspection with this violation).
Please be advised that these continued failures to properly maintain the wastewater treatment facility and
measure flow are violations of the subject NPDES Permit and North Carolina General Statute (G.S.) 143-215.1 as
detailed in the Sand Filter/Low Rate, Disinfection/Tablet and Flow Measurement Sections of the attached report.
Please be advised that G.S. 143-215.6A provides for a civil penalty assessment of not more than twenty-five
thousand dollars ($25,000.00), or twenty-five thousand dollars ($25,000.00) per day when the violation is of a
continuing nature, against any person who violates or fails to act in accordance with the terms, conditions, or
requirements of any permit issued pursuant to G.S. 143-215.1. Penalties may also be assessed for any damage to
surface waters of the State that may result from the violations.
�Office
Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
NOR7�CARCLINAI i
�,"rJ J m Em^'m'"^e^ai Qmli /`� 704.663.1699
Mr. Robert Hoyle
December 21, 2020
Page Two
This letter is also to advise you that this Office is considering the initiation of an enforcement action for
the violations of G.S. 143-215.1 and NPDES Permit No. NC0029297. If you have an explanation for the
violations that you wish to present, please include it in the written response. The written response and any
additional information (corrective actions, etc.) you wish to provide regarding these violations must be
received by this Office by January 11, 2021. In responding, please address your comments to the
attention of Mr. Wes Bell.
Should you have any questions concerning this letter, please do not hesitate to contact Mr. Bell at (704) 235-
2192, or via email at wes.bellgncdenr.gov.
Sincerely,
Docu Signed by:
4d4tV i1 PU4,f . for
F161FB69A2D84A3...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
Enclosure:
Inspection Report
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO029297 I11 121 20/12/02 I17 18I � I 19 I s I 201 I
211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
2.0 70LJ 71 I„ I 72 L71 74 79 I I I I
80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
12:46PM 20/12/02
20/09/01
Fred T. Foard High School
3407 Plateau Rd NCSR 2036
Exit Time/Date
Permit Expiration Date
Newton NC 28658
01:18PM 20/12/02
25/07/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Joshua Steven Greene/ORC/828-396-4444/
Morgan C Williams//828-464-3562 ext 403/8284654442
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Robert Hoyle,PO Box 1010 Newton NC 286581010/Director of Construction &
Maintenance/828-464-3562/8284654442 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Wes Bell signed by: DWR/MRO WQ/704-663-1699 Ext.2192/ 12/16/2020
2 re&
E�Docu`,','�96D90=437
...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Num erS Docusigned by: Date
Andrew Pitner DWR/MRO WQ/704-663-1699 Ext.2180/ A".4" H Nuft 12.21.2020
F161FB69A2D84A3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO029297 I11 12I 20/12/02 117 18 I c
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO029297 Owner - Facility: Fred T. Foard High School
Inspection Date: 12/02/2020 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
❑
0
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The last compliance evaluation inspection at this facility was performed by DWR staff on
10/2/18.
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operatc
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification'
❑
❑
❑
Is a copy of the current NPDES permit available on site?
0
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
0
❑
Page# 3
Permit: NCO029297
Inspection Date: 12/02/2020
Record Keeping
Owner - Facility: Fred T. Foard High School
Inspection Type: Compliance Evaluation
Yes No NA NE
Comment: The records reviewed durina the insDection were oraanized and well maintained. Discharae
Monitoring Reports (eDMRs) were reviewed for the period October 2019 through Septembel
2020. No effluent limit violations were reported and all monitoring frequencies were correct.
The ORC had mixed up the arrival times and collection and analysis times during effluent
sampling events. The ORC must ensure to properly document all self -monitoring data as
required by the subject permit. In addition, the ORC must also ensure that all operation and
maintenance activities (including activities performed by school staff) are documented.
The April, May and June 2020 eDMRs were not completed correctly to reflect the no flow
conditions at the facility during selected weeks/months. These eDMRs will be revised and
Laboratory
Yes
No
NA
NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
❑
0
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
0
❑
Comment: Effluent analyses (all permit -required parameters including field) are performed under Water
Tech Labs' certification #50.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment: The subject permit requires effluent grab samples.
Yes No NA NE
❑ ❑ ■ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Page# 4
Permit: NCO029297 Owner - Facility: Fred T. Foard High School
Inspection Date: 12/02/2020 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Comment: The facility was not being properly operated and maintained. Operational issues associated
with the high level alarm system has been noted in the previous two inspections (5/3/17 and
10/2/18). The tablet chlorination system not providing adequate disinfection during low flow:
was also noted in the previous inspection. The warped laterals and "spent" sand were also
noted in the complaint investigation (and resulting Notice of Violation) on 9/26/2019. The
permittee/School System has also failed to provide an adequate flow measurement
device/method as has been requested in the previous two inspections. Please see Sand
Filter/Low Rate, Disinfection/Tablet and Flow Measurement/Effluent Sections for additional
comments.
Septic Tank Yes No NA NE
(If pumps are used) Is an audible and visual alarm operational? ❑ ❑ MEI
Is septic tank pumped on a schedule? 0 ❑ ❑ ❑
Are pumps or syphons operating properly? M ❑ ❑ ❑
Are high and low water alarms operating properly? ❑ ❑ 0 ❑
Comment: The septic tank and recirculation tank are pumped out every summer by a contracted
company (Leatherman's Septic Tank Service). Sodium bicarbonate is added at the school
by custodial staff to maintain appropriate alkalinity/pH levels.
Sand Filters (Low rate)
Yes
No
NA NE
(If pumps are used) Is an audible and visible alarm Present and operational?
❑
0
❑
❑
Is the distribution box level and watertight?
❑
❑
0
❑
Is sand filter free of ponding?
❑
❑
❑
Is the sand filter effluent re -circulated at a valid ratio?
0
❑
❑
❑
# Is the sand filter surface free of algae or excessive vegetation?
0
❑
❑
❑
# Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1)
0
❑
❑
❑
Comment: The facility was not dosing at the time of the inspection.
The audible alarm did not work when activated by the test button and the alarms (audible
and visual) were not activated when the float was triggered. The alarm system must be
repaired/replaced. Several laterals were warped and the sand was bound with solids and
clay/dirt. All warped laterals must be replaced and all "spent" sand must be removed and
replaced with appropriately sized sand. Please be advised that the subject permit requires
the permittee to properly operate and maintain the facility at all times [Permit Condition
Reference: Part II, Section C(2) Proper Operation and Maintenancel. In addition, the ORC
must become familiar with all treatment components (including floats, etc.) at this facility.
Disinfection -Tablet Yes No NA NE
Are tablet chlorinators operational? ❑ 0 ❑ ❑
Are the tablets the proper size and type? 0 ❑ ❑ ❑
Number of tubes in use? 2
Page# 5
Permit: NCO029297
Inspection Date: 12/02/2020
Owner - Facility: Fred T. Foard High School
Inspection Type: Compliance Evaluation
Disinfection -Tablet
Yes
No
NA
NE
Is the level of chlorine residual acceptable?
❑
0
❑
❑
Is the contact chamber free of growth, or sludge buildup?
M
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
❑
0
❑
❑
Comment: Calcium hvDochlorite tablets are used for disinfection. No chlorine residual was detected in
the chlorine contact chamber. A two-inch gap was observed between the lowest tablet (in
the sleeves) and wastewater flow which prevented adequate disinfection during the lower
flow conditions. The facility must provide adequate disinfection during all flow conditions.
Please be advised that the subject permit requires the permittee to properly operate and
maintain the facility at all times [Permit Condition Reference: Part II, Section C(2) Proper
Operation and Maintenance].
De -chlorination
Yes No
NA
NE
Type of system ?
Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
0 ❑
❑
❑
Is storage appropriate for cylinders?
❑ ❑
0
❑
# Is de -chlorination substance stored away from chlorine containers?
❑ ❑
0
❑
Comment:
Are the tablets the proper size and type? 0 ❑ ❑ ❑
Are tablet de -chlorinators operational? 0 ❑ ❑ ❑
Number of tubes in use? 2
Comment: Sodium sulfite tablets are used for dechlorination.
Flow Measurement - Effluent
Yes
No
NA
NE
# Is flow meter used for reporting?
❑
0
❑
❑
Is flow meter calibrated annually?
❑
❑
0
❑
Is the flow meter operational?
❑
❑
0
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
MEI
Comment: The flows reported on the eDMRs (Dast and Dresent) were not based on an aDDroved flow
measurement device and/or method. Flows have been estimations and consistently
reported as low as 0.00006 mqd (60 gallons per day) prior to the June 2020 eDMR. A new
ORC was designated in June 2020 and the flows have been consistently estimated at 0.001
MGD (1,000 gallons per day). Please be advised that the permittee must select the
appropriate flow measurement devices and methods consistent with accepted scientific
practices to ensure the accuracy and reliability of measurements of the volume of monitored
discharges [Permit Reference: Part Il, Section D(3) Flow Measurements].
Effluent Pipe
Is right of way to the outfall properly maintained?
Yes No NA NE
■ ❑ ❑ ❑
Page# 6
Permit: NC0029297
Inspection Date: 12/02/2020
Effluent Pipe
Owner - Facility: Fred T. Foard High School
Inspection Type: Compliance Evaluation
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment: The effluent appeared clear with no floatable solids or foam.
Yes No NA NE
❑ ❑ ❑ ■
❑ ❑ ■ ❑
Page# 7