HomeMy WebLinkAboutWQ0004230_Compliance Evaluation Inspection_20170921Water R esourc es
ENIVIRCINMENTAL QUALM
September 28, 2017
Walter Hancock
A Place at the Beach - Atlantic Beach III Inc HOA
1904 E Fort Macon Rd
Atlantic Beach, NC 28512
SUBJECT: Compliance Inspection Report
A Place at the Beach III WWTF
Non -discharge Permit No. WQ0004230
Carteret County
Dear Permittee:
ROY COOPER
GOVIR.-no-
'_vBCH A -EL S. REG-kN
SRC;'SYM7J
S. JAY ZL T-ER-Ni N,
Lirsclor
The North Carolina Division of Water Resources conducted an inspection of the A Place at the
Beach III WWTF on 9/21/2017. This inspection was conducted to verify that the facility is
operating in compliance with the conditions and limitations specified in Non -discharge Permit
No. WQ0004230. The findings and comments noted during this inspection are provided in the
enclosed copy of the inspection report entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a
response to this inspection report is not required.
If you should have any questions, please do not hesitate to contact Geoff Kegley with the
Water Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215
or via email at geoff.kegley@ncdenr.gov.
Sincerely,
Ja ems H. Gregson, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: Don O'Mara — ORC
Q1fV 45UVilmrl gto'n_RegiorJaJ Office
State of North Carolina I Environmental Quality I Water Resources
127 Cardinal Drive Extension, Wilmington, North Carolina 28405
910-796-7215
r
Compliance Inspection Report
Permit: WQ0004230 Effective: 11/13/06 Expiration: 10/31/15 Owner: A Place at the Beach - Atlantic Beach III Inc
HOA
SOC: Effective: Expiration: Facility: A Place at the Beach III WWTF
County: Carteret 1904 E Fort Macon Rd
Region: Wilmington
Atlantic Beach NC 285121011
Contact Person: Walter Hancock Title: General Manager Phone: 252-247-0906
Directions to Facility:
Take US 70 East to Morehead City. Take a right (south) onto Ocean Ridge Road. Turn left onto NC 58 and drive approximately 2
miles. Turn right into the complex (Sea Spray Way).
System Classifications: WW3•,
Primary ORC: Donald P Omara Certification: 7904 Phone: 252-247-9167
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Inspection Date: 09/21/2017 Entry Time: 11:OOAM
Primary Inspector: Geoff Kegley
Secondary Inspector(s):
Reason for Inspection: Routine
Permit Inspection Type: High Rate Infiltration
Facility Status: Compliant Not Compliant
Question Areas:
Exit Time: 12:30PM
Phone:
Inspection Type: Compliance Evaluation
Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent Miscellaneous Questions
Treatment Flow Measurement -Water Treatment Treatment Disinfection
Use Records
End Use -Infiltration Treatment Flow Measurement Standby Power
(See attachment summary)
Page: 1
Permit: WO0004230 Owner - Facility:A Place at the Beach - Atlantic Beach III Inc HOA
Inspection Date: 09/21/2017 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
This facility is currently deemed compliant under permit number W00004230.
The spray fields are in good condition with little vegetative growth.
Generator and automatic transfer switch were tested and were both functional.
Flow meter has been calibrated within the last 12 months.
Effluent is clear and odorless.
High water alarms were tested and were functional.
Some of the wells are subject to standing water after heavy rainfall events. MW-6 is a flush mount -well head and should be
checked to make sure the well seal is watertight. Ammonia has recently been detected in in 2 monitoring wells. It was
noted in the last groundwater monitoring report that insufficient water is being purged prior to sampling. A total of three (3)
well volumes should be purged from the well prior to sampling. For the depth and casing diameter of these wells, this
amounts to approximately 5.5 gallons of water.
Page: 2
Permit: WQ0004230
Inspection Date: 09/21/2017
Type
Reuse (Quality)
Single Family Spray, LR
Lagoon Spray, LR
Activated Sludge Spray, LR
Activated Sludge Spray, HR
Recycle/Reuse
Activated Sludge Drip, LR
Single Family Drip
Infiltration System
Owner -Facility: A Place at the Beach -Atlantic Beach III Inc HOA
Inspection Type : Compliance Evaluation Reason for Visit: Routine
Yes No .NA NE
El
El
El
El
El
Treatment
Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? ® ❑ ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) ®❑ ❑ ❑
Comment:
Treatment Flow Measurement -Influent
Yes No NA NE
Is flowmeter calibrated annually?
