HomeMy WebLinkAboutNC0021962_Compliance Evaluation Inspection_20201221ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
S. DANIEL SMITH
Director
Jim Utke, Terminal Manager
CITGO Petroleum Corporation
Post Office Box 58
Paw Creek, North Carolina 28130
Dear Mr. Utke:
NORTH CAROLINA
Environmental Quality
December 21, 2020
Subject: Compliance Evaluation Inspection
CITGO — Charlotte Terminal
NPDES Permit No. NCO021962
Mecklenburg County
Enclosed is a copy of the Compliance Evaluation Inspection Report for the inspection conducted at the subject facility on
December 15, 2020, by Mr. Wes Bell of this Office. Please inform the facility's Operator -in -Responsible Charge (ORC) of
our findings by forwarding a copy of the enclosed report.
The report should be self-explanatory; however, should you have any questions concerning this report, please do
not hesitate to contact Mr. Bell at (704) 235-2192 or at wes.bell@ncdenr.gov.
Sincerely,
EA
DocuSigned by:
�r.�n.aty H Nuft for
F161 FB69A2D84A3...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, DEQ
Enclosure:
Inspection Report
D-;� North Carolina Department of Environmental Quality I Division of Water Resources
EMooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
NOR7H ORROLINA i
kmrl l m EnNromi W uwi` /`� 704.663.1699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO021962 I11 121 20/12/15 I17 18I � I 19 I s I 201 I
211IIIII 111111III II III III1 I I IIIII IIIIIIIII II r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
2.0 701d I 71 I„ I 72 I r., I 71 I 74 79 I I I I I I I80
L—I ty L-1 I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
09:15AM 20/12/15
15/09/01
Charlotte Terminal
7600 Mount Holly Rd
Exit Time/Date
Permit Expiration Date
Charlotte NC 28214
10:50AM 20/12/15
20/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Jim Utke//704-392-3236 /
Robert Edward Durham/ORC/704-392-3236/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Michael Santee,36th St Delaware River Box 655 Pennsauken NJ 08110/EHSS
Manager/856-952-0390/8569632587 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Wes Bell Signed by: DWR/MRO WQ/704-663-1699 Ext.2192/ 12/18/2020
2 re&
E�D`,','�96D90=437
...
Signature of M 'r�tWYA'Reviewer Agency/Office/Phone and Fax Numbers Date
[e�44"
Andrew Pit H P WR/MRO WQ/704-663-1699 Ext.2180/ 12.21.2020
F161FB69A2D84A3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO021962 I11 12I 20/12/15 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO021962 Owner -Facility: Charlotte Terminal
Inspection Date: 12/15/2020 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
❑
0
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The Division received the facility's permit renewal application on 12/3/19.
The last compliance evaluation inspection at this facility was performed by
Mecklenburg
Countv Stormwater Services staff on 8/29/18.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operatc
on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility classification
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
■
❑
❑
❑
❑
❑
■
❑
❑
❑
■
❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ■ ❑
Page# 3
Permit: NCO021962
Inspection Date: 12/15/2020
Owner -Facility: Charlotte Terminal
Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Comment: The records reviewed durina the insDection were oraanized and well maintained. Discharae
Monitoring Reports (eDMRs) were reviewed for the period September 2019 through Octobel
2020. No effluent limit violations were reported and all monitoring frequencies were correct.
The ORC and staff must ensure that the times for effluent sampling (at outfall), preservation
(transported samples put on ice) and sample relinquishment are properly documented.
Please note that all effluent samples must be preserved (chemically, on ice, etc.) within
15-minutes of sample collection (Reference: 40 CFR 136.3 Table II).
In addition, the ORC and staff must ensure to report all future effluent total recoverable
phenols down to the contracted lab's reporting limit (40 uq/L) and not the method detection
limit (8.3 ug/L). The contracted lab should be contacted to obtain a lower reporting limit (5
uq/L) for this parameter.
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
Comment: The on -site personnel (ORC and Backup ORC) collect all effluent samples. Pace Analytical
Services. Inc. has been contracted to Derform all effluent analvses.
Effluent Sampling
Yes
No
NA
NE
Is composite sampling flow proportional?
❑
❑
0
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
❑
❑
0
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
❑
0
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment: The subject permit requires effluent grab samples
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Page# 4
Permit: NCO021962 Owner -Facility: Charlotte Terminal
Inspection Date: 12/15/2020 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Comment: NPDES facilities appeared to be properly operated and well maintained. The secondary
containment dikes and valves, storage tanks, etc. are inspected daily (minimum) during all
business days. Any water (stormwater runoff, wash down water, etc.) from the truck
loading rack is collected and pumped into a storage tank for off -site disposal. Zebra
Environmental & Industrial Services has been contracted for the removal and disposal
(approximately 2-3 times per year) of the storage tank contents.
Although no effluent total suspended solids and turbidity violations have been reported, this
Office recommends the facility staff to apply a gravel/rock cover to the small areas of
exposed dirt observed within the secondary containment structure.
Flow Measurement - Effluent
Yes
No
NA NE
# Is flow meter used for reporting?
❑
❑
0 ❑
Is flow meter calibrated annually?
❑
❑
0 ❑
Is the flow meter operational?
❑
❑
0 ❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0 ❑
Comment: Effluent flows are based on a previously determined instantaneous flow rate and duration of
discharge. The facility staff should re -verify the flow rate to ensure accurate flow values are
being measured/reported.
Effluent Pipe
Yes
No
NA NE
Is right of way to the outfall properly maintained?
❑
❑
0 ❑
Are the receiving water free of foam other than trace amounts and other debris?
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0 ❑
Comment: The facility was not discharging at the time of the inspection. The manually operated
discharge valve was secured with a lock. The accumulated water inside the dike (near the
discharge outfall) appeared clear with no petroleum sheens.
Page# 5