❑ ❑ ® ❑
Is flowmeter operating properly?
❑ ❑ 0 ❑
Does flowmeter monitor continuously?
❑ ❑ M ❑
Does flowmeter record flow?
❑ ❑ ■ ❑
Does flowmeter appear to monitor accurately?
❑ ❑ M ❑
Comment
Treatment Flow Measurement -Water Use Records Yes No NA NE
Is water use metered? ❑ ❑ ❑
Are the daily average values properly calculated? ❑ ❑ ❑
Comment:
Treatment Flow Measurement -Effluent
Yes No NA NE
Is flowmeter calibrated annually?
■ ❑ ❑ ❑
Is flowmeter operating properly?
0 ❑ ❑ ❑
Does flowmeter monitor continuously?
■ ❑ ❑ ❑
Does flowmeter record flown?
M ❑ ❑ ❑
Does flowmeter appear to monitor accurately?
0 ❑ ❑ ❑
Comment:
Standby Power Yes No NA NE
Is automatically activated standby power available? ® ❑ ❑ ❑
Page: 3
i
Permit: WQ0004230 Owner - Facility:A Place at the Beach - Atlantic Beach III Inc HOA
Inspection Date: 09/21/2017 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Is generator tested weekly by interrupting primary power source? ❑ ❑ ❑
Is generator operable? N ❑ ❑ ❑
Does generator have adequate fuel? ❑ ❑ ❑
Comment:
Treatment Disinfection
Yes No NA NE
Is the system working?
® ❑ ❑ ❑
Do the fecal coliform results indicate proper disinfection?
® ❑ ❑ ❑
Is there adequate detention time (-30 minutes)?
❑ ❑ ® ❑
Is the system properly maintained?
® ❑ ❑ ❑
If gas, does the cylinder storage appear safe?
❑ ❑ ® ❑
Is the fan in the chlorine feed room and storage area operable?
❑ ❑ ® ❑
Is the chlorinator accessible?
❑ ❑ ® ❑
If tablets, are tablets present?
❑ ❑ ® ❑
Are the tablets the proper size and type?
❑ ❑ E ❑
Is contact chamber free of sludge, solids, and growth?
❑ ❑ N ❑
If UV, are extra UV bulbs available?
❑ ❑ ❑
If UV, is the UV intensity adequate?
❑ ❑ ❑
# Is it a dual feed system?
N ❑ ❑ ❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
❑ ❑ ® ❑
If yes, then is there a Risk Management Plan on site?
❑ ❑ ® ❑
If yes, then what is the EPA twelve digit ID Number? (1000-
If yes, then when was the RMP last updated?
Comment:
End Use -Infiltration
Yes No NA NE
# Is the application High Rate or Low Rate?
High Rate
Are buffers maintained?
■ ❑ ❑ ❑
Are any supply wells within the CB?
❑ ❑ 0 ❑
Are any supply wells within 250' of the CB?
❑ ❑ 0 ❑
Is municipal water available in the area?
0 ❑ ❑ ❑
Are GW monitoring wells required?
0 ❑ ❑ ❑
Are GW monitoring wells located properly w/ respect to RB and CB?
❑ ❑ ❑ E
Are GW monitoring wells properly constructed, including screened interval?
❑ ❑ ❑
Is a usable green area maintained?
❑ ❑ ❑
Is the disposal site acceptable?
E ❑ ❑ ❑
Is the distribution equipment acceptable?
E ❑ ❑ ❑
Is the disposal site free of ponding?
N ❑ ❑ ❑
Page: 4
J
Permit: WQ0004230 Owner • Facility: A Place at the Beach -Atlantic Beach III Inc HOA
Inspection Date: 09/21/2017 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Is the disposal site free of breakout? E ❑ ❑ ❑
Are the disposal sites free of solids, algae, etc.? ® ❑ ❑ ❑
Do the records show that the fields are properly maintained? ❑ ❑ ❑ W
Are the disposal sites free of vegetation? ® ❑ ❑ ❑
Do any surface water features appear to be adversely impacted by GW discharge? ❑ ❑ ® ❑
No chemicals or rototiller used to eliminate vegetation, solids, algae, etc.? ❑ ❑ ❑
Comment:
Page: 